HomeMy WebLinkAboutDERR-2024-006920Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name STAKER PARSON MATERIALS AND
CONSTRUCTION
Address 89 WEST 13490 SOUTH, SUITE 100
DRAPER, UT 84020
Contact STAKER PARSON MATERIALS AND
CONSTRUCTION
Phone
Email christian.boudreau@stakerparson.com
TANK LOCATION
Name STAKER PARSON REDMOND # F480978
Address 408 W 100 S
REDMOND, UT 84652
A Operator None
Phone None
B Operator SAME
Phone SAME
Facility ID: 2000742 Inspection Date: 05/01/2024
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
1 - 1/2 No Jan. 1,
2009
None Yes No None None
TANK DETAILS
Tank ID/Alt ID 2 / 2
E-Gen/AST No / Yes
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Jan. 1, 2009 / 20000 /
Substance Stored Diesel / Diesel #2
(U.L.S.)
Tank Material-Mod Concrete-Double-Walled
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Bare Steel / None
Pipe type/STP Cont Safe Suction / No
STP Flex
Connectors Steel Flex in Sump
LLD Model
Spill/Overfill/Sm
Delivery
Dry Connect Fitting / Overfill
alarm / No
PST Fund/Other
Type No / Insurance
Tank/Pipe Rel Det TankATG PipeLineTightness
CP Tank Test None
CP Pipe Test None
INSPECTION COMMENTS
None
2024-05-01 Page 1 of 3
FACILITY RESPONSES
The above accurately represents the
facility's release detection records Yes
Financial Responsibility
Financial responsibility method is ok?Yes
TANK RESPONSES
Tank 2 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
DISPENSER RESPONSES
Dispenser 1/2
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
MONTHLY LEAK DETECTION MONITORING
May '23 Jun '23 Jul '23 Aug '23 Sep '23 Oct '23 Nov '23 Dec '23 Jan '24 Feb '24 Mar '24 Apr '24
Tank 2 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
NON-COMPLIANCE ITEMS
All items are in compliance.
2024-05-01 Page 2 of 3
Prepared by fueloperator.com
Inspection Information
Inspector:Warner, Sean
Record Created:May 1, 2024, 2:39 p.m.
Inspection Date:May 1, 2024
2024-05-01 Page 3 of 3