Loading...
HomeMy WebLinkAboutDAQ-2024-004791 1 DAQC-138-24 Site ID 10238 (B5) MEMORANDUM TO: FILE – PACIFICORP HUNTINGTON POWER PLANT THROUGH: Harold Burge, Major Source Compliance Section Manager FROM: Rob Leishman, Environmental Scientist DATE: February 13, 2024 SUBJECT: PacifiCorp Huntington Power Plant (Huntington), Major, NSPS, Title V, Emery County FRS # UT00000049001501001 INSPECTION TYPE: State Electronic Data Report (SEDR) Review REVIEW DATE: February 13, 2024 SOURCE LOCATION: Huntington Canyon/Emery County SOURCE CONTACT: Russ Wilson - 435-687-4331 APPLICABLE REGULATIONS: Title V Operating Permit PERMIT NUMBER: 1501001005 DATE OF PERMIT: January 22, 2020 Date of Last Revision: August 26, 2021 SOURCE INSPECTION EVALUATION: With the exception of sources that only monitor for opacity, quarterly report memoranda will only address the findings of the quarterly report. Approval Order and Title V permit conditions addressing continuous emission monitoring requirements will be addressed in Huntington’s relative accuracy performance specification test review memorandum. SOURCE REVIEW EVALUATION: Fourth Quarter 2023 % Monitor Availability (MA) Performance Test Dates (N/A to Opacity) Summary of Excess Emissions During Point Source Operation Point Source Op. hrs. Channel MA CGA Lin RATA Point Source Channel Hrs. Limitation 1 2208 SO2 100% 10/04/23 04/13/23 1 SO2 0.00 0.12 lb/MMBtu - 30 DRA 1 2208 NOx 100% 10/04/23 04/13/23 1 SO2 0.00 595 (lb/hr) - 30 DRA 1 8 2 2 Fourth Quarter 2023 % Monitor Availability (MA) Performance Test Dates (N/A to Opacity) Summary of Excess Emissions During Point Source Operation Point Source Op. hrs. Channel MA CGA Lin RATA Point Source Channel Hrs. Limitation 1 2208 CO2 100% 10/04/23 04/13/23 1 SO2 0.00 0.2 lb/MMBtu - 30 DRA 1 2208 Opacity 100% 1 NOx 0.00 0.26 lb/MMBtu - 30 DRA 1 2208 CO 100% 10/09/23 04/13/23 1 NOx 0.00 1290 (lb/hr) - 30 DRA 2 1697 SO2 99% 11/01/23 04/14/23 1 Opacity 0.00 20 Percent - 6 min 2 1697 NOx 98% 11/01/23 04/14/23 1 CO 0.00 0.34 lb/MMBtu - 30 DRA 2 1697 CO2 100% 11/01/23 04/14/23 1 CO 0.00 1686 (lb/hr) - 30 DRA 2 1697 Opacity 99% 2 SO2 0.00 0.12 lb/MMBtu - 24 hr Block 2 SO2 0.00 0.2 lb/MMBtu - 30 DRA 2 NOx 0.00 0.26 lb/MMBtu - 30 DRA 2 Opacity 0.00 20 Percent - 6 min Excess Emission Report - Hourly Summary Point Source Channel Startup & Shutdown Control Equipment Problems Process Problems Other Known Causes Unknown Causes Emission Limit 1 SO2 0 0 0 0 0 0.12 lb/MMBtu - 30 DRA 1 SO2 0 0 0 0 0 595 (lb/hr) - 30 DRA 1 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA 1 NOx 0 0 0 0 0 0.26 lb/MMBtu - 30 DRA 1 NOx 0 0 0 0 0 1290 (lb/hr) - 30 DRA 1 Opacity 0 0 0 0 0 20 Percent - 6 min 1 CO 0 0 0 0 0 0.34 lb/MMBtu - 30 DRA 1 CO 0 0 0 0 0 1686 (lb/hr) - 30 DRA 2 SO2 0 0 0 0 0 0.12 lb/MMBtu - 24 hr Block 2 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA 2 NOx 0 0 0 0 0 0.26 lb/MMBtu - 30 DRA 2 Opacity 0 0 0 0 0 20 Percent - 6 min 3 CMS Performance Summary - Hourly Summary Point Source Channel Monitor Malfunction Non-monitor Malfunction QA Calibrations Other Known Causes