HomeMy WebLinkAboutDAQ-2024-007732
1
DAQC-402-24
Site ID 10238 (B5)
MEMORANDUM
TO: FILE – PACIFICORP HUNTINGTON POWER PLANT
THROUGH: Harold Burge, Major Source Compliance Section Manager
FROM: Rob Leishman, Environmental Scientist
DATE: April 30, 2024
SUBJECT: PacifiCorp Huntington Power Plant (Huntington), Major, NSPS, Title V,
Emery County FRS #UT00000049001501001
INSPECTION TYPE: State Electronic Data Report (SEDR) Review
REVIEW DATE: April 30, 2024
SOURCE LOCATION: Huntington Canyon/Emery County
SOURCE CONTACT: Russ Wilson - 435-687-4331
APPLICABLE
REGULATIONS: Title V Operating Permit
PERMIT NUMBER: 1501001005
DATE OF PERMIT: January 22, 2020
Date of Last Revision: August 26, 2021
SOURCE INSPECTION
EVALUATION: With the exception of sources that only monitor for opacity, quarterly
report memoranda will only address the findings of the quarterly report.
Approval Order and Title V permit conditions addressing continuous
emission monitoring requirements will be addressed in Huntington’s
relative accuracy performance specification test review memorandum.
SOURCE REVIEW EVALUATION:
First Quarter 2024
% Monitor Availability (MA) Performance Test Dates
(N/A to Opacity)
Summary of Excess Emissions During
Point Source Operation
Point
Source
Op.
hrs. Channel MA CGA Lin RATA Point
Source Channel Hrs. Limitation
1 2184 SO2 100% 01/17/24 04/13/23 1 SO2 0.00 0.12 lb/MMBtu
- 30 DRA
1 2184 NOx 100% 01/17/24 04/13/23 1 SO2 0.00 595 (lb/hr) - 30
DRA
1 2184 CO2 100% 01/17/24 04/13/23 1 SO2 0.00 0.2 lb/MMBtu -
30 DRA
1 2184 Opacity 99% 1 NOx 0.00 0.26 lb/MMBtu
- 30 DRA
1 8 2
2
First Quarter 2024
% Monitor Availability (MA) Performance Test Dates
(N/A to Opacity)
Summary of Excess Emissions During
Point Source Operation
Point
Source
Op.
hrs. Channel MA CGA Lin RATA Point
Source Channel Hrs. Limitation
1 2184 CO 100% 01/18/24 04/13/23 1 NOx 0.00 1290 (lb/hr) -
30 DRA
2 2184 SO2 100% 01/24/24 04/14/23 1 Opacity 0.00 20 Percent - 6
min
2 2184 NOx 100% 01/24/24 04/14/23 1 CO 0.00 0.34 lb/MMBtu
- 30 DRA
2 2184 CO2 100% 01/24/24 04/14/23 1 CO 0.00 1686 (lb/hr) -
30 DRA
2 2184 Opacity 100% 2 SO2 0.00 0.12 lb/MMBtu
- 24 hr Block
2 SO2 0.00 0.2 lb/MMBtu -
30 DRA
2 NOx 0.00 0.26 lb/MMBtu
- 30 DRA
2 Opacity 0.00 20 Percent - 6
min
Excess Emission Report - Hourly Summary
Point
Source Channel
Startup
&
Shutdown
Control
Equipment
Problems
Process
Problems
Other
Known
Causes
Unknown
Causes
Emission
Limit
1 SO2 0 0 0 0 0 0.12 lb/MMBtu - 30 DRA
1 SO2 0 0 0 0 0 595 (lb/hr) - 30 DRA
1 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA
1 NOx 0 0 0 0 0 0.26 lb/MMBtu - 30 DRA
1 NOx 0 0 0 0 0 1290 (lb/hr) - 30 DRA
1 Opacity 0 0 0 0 0 20 Percent - 6 min
1 CO 0 0 0 0 0 0.34 lb/MMBtu - 30 DRA
1 CO 0 0 0 0 0 1686 (lb/hr) - 30 DRA
2 SO2 0 0 0 0 0 0.12 lb/MMBtu - 24 hr Block
2 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA
2 NOx 0 0 0 0 0 0.26 lb/MMBtu - 30 DRA
2 Opacity 0 0 0 0 0 20 Percent - 6 min
CMS Performance Summary - Hourly Summary
Point
Source Channel Monitor
Malfunction
Non-monitor
Malfunction
QA
Calibrations
Other
Known
Causes
Unknown
Causes
1 SO2 0 0 4 0 0
1 NOx 0 0 4 0 0
1 CO2 0 0 4 0 0
1 Opacity 0 0 11 0 0
3
CMS Performance Summary - Hourly Summary
Point
Source Channel Monitor
Malfunction
Non-monitor
Malfunction
QA
Calibrations
Other
Known
Causes
Unknown
Causes
1 CO 0 0 4 0 0
2 SO2 0 0 2 1 0
2 NOx 0 0 2 1 0
2 CO2 0 0 2 1 0
2 Opacity 0 0 9 0 0
Type Code 280 (COMS Attenuator Filters) Procedure 3
Point Source
& Location
Attenuator
I.D.
