HomeMy WebLinkAboutDAQ-2024-0042711
DAQC-037-24
Site ID 10264 (B4)
MEMORANDUM
TO: STACK TEST FILE – MID-AMERICA PIPELINE COMPANY, LLC – Moab
Pump Station
THROUGH: Rik Ombach, Minor Source Oil and Gas Compliance Section Manager
FROM: Paul Bushman, Environmental Scientist
DATE: January 11, 2024
SUBJECT: Sources: One (1) Solar Saturn 20 Unit ID: T2
Contact: Patrick Abbot: 970-263-3016
Location: Remote location 8 miles south of Moab, Grand County, Utah
Test Contractor: Oasis Emissions Consultants, Inc.
Permit/AO#: DAQE-AN102640004-07, dated January 5, 2007
Action Code: TR
Subject: Review of stack test report received January 9, 2024
On January 9, 2024, Utah Division of Air Quality (DAQ) received a test report for a Solar Saturn 20 Unit
ID: T2 at Moab Pump Station in Grand County, Utah. Testing was performed on November 14, 2023, to
demonstrate compliance with the emission limits found in Conditions 10 and 11 of the Approval Order
DAQE-AN102640004-07, dated January 5, 2007, and the emission limits found in 40 CFR 60 subpart
KKKK. The calculated test results are:
Source Test Date Pollutant Method Tester Results DAQ Results Limits
Solar Saturn 20
Unit ID: T2
SN: 20548
November
14, 2023
NOx 7E
53.87 ppmvd @
15% O2
54.050 ppmvd
@ 15% O2
100 ppmvd
@ 15% O2
2.30 lb/hr 2.301 lb/hr 2.3 lb/hr
CO 10
47.27 ppmvd @
15% O2
47.374 ppmvd
@ 15% O2
120 ppmvd
@ 15% O2
1.23 lb/hr 1.228 lb/hr 4.38 lb/hr
DEVIATIONS: None.
CONCLUSION: The stack test report for the Solar Saturn 20 Unit ID: T2 appears to be
acceptable.
RECOMMENDATION: The emissions from the Solar Saturn 20 Unit ID: T2 should be
considered to have been in compliance with the emission limits found in
the AO and in 40 CFR 60 subpart KKKK during the stack test.
ATTACHMENTS: DAQ stack test review excel spreadsheets, Mid-America Pipeline
Company, LLC stack test report.
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66