Unknown Causes 1 SO2 2 0 0 0 0 1 NOx 0 0 0 0 0 1 CO2 8 0 0 0 0 1 Opacity 0 0 10 0 0 1 CO 0 0 0 0 0 2 SO2 0 4 6 0 0 2 NOx 0 0 0 30 0 2 CO2 0 2 0 3 0 2 Opacity 0 0 9 0 0 Type Code 280 (COMS Attenuator Filters) Procedure 3 Point Source & Location Attenuator I.D. Attenuator Certification Date Certified Attenuator Opacity OPLR, SECR, or PLCF, Corrected Opacity Value Range Low, Mid, & High Certification 1-year or 5- year 1 - A ZN-47 4/20/23 13.60 0.63 16.82 L 1 1 - A YN-39 4/20/23 18.90 0.63 23.28 M 1 1 - A TX-32 4/20/23 36.70 0.63 43.83 H 1 1 - B ZN-47 4/20/23 13.60 0.63 16.82 L 1 1 - B YN-39 4/20/23 18.90 0.63 23.28 M 1 1 - B TX-32 4/20/23 36.70 0.63 43.83 H 1 2 - 2 ZP-04 4/20/23 29.60 0.25 15.81 L 1 2 - 2 ZR-19 4/20/23 43.70 0.25 24.55 M 1 2 - 2 TX-33 4/20/23 59.20 0.25 35.54 H 1 Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error) Point Source Location Audit Date Opacity Monitor Response (Average of 5) Mean Difference Calibration Error (≤ 3%) Low Mid High 1 A 12/13/23 18 0.880 1.000 1 A 12/13/23 24 1.020 1.000 1 A 12/13/23 45 1.150 1.000 1 B 11/30/23 16 -0.740 1.000 1 B 11/30/23 23 -0.580 1.000 1 B 11/30/23 44 -0.330 2 2 12/1/23 16 0.390 2 2 12/1/23 25 0.150 2 2 12/1/23 35 -0.440 4 Type Code 282 (Annual Zero Alignment Audit) Procedure 3 Point Source Location Audit Date Alternative Zero Alignment (Yes or No) COM Clear Condition Zero Response (CCZR) COM Simulated Zero Response (CSZR) Zero Alignment Error Difference (CCZR)- (CSZR) Adjustment to COM Simulated Zero Response (CSZR) (Yes or No) 1 A 12/13/23 yes 0.08 0 0 yes 1 B 11/30/23 yes -0.01 0 0 yes 2 2 12/1/23 yes 0.20 0 0 yes Pollutant Concentration Exceeded Span of CEM Monitor Outage During Point Source Operation Alternate Sampling CEM Modifications 0 Hours 49 Hours 0 Hours 0 Events SOURCE INSPECTION SUMMARY EVALUATION: Huntington maintains its CEMS as required in R307-170 and 40 CFR 60.13. CURRENT RECOMMENDATIONS: All deviations appear to be a result of breakdown or process related problems that do not warrant issuing a violation. Huntington was in compliance during this reporting period. No further compliance action is recommended. Huntington’s NSPS monitoring system meets the performance standards of 40 CFR 60, Appendix B Performance Specifications. Huntington’s acid rain monitoring system meets the performance standards of 40 CFR 75 Acid Rain Performance Specifications. Periods of excess emissions that were recorded by the CMS in service on each point source during this reporting period are summarized in the SEDR and described in Pivot Table 400 “Excess Emissions Review.” HIGH PRIORITY VIOLATOR (HPV): No. RECOMMENDATION FOR NEXT INSPECTION: Check DAS for daily zero and span drift. Check the QC program to ensure that monitor drift is being tracked that the source can identify excessive drift. ATTACHMENTS: Excel spreadsheet review. Huntington EER 4Q2023 Point Source Information Late Expired Cal. Gas Valid Cal. Gas Days Yes No 1 Type Code 100 (Company Information)Type Code Company Manager Company Name AIRS # Phone Number Environmental Contact 1 100 Laren Huntsman 