Attenuator
Certification
Date
Certified
Attenuator
Opacity
OPLR,
SECR,
or
PLCF,
Corrected
Opacity
Value
Range
Low,
Mid, &
High
Certification
1-year or 5-
year
1 - A YN-91 10/9/23 11.70 0.63 14.56 L 1
1 - A YN-92 10/9/23 18.50 0.63 22.72 M 1
1 - A YN-93 10/9/23 28.40 0.63 34.43 H 1
1 - B YN-91 10/9/23 11.70 0.63 14.56 L 1
1 - B YN-92 10/9/23 18.50 0.63 22.72 M 1
1 - B YN-93 10/9/23 28.40 0.63 34.43 H 1
2 - 2 VL-84 10/9/23 28.90 0.25 15.36 L 1
2 - 2 VL-85 10/9/23 45.20 0.25 25.52 M 1
2 - 2 VL-86 10/9/23 69.90 0.25 44.48 H 1
Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error)
Point
Source Location Audit Date
Opacity Monitor Response
(Average of 5) Mean Difference Calibration
Error (≤ 3%) Low Mid High
1 A 2/1/24 15 0.170
1 A 2/1/24 23 -0.050
1 A 2/1/24 35 0.200
1 B 1/31/24 14 -0.190
1 B 1/31/24 22 -0.320
1 B 1/31/24 34 -0.030
2 2 2/6/24 15 -0.040
2 2 2/6/24 25 -0.150
2 2 2/6/24 45 0.400
4
Type Code 282 (Annual Zero Alignment Audit) Procedure 3
Point
Source Location Audit
Date
Alternative
Zero Alignment
(Yes or No)
COM Clear
Condition
Zero Response
(CCZR)
COM
Simulated
Zero
Response
(CSZR)
Zero
Alignment
Error
Difference
(CCZR)-
(CSZR)
Adjustment to
COM
Simulated Zero
Response
(CSZR)
(Yes or No)
1 A 2/1/24 yes 0.60 0 1 yes
1 B 1/31/24 yes -0.10 0 0 yes
2 2 2/6/24 yes 0.20 0 0 yes
Pollutant Concentration
Exceeded Span of CEM
Monitor Outage During
Point Source Operation
Alternate
Sampling CEM Modifications
0 Hours 45 Hours 0 Hours 0 Events
SOURCE INSPECTION
SUMMARY EVALUATION: Huntington maintains its CEMS as required in R307-170 and 40 CFR
60.13.
CURRENT
RECOMMENDATIONS: All deviations appear to be a result of breakdown or process related
problems that do not warrant issuing a violation. Huntington was in
compliance during this reporting period. No further compliance action is
recommended.
Huntington’s NSPS monitoring system meets the performance standards of
40 CFR 60, Appendix B Performance Specifications. Huntington’s acid
rain monitoring system meets the performance standards of 40 CFR 75
Acid Rain Performance Specifications.
Periods of excess emissions that were recorded by the CMS in service on
each point source during this reporting period are summarized in the
SEDR and described in Pivot Table 400 “Excess Emissions Review.”
