HomeMy WebLinkAboutDERR-2024-008856PEI/RP1200 -19 pei.org56 APPENDIX C-6 OVERFILL ALARM OPERATION INSPECTION Facility Name:Owner: Address:Address: City, State, Zip Code:City, State, Zip Code: Facility I.D. #:Phone #: Testing Company:Phone #:Date: This procedure is to determine whether the high level alarm is operational and will trigger when the tank is no more than 90% full. See PEI/RP1200 Section 7.3 for the inspection procedure. This procedure is applicable to tank level monitor stems that touch the bottom of the tank when in place. Tank Number Product Stored Tank Level Monitor Brand and Model 1. Tank Volume, gallons 2. Tank Diameter, inches 3. Overfill alarm activates in the test mode at the console? Yes No Yes No Yes No Yes No 4. When activated, overfill alarm can be heard or seen while delivering to the tank? Yes No Yes No Yes No Yes No 5. After removing the probe from the tank, it has been inspected and any damaged or missing parts replaced? Yes No Yes No Yes No Yes No 6. Float moves freely on the stem without binding? Yes No Yes No Yes No Yes No 7. Moving product level float up the stem trigger alarm? Yes No Yes No Yes No Yes No 8. Inch level from bottom of stem when 90% alarm is triggered. 9. Tank volume at inch level in Line 8. 10. Calculate (Line 9 / Line 1) x 100 11. Is Line 10 less than 90%? Yes No Yes No Yes No Yes No 12. Fuel float level on the console agrees with the gauge stick reading? Yes No Yes No Yes No Yes No 13. Overfill alarm activates at any product level above 90% tank capacity? Yes No Yes No Yes No Yes No If any answers in Lines 3, 4, 5, 6, 7 or 11 are “No,” or Line 13 is “Yes,” the system has failed the test. Test Results Pass Fail Pass Fail Pass Fail Pass Fail Comments: Tester’s Name (print) ___________________________________ Tester’s Signature _________________________________