01501001 435-687-4000 Russ Willson 1 100 0 0 0 0 1 Type Code 110 (Point Source Identification)Type Code Point Source Quarter 1 - 4 Year Point Source Operating Hrs. in Quarter 1 110 4 2023 2208 1 110 4 2023 1697.4 1 110 0 0 0 1 Type Code 200 (Monitor Identification)Type Code Point Source Channel Manufacturer Model No. Monitor SN Low Span High Span Installation Date Monitor Location 1 200 CO THERMO 48iQ-ACN 12108511485 0 1000 6/15/2021 Stack 1 200 CO2 THERMO 410iQ-ACN 12108511478 0 20 6/15/2021 Stack 1 200 NOx THERMO 42iQ-ACANN 12108511481 0 400 6/15/2021 Stack 1 200 Opacity Land Instr. 4500 MkIII 232342 81 0 100 10/11/2018 Scrubber Inlet Duct A - stack 1 200 Opacity Land Instr. 4500 MkIII 236573 83 0 100 10/11/2018 Scrubber Inlet Duct B - stack 1 200 SO2 THERMO 43iQ-ACN 12108511483 0 800 6/15/2021 Stack 1 200 CO2 THERMO 410iQ-ACN 12108511479 0 20 6/17/2021 Stack 1 200 NOx THERMO 42iQ-ACANN 12108511480 0 400 6/17/2021 Stack 1 200 Opacity Land Instr. 4500 MkIII 241977 92 0 100 10/15/2019 Inlet Duct - 1 200 SO2 THERMO 43iQ-ACN 12108511482 0 800 6/17/2021 Stack 1 200 0 0 0 0 0 0 1/0/1900 0 1 Type Code310 (Excess Emissions) SUMMARY REPORT Type Code Channel Total Hours of Excess Emissions Excess Emissions - % of Total Operating Hours RC 701 Hours - start up/Shutdown RC 702 Hours- Control Equipment Problems RC 703 Hours - Process Problems RC 704, 706, 707 Hours -Other Known Causes RC 705 Hours - Unknown Causes Emission Limitation Emission Limitation Units Emission Limitation Averaging Period 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 595 (lb/hr) 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.26 lb/MMBtu 30 DRA 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 1290 (lb/hr) 30 DRA 1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 0.34 lb/MMBtu 30 DRA 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 1686 (lb/hr) 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 24 hr Block 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.26 lb/MMBtu 30 DRA 1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min 1 310 0 0 0 0 0 0 0 0 0 1 Type Code 300 (CMS Performance Summary) Type Code Channel Point Source Operating Hours Downtime - % of Total Operating Hours Total CMS Downtime RC 721 Hours - Monitor Malfunction RC 722 Hours - Non-monitor Malfunction RC 723 Hours - QA Calibrations RC 724 Hours - Other Known Causes RC 725 Hours - Unknown Causes 1 TRUE 300 SO2 2208 0.09% 2 2 0 0 0 0 1 TRUE 300 NOx 2208 0.00% 0 0 0 0 0 0 1 TRUE 300 CO2 2208 0.36% 8 8 0 0 0 0 1 TRUE 300 Opacity 2208 0.46% 10.05 0 0.2 9.85 0 0 1 TRUE 300 CO 2208 0.00% 0 0 0 0 0 0 1 TRUE 300 SO2 1697.4 0.58% 9.9 0 4 5.9 0 0 1 TRUE 300 NOx 1697.4 1.76% 29.9 0 0 0 29.9 0 1 TRUE 300 CO2 1697.4 0.29% 5 0 2 0 3 0 1 TRUE 300 Opacity 1697.4 0.53% 9.08 0 0.1 8.98 0 0 1 300 0 0 0 0 0 0 1 Type Code 250 (Performance Specification RATA Results) Type Code Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units of Measurement CEM Value Reference Method Value Relative accuracy Pass/ Fail 1 262 Days 250 SO2 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil. 