HIGH PRIORITY
VIOLATOR (HPV): No
RECOMMENDATION
FOR NEXT INSPECTION: Check DAS for daily zero and span drift.
Check the QC program to ensure that monitor drift is being tracked that
the source can identify excessive drift.
ATTACHMENTS: Excel spreadsheet review
Pacificorp Huntington EER 1Q2024
Point Source Information Late Expired Cal. Gas Valid Cal. Gas Days Yes No
1 Type Code 100
(Company Information)Type Code Company Manager Company Name AIRS # Phone Number
Environmental
Contact
1 100 Laren Huntsman 01501001 435-687-4000 Russ Willson
1 100 0 0 0 0
1 Type Code 110
(Point Source Identification)Type Code Point Source
Quarter
1 - 4 Year
Point Source
Operating Hrs. in
Quarter
1 110 1 2024 2184
1 110 1 2024 2184
1 110 0 0 0
1 Type Code 200
(Monitor Identification)Type Code Point Source Channel Manufacturer Model No. Monitor SN Low Span High Span Installation Date
Monitor
Location
1 200 CO THERMO 48iQ-ACN 12108511485 0 1000 6/15/2021 Stack
1 200 CO2 THERMO 410iQ-ACN 12108511478 0 20 6/15/2021 Stack
1 200 NOx THERMO 42iQ-ACANN 12108511481 0 400 6/15/2021 Stack
1 200 Opacity Land Instr. 4500 MkIII 232342 81 0 100 10/11/2018 Scrubber Inlet Duct A - stack
1 200 Opacity Land Instr. 4500 MkIII 236573 83 0 100 10/11/2018 Scrubber Inlet Duct B - stack
1 200 SO2 THERMO 43iQ-ACN 12108511483 0 800 6/15/2021 Stack
1 200 CO2 THERMO 410iQ-ACN 12108511479 0 20 6/17/2021 Stack
1 200 NOx THERMO 42iQ-ACANN 12108511480 0 400 6/17/2021 Stack
1 200 Opacity Land Instr. 4500 MkIII 241977 92 0 100 10/15/2019 Inlet Duct -
1 200 SO2 THERMO 43iQ-ACN 12108511482 0 800 6/17/2021 Stack
1 200 0 0 0 0 0 0 1/0/1900 0
1
Type Code310
(Excess Emissions)
SUMMARY REPORT
Type Code Channel
Total Hours of Excess
Emissions
Excess Emissions -
% of Total
Operating Hours
RC 701 Hours -
start
up/Shutdown
RC 702 Hours-
Control Equipment
Problems
RC 703 Hours -
Process Problems
RC 704, 706, 707
Hours -Other Known
Causes
RC 705 Hours -
Unknown
Causes
Emission
Limitation
Emission
Limitation
Units
Emission
Limitation
Averaging
Period
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 30 DRA
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 595 (lb/hr) 30 DRA
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA
1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.26 lb/MMBtu 30 DRA
1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 1290 (lb/hr) 30 DRA
1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min
1 TRUE 310 CO 0 0.00% 0 0 0 0 0 0.34 lb/MMBtu 30 DRA
1 TRUE 310 CO 0 0.00% 0 0 0 0 0 1686 (lb/hr) 30 DRA
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 24 hr Block
1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA
1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.26 lb/MMBtu 30 DRA
1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min
1 310 0 0 0 0 0 0 0 0 0
1 Type Code 300 (CMS
Performance Summary) Type Code Channel
Point Source Operating
Hours
Downtime - % of
Total Operating
Hours
Total CMS
Downtime
RC 721 Hours -
Monitor
Malfunction
RC 722 Hours -
Non-monitor
Malfunction
RC 723 Hours -
QA Calibrations
RC 724 Hours -
Other Known
Causes
RC 725 Hours
- Unknown
Causes
1 TRUE 300 SO2 2184 0.18% 4 0 0 4 0 0
1 TRUE 300 NOx 2184 0.18% 4 0 0 4 0 0
1 TRUE 300 CO2 2184 0.18% 4 0 0 4 0 0
1 TRUE 300 Opacity 2184 0.50% 10.94 0 0.1 10.84 0 0
1 TRUE 300 CO 2184 0.18% 4 0 0 4 0 0
1 TRUE 300 SO2 2184 0.14% 3 0 0 2 1 0
1 TRUE 300 NOx 2184 0.14% 3 0 0 2 1 0
1 TRUE 300 CO2 2184 0.14% 3 0 0 2 1 0
1 TRUE 300 Opacity 2184 0.41% 9.05 0 0.1 8.95 0 0
1 300 0 0 0 0 0 0
1
Type Code 250
(Performance Specification
RATA Results)
Type Code Channel
Date of Most Current
RATA
Date of Preceding
RATA
Months Between
RATA's
Units of
Measurement CEM Value Reference Method
Value
Relative
accuracy Pass/ Fail
1 262 Days 250 SO2 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil. 0.057 0.061 9.60% Pass
1 262 Days 250 NOx 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil. 0.204 0.197 4.40% Pass
1 262 Days 250 CO2 04/13/23 07/25/22 8.61 Percent 10.8 11 3.10% Pass
1 262 Days 250 CO 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil. 0.169 0.171 4.00% Pass
1 262 Days 250 CO 04/13/23 07/25/22 8.61 #/hr 770.9 823.2 9.70% Pass
1 289 Days 250 CO2 04/14/23 06/29/22 9.5 Percent 10.7 10.5 3.10% Pass
1 289 Days 250 NOx 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil. 0.228 0.225 2.00% Pass
1 289 Days 250 SO2 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil. 0.074 0.074 0.50% Pass
1 0 Days 250 0 01/00/00 01/00/00 0 0 0 0 0.00% 0
1
1
1
1
2
1
2
0
0
PacifiCorp Huntington
0
1
1
1
1
1
1
2
2
2
2
0
1
1
1
2
2
1
1
1
1
1
1
1
2
2
2
2
2
1
1
1
2
2
0
1
2
0
Point Source
Point Source
Point Source
Pacificorp Huntington EER 1Q2024
1 Type Code 260
(CGA Results)Type Code Channel Date Audit Point No. Cylinder ID
Cylinder Expiration
Date
Type of
Certification
Units of
Measurement CEM Value Cylinder
Value
Precision
%Pass/ Fail Range - High or
Low
1 Valid Cal. Gas 260 CO 01/18/24 low DT0016226 06/11/24 0 ppm 252.9 250 1.10% Pass 0
1 Valid Cal. Gas 260 CO 01/18/24 mid DT0027667 02/08/27 0 ppm 545.1 547 -0.30% Pass 0
1 260 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0
1 Type Code 270
(Linearity Test Results)Type Code Channel Date Audit Point No. Cylinder ID
Cylinder Expiration
Date
Type of
Certification
Units of
Measurement CEM Value Cylinder
Value
Precision
%Pass/ Fail Range - High or
Low
1 Valid Cal. Gas 270 CO2 01/17/24 low DT0035319 04/05/30 P1 percent 5 5 0.70% Pass 0
1 Valid Cal. Gas 270 CO2 01/17/24 mid DT0019792 11/10/30 P1 percent 11 11 0.00% Pass 0
1 Valid Cal. Gas 270 CO2 01/17/24 high SA12912 02/04/30 P1 percent 17.9 18.1 0.90% Pass 0
1 Valid Cal. Gas 270 NOx 01/17/24 low DT0035319 04/05/30 P1 ppm 101.3 100.9 0% Pass 0
1 Valid Cal. Gas 270 NOx 01/17/24 mid DT0019792 11/10/30 P1 ppm 218.3 218 0% Pass 0
1 Valid Cal. Gas 270 NOx 01/17/24 high SA12912 02/04/30 P1 ppm 356.8 363 2% Pass 0