0.057 0.061 9.60% Pass 1 262 Days 250 NOx 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil. 0.204 0.197 4.40% Pass 1 262 Days 250 CO2 04/13/23 07/25/22 8.61 Percent 10.8 11 3.10% Pass 1 262 Days 250 CO 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil. 0.169 0.171 4.00% Pass 1 262 Days 250 CO 04/13/23 07/25/22 8.61 #/hr 770.9 823.2 9.70% Pass 1 289 Days 250 CO2 04/14/23 06/29/22 9.5 Percent 10.7 10.5 3.10% Pass 1 289 Days 250 NOx 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil. 0.228 0.225 2.00% Pass 1 289 Days 250 SO2 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil. 0.074 0.074 0.50% Pass 1 0 Days 250 0 01/00/00 01/00/00 0 0 0 0 0.00% 0 1 1 1 1 2 1 2 0 0 PacifiCorp Huntington 0 1 1 1 1 1 1 2 2 2 2 0 1 1 1 2 2 1 1 1 1 1 1 1 2 2 2 2 2 1 1 1 2 2 0 1 2 0 Point Source Point Source Point Source Huntington EER 4Q2023 1 Type Code 260 (CGA Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 Valid Cal. Gas 260 CO 10/09/23 low DT0008703 06/11/24 0 ppm 234.4 242 -3.20% Pass 0 1 Valid Cal. Gas 260 CO 10/09/23 mid CC82604 09/22/26 0 ppm 545.9 543 0.50% Pass 0 1 260 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 270 (Linearity Test Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 Valid Cal. Gas 270 CO2 10/04/23 low DT0035319 04/05/30 P1 percent 5 5 0.00% Pass 0 1 Valid Cal. Gas 270 CO2 10/04/23 mid DT0045304 05/30/31 P1 percent 11.1 11 0.90% Pass 0 1 Valid Cal. Gas 270 CO2 10/04/23 high SA12912 02/04/30 P1 percent 18.1 18.1 0.00% Pass 0 1 Valid Cal. Gas 270 NOx 10/04/23 low DT0035319 04/05/30 P1 ppm 101.8 100.9 1% Pass 0 1 Valid Cal. Gas 270 NOx 10/04/23 mid DT0045304 05/30/31 P1 ppm 221.4 220 1% Pass 0 1 Valid Cal. Gas 270 NOx 10/04/23 high SA12912 02/04/30 P1 ppm 359.8 363 1% Pass 0 1 Valid Cal. Gas 270 SO2 10/04/23 low DT0035319 04/05/30 P1 ppm 206 199.9 3.00% Pass High 1 Valid Cal. Gas 270 SO2 10/04/23 mid DT0045304 05/30/31 P1 ppm 435.6 434 0.40% Pass High 1 Valid Cal. Gas 270 SO2 10/04/23 high SA12912 02/04/30 P1 ppm 685.8 705 2.70% Pass High 1 Valid Cal. Gas 270 CO2 11/01/23 low DT0035319 04/05/30 P1 percent 4.9 5 2.70% Pass 0 1 Valid Cal. Gas 270 CO2 11/01/23 mid DT0046865 05/30/31 P1 percent 11 11 0.00% Pass 0 1 Valid Cal. Gas 270 CO2 11/01/23 high SA12912 02/04/30 P1 percent 18.3 18.1 1.10% Pass 0 1 Valid Cal. Gas 270 NOx 11/01/23 low DT0035319 04/05/30 P1 ppm 101.4 100.9 0.50% Pass 0 1 Valid Cal. Gas 270 NOx 11/01/23 mid DT0046865 05/30/31 P1 ppm 221.4 220 0.70% Pass 0 1 Valid Cal. Gas 270 NOx 11/01/23 high SA12912 02/04/30 P1 ppm 359 363 1.10% Pass 0 1 Valid Cal. Gas 270 SO2 11/01/23 low DT0035319 04/05/30 P1 ppm 206.5 199.9 3% Pass High 1 Valid Cal. Gas 270 SO2 11/01/23 mid DT0046865 05/30/31 P1 ppm 433.5 434 0% Pass High 1 Valid Cal. Gas 270 SO2 11/01/23 high SA12912 02/04/30 P1 ppm 689.9 705 2% Pass High 1 270 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code Channel Start Date Start Time End Date End Time Hours 1 0 0 0 1/0/00 0:00 1/0/00 0:00 1 1 None Reported 1 0 TC 220 Hours 49.40 TC 220 Hours 0.00 TC 230 Hours 0.00 Events 0.00 Hours 0.00 Events 0.00 0.00 1 73.93 