1 Valid Cal. Gas 270 SO2 01/17/24 low DT0035319 04/05/30 P1 ppm 203.4 199.9 1.70% Pass High
1 Valid Cal. Gas 270 SO2 01/17/24 mid DT0019792 11/10/30 P1 ppm 438.4 441 0.60% Pass High
1 Valid Cal. Gas 270 SO2 01/17/24 high SA12912 02/04/30 P1 ppm 672.7 705 4.60% Pass High
1 Valid Cal. Gas 270 CO2 01/24/24 low DT0035319 04/05/30 P1 percent 4.9 5 2.00% Pass 0
1 Valid Cal. Gas 270 CO2 01/24/24 mid CC2949 11/07/30 P1 percent 11.1 11 0.90% Pass 0
1 Valid Cal. Gas 270 CO2 01/24/24 high SA12912 02/04/30 P1 percent 18.3 18.1 1.30% Pass 0
1 Valid Cal. Gas 270 NOx 01/24/24 low DT0035319 04/05/30 P1 ppm 101.8 100.9 0.90% Pass 0
1 Valid Cal. Gas 270 NOx 01/24/24 mid CC2949 11/07/30 P1 ppm 215.6 214 0.80% Pass 0
1 Valid Cal. Gas 270 NOx 01/24/24 high SA12912 02/04/30 P1 ppm 360.8 363 0.60% Pass 0
1 Valid Cal. Gas 270 SO2 01/24/24 low DT0035319 04/05/30 P1 ppm 204.3 199.9 2% Pass High
1 Valid Cal. Gas 270 SO2 01/24/24 mid CC2949 11/07/30 P1 ppm 435.8 437 0% Pass High
1 Valid Cal. Gas 270 SO2 01/24/24 high SA12912 02/04/30 P1 ppm 682.5 705 3% Pass High
1 270 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0
1
Type Code 210
(Pollutant Concentration
Exceeded Span of CEM)
Type Code Channel Start Date Start Time End Date End Time Hours
1 0 0 0 1/0/00 0:00 1/0/00 0:00
1
1 None Reported
1 0 TC 220 Hours 44.90 TC 220 Hours 0.00 TC 230 Hours 0.00 Events 0.00 Hours 0.00 Events 0.00 0.00
1 44.99 TC 300 Hours 0.09 FALSE
0
2
0
1
1
1
1
2
1
1
1
1
1
2
2
2
2
0
Type Code 210
(Pollutant Concentration
Exceeded Span of CEM)
Type Code 220
(Monitor Outage
During Point Source Operation)
Type Code 230
(Manual Sample - Alternate
Sampling During Monitor
Outage)
Type Code 240
(CEM Modifications)
Type Code 530
(Excess Emissions During
Emergency Conditions)
Type Code 450
(Data Excluded)
Type Code 550
(Changes in Operation in
Control Equipment When
CEM Data Not Available)
Type Code 500
(Boiler Operating Days
w/o 18 Hours of Data)
1
1
Point Source
Point Source
Point Source
Yes None Reported None Reported None Reported None Reported None Reported None Reported
2
2
2
Pacificorp Huntington EER 1Q2024
Relative Accuracy Overview
Point Source Channel
Date of Most
Current
RATA
Date of
Preceding
RATA
Months Between
RATA's
Units
Measured CEM Value Reference Method
Value
Relative
Accuracy Pass/ Fail 2024
1 SO2 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil.0.057 0.06 9.60% Pass
1 NOx 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil.0.204 0.20 4.40% Pass
1 CO2 04/13/23 07/25/22 8.61 Percent 10.8 11.00 3.10% Pass
1 CO 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil.0.169 0.17 4.00% Pass
1 CO 04/13/23 07/25/22 8.61 #/hr 770.9 823.20 9.70% Pass
2 CO2 04/14/23 06/29/22 9.5 Percent 10.7 10.50 3.10% Pass
2 NOx 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil.0.228 0.23 2.00% Pass
2 SO2 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil.0.074 0.07 0.50% Pass