TC 300 Hours 24.53 FALSE 0 2 0 1 1 1 1 2 1 1 1 1 1 2 2 2 2 0 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code 220 (Monitor Outage During Point Source Operation) Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) Type Code 240 (CEM Modifications) Type Code 530 (Excess Emissions During Emergency Conditions) Type Code 450 (Data Excluded) Type Code 550 (Changes in Operation in Control Equipment When CEM Data Not Available) Type Code 500 (Boiler Operating Days w/o 18 Hours of Data) 1 1 Point Source Point Source Point Source Yes None Reported None Reported None Reported None Reported None Reported None Reported 2 2 2 Huntington EER 4Q2023 Relative Accuracy Overview Point Source Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units Measured CEM Value Reference Method Value Relative Accuracy Pass/ Fail 2023 1 SO2 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil.0.057 0.06 9.60% Pass 1 NOx 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil.0.204 0.20 4.40% Pass 1 CO2 04/13/23 07/25/22 8.61 Percent 10.8 11.00 3.10% Pass 1 CO 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil.0.169 0.17 4.00% Pass 1 CO 04/13/23 07/25/22 8.61 #/hr 770.9 823.20 9.70% Pass 2 CO2 04/14/23 06/29/22 9.5 Percent 10.7 10.50 3.10% Pass 2 NOx 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil.0.228 0.23 2.00% Pass 2 SO2 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil.0.074 0.07 0.50% Pass * NSPS CGA Fourth 2023 Audit Gas Ranges Audit Gas Ranges AP1 Low AP2 Low AP1 High AP2 High 1 CO 10/9/23 1000 242 200 to 300 1 CO 10/9/23 1000 543 500 to 600 * Acid Rain Audit Linearity Fourth 2023 Low Span Gas Ranges High Span Gas Ranges Low Mid High Low Mid High 1 CO2 10/4/23 20 5 4 to 6 1 CO2 10/4/23 20 11 10 to 12 1 CO2 10/4/23 20 18.1 16 to 20 1 NOx 10/4/23 400 100.9 80 to 120 1 NOx 10/4/23 400 220 200 to 240 1 NOx 10/4/23 400 363 320 to 400 1 SO2 10/4/23 800 199.9 160 to 240 1 SO2 10/4/23 800 434 400 to 480 1 SO2 10/4/23 800 705 640 to 800 2 CO2 11/1/23 20 5 4 to 6 2 CO2 11/1/23 20 11 10 to 12 2 CO2 11/1/23 20 18.1 16 to 20 2 NOx 11/1/23 400 100.9 80 to 120 2 NOx 11/1/23 400 220 200 to 240 2 NOx 11/1/23 400 363 320 to 400 2 SO2 11/1/23 800 199.9 160 to 240 2 SO2 11/1/23 800 434 400 to 480 2 SO2 11/1/23 800 705 640 to 800 * Type Code 280 (COMS Attenuator Filters) Procedure 3 Point Source Location Attenuator I.D. Attenuator Certification Date Certified Attenuator Opacity OPLR, SECR, or PLCF, Corrected Opacity Value Range Low, Mid, & High Certification 1-year or 5-year 1 A ZN-47 4/20/23 14 0.632 16.82 L 1 1 A YN-39 4/20/23 19 0.632 23.28 M 1 1 A TX-32 4/20/23 37 0.632 43.83 H 1 1 B ZN-47 4/20/23 13.6 0.632 16.82 L 1 1 B YN-39 4/20/23 18.9 0.632 23.28 M 1 1 B TX-32 4/20/23 36.7 0.632 43.83 H 1 2 2 ZP-04 4/20/23 29.6 0.245 15.81 L 1 2 2 ZR-19 4/20/23 43.7 0.245 24.55 M 1 2 2 TX-33 4/20/23 59.2 0.245 35.54 H 1 * Opacity Monitor Response (Average of 5) Low Range Mid Range High Range 1 A 12/13/23 18 0.880 0.010 0.000 1.000 1 A 12/13/23 24 1.020 0.130 0.000 1.000 1 A 12/13/23 45 1.150 0.030 0.070 1.000 1 B 11/30/23 16 -0.740 0.140 0.360 1.000 1 B 11/30/23 23 -0.580 0.000 0.000 1.000 1 B 11/30/23 44 -0.330 0.000 0.000 0.000 2 2 12/1/23 16 0.390 0.000 0.000 0.000 2 2 12/1/23 25 0.150 0.000 0.000 0.000 2 2 12/1/23 35 -0.440 0.000 0.000 0.000 * Point Source Location Audit Date Alternitive Zero Alignment (Yes or No) COM Clear Condition Zero Response (CCZR) COM Simulated Zero Response (CSZR) Zero Alignment Error Difference (CCZR)-(CSZR) Adjustment to COM Simulated Zero Response (CSZR) (Yes or No) 1 A 12/13/23 yes 0.080 0.000 0.080 yes 1 B 11/30/23 yes -0.010 0.000 -0.010 yes 2 2 12/1/23 yes 0.200 0.000 0.200 yes Audit Gas Used High Span Audit Gas Used High SpanAudit Gas Used Point Source Channel Audit Date Low Span Point Source Channel Audit Date Low Span Type Code 282 (Procedure 3 - Annual Zero Alignment Audit) Audit Gas Used Point Source Location Audit Date Mean Difference Standard Deviation Confidence Coefficient Calibration Error (≤ 3%) Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error) Huntington EER 4Q2023 Monitoring Information TC 210, 230, & 240 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank)0 0 Grand Total 0 0 * Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank)0 0 Grand Total 0 0 * Type Code 240 (CEM Modifications) - 100 (All) * Count of Channel Column Labels Row Labels (blank) Grand Total (blank) (blank) Grand Total Huntington EER 4Q2023 Type Code 220 (Monitor Outage During Point Source Operation) - 600 (All) * Sum of Hours Column Labels Row Labels 723 722 721 724 Grand Total 1 Opacity The monitor was unavailable during the daily monitor calibration as required by 40 CFR parts 60 and 75.7.67 7.67 A loss/interuption of power or communication to the DCS and/or monitor resulted in a loss of data. Power/communication was restored and the monitor was returned to service. 0.17 0.17 An opacity monitor filter check and/or audit was conducted followed by a manual calibration.2.37 2.37 SO2 The analyzer stopped collecting valid data (went to data error), Could not see any problems or the analyzer temporarily exceeded its span; powered down the analyzer and then back up; analyzer started collecting valid data again after emissions were within range. 1.98 1.98 CO2 The monitor failed its daily calibration drift test by more than 4 times the performance specification. The monitor was cleaned/inspected/ recalibrated and returned to service. 7.98 7.98 2 Opacity The monitor was unavailable during the daily monitor calibration as required by 40 CFR parts 60 and 75.5.83 5.83 A loss/interuption of power or communication to the DCS and/or monitor resulted in a loss of data. Power/communication was restored and the monitor was returned to service. 0.08 0.08 An opacity monitor filter check and/or audit was conducted followed by a manual calibration.1.28 1.28 Monitor critical orifices and/or lenses were cleaned and/or replaced and inspected. The monitor was then returned to service after a successful calibration error test 0.38 0.38 A post outage start-up calibration was performed.0.83 0.83 SO2 A loss/interuption of power or communication to the DCS and/or monitor resulted in a loss of data. Power/communication was restored and the monitor was returned to service. 1.98 1.98 Monitor was not calibrated timely after startup of unit after outage. Calibration followed and system restored.2.97 2.97 A daily calibration reference gas bottle was empty, resulting in a calibration fail out of control indication. The bottle was changed and a second calibration initiated. 2.98 2.98 CO2 A loss/interuption of power or communication to the DCS and/or monitor resulted in a loss of data. Power/communication was restored and the monitor was returned to service. 1.98 1.98 Monitor was not calibrated timely after startup of unit after outage. Calibration followed and system restored.2.97 2.97 NOx A loss/interuption of power or communication to the DCS and/or monitor resulted in a loss of data. Power/communication was restored and the monitor was returned to service. 1.98 1.98 Monitor was not calibrated timely after startup of unit after outage. Calibration followed and system restored.2.97 2.97 A daily calibration reference gas bottle was empty, resulting in a calibration fail out of control indication. The bottle was changed and a second calibration initiated. 2.98 2.98 Grand Total 18.37 6.20 9.97 14.87 49.40 Huntington EER 4Q2023 Opy * Opy Count of Magnitude of Emissions Column Labels Opy Row Labels Grand Total Opy Grand Total SO2 * SO2 Type Code 410 (SO2) - 6000 (All) SO2 * SO2 Count of Magnitude of Emissions Column Labels SO2 Row Labels Grand Total SO2 Grand Total NOx * NOx Type Code 420 (NOx) - 6000 (All) NOx * NOx Count of Magnitude of Emissions Column Labels NOx Row Labels Grand Total NOx Grand Total NOx d * NOx d Type Code 421 (Daily NOx Emissions) - 500 (All) NOx d * NOx d Count of Reason Code Column Labels NOx d Row Labels 701 Grand Total NOx d 2 NOx d The unit was removed from service in a controlled fasion for a planned overhaul.16 16 NOx d The unit was removed from service in a controlled fashion in order to conduct maintenance. The maintenance was completed and the unit was returned to service. 2 2 NOx d Grand Total 18 18 CO * CO Type Code 440 (CO) - 6000 (All) CO * CO Count of Magnitude of Emissions Column Labels CO Row Labels Grand Total CO Grand Total Huntington EER 4Q2023 Type Code 500 Before February 28, 2005 (Boiler Operating Days w/o 18 Hours of Data) After February 28, 2005 (90% Operating Hours For each 30 BOD) - 500 (All) * Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 510 (F-factor, Equations & Conversion Factors) - 500 (All) Count of F-factor Column Labels Row Labels Grand Total Grand Total * Type Code 520 (Minimum Data Not Obtained <22/30 BODs) - 500 (All) Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 530 (Excess Emissions During Emergency Conditions) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * Type Code 540 (Fuel Pre-treatment Credit SO2) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * TypeCode 550 (Changes in Operation in Control Equipment When CEM Data Not Available) - 500 (All) Column Labels Row Labels Grand Total Grand Total