*
NSPS CGA First 2024
Audit Gas Ranges Audit Gas Ranges
AP1 Low AP2 Low AP1 High AP2 High
1 CO 1/18/24 1000 250 200 to 300
1 CO 1/18/24 1000 547 500 to 600
*
Acid Rain Audit Linearity First 2024
Low Span Gas Ranges High Span Gas Ranges
Low Mid High Low Mid High
1 CO2 1/17/24 20 5 4 to 6
1 CO2 1/17/24 20 11 10 to 12
1 CO2 1/17/24 20 18.1 16 to 20
1 NOx 1/17/24 400 100.9 80 to 120
1 NOx 1/17/24 400 218 200 to 240
1 NOx 1/17/24 400 363 320 to 400
1 SO2 1/17/24 800 199.9 160 to 240
1 SO2 1/17/24 800 441 400 to 480
1 SO2 1/17/24 800 705 640 to 800
2 CO2 1/24/24 20 5 4 to 6
2 CO2 1/24/24 20 11 10 to 12
2 CO2 1/24/24 20 18.1 16 to 20
2 NOx 1/24/24 400 100.9 80 to 120
2 NOx 1/24/24 400 214 200 to 240
2 NOx 1/24/24 400 363 320 to 400
2 SO2 1/24/24 800 199.9 160 to 240
2 SO2 1/24/24 800 437 400 to 480
2 SO2 1/24/24 800 705 640 to 800
*
Audit Gas Used High Span Audit Gas Used
High SpanAudit Gas Used
Point Source Channel Audit Date Low Span
Point Source Channel Audit Date Low Span Audit Gas Used
Pacificorp Huntington EER 1Q2024
Type Code 280 (COMS Attenuator Filters) Procedure 3
Point Source Location
Attenuator
I.D.
Attenuator
Certification Date
Certified Attenuator
Opacity
OPLR,
SECR, or
PLCF,
Corrected Opacity
Value
Range
Low, Mid, & High
Certification
1-year or 5-year
1 A YN-91 10/9/23 12 0.632 14.56 L 1
1 A YN-92 10/9/23 19 0.632 22.72 M 1
1 A YN-93 10/9/23 28 0.632 34.43 H 1
1 B YN-91 10/9/23 11.7 0.632 14.56 L 1
1 B YN-92 10/9/23 18.5 0.632 22.72 M 1
1 B YN-93 10/9/23 28.4 0.632 34.43 H 1
2 2 VL-84 10/9/23 28.9 0.245 15.36 L 1
2 2 VL-85 10/9/23 45.2 0.245 25.52 M 1
2 2 VL-86 10/9/23 69.9 0.245 44.48 H 1
*
Opacity Monitor Response (Average of 5)
Low Range Mid Range High Range
1 A 2/1/24 15 0.170 0.060 0.140 0.000
1 A 2/1/24 23 -0.050 0.060 0.140 0.000
1 A 2/1/24 35 0.200 0.060 0.140 0.000
1 B 1/31/24 14 -0.190 0.060 0.140 0.000
1 B 1/31/24 22 -0.320 0.000 0.000 0.000
1 B 1/31/24 34 -0.030 0.000 0.000 0.000
2 2 2/6/24 15 -0.040 0.030 0.070 0.000
2 2 2/6/24 25 -0.150 0.060 0.140 0.000
2 2 2/6/24 45 0.400 0.030 0.070 0.000
*
Point Source Location Audit Date
Alternitive Zero
Alignment
(Yes or No)
COM Clear
Condition Zero
Response
(CCZR)
COM Simulated
Zero Response
(CSZR)
Zero Alignment
Error Difference
(CCZR)-(CSZR)
Adjustment to COM
Simulated Zero
Response
(CSZR)
(Yes or No)
1 A 2/1/24 yes 0.600 0.000 0.600 yes
1 B 1/31/24 yes -0.100 0.000 -0.100 yes
2 2 2/6/24 yes 0.200 0.000 0.200 yes
Type Code 282 (Procedure 3 - Annual Zero Alignment Audit)
Point
Source Location Audit Date Mean Difference Standard Deviation
Confidence
Coefficient
Calibration
Error (≤ 3%)
Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error)
Pacificorp Huntington EER 1Q2024
Monitoring Information TC 210, 230, & 240
Type Code 210
(Pollutant Concentration Exceeded Span of CEM) - 500 (All)
*
Sum of Hours Column Labels
Row Labels (blank) Grand Total
(blank)0 0
Grand Total 0 0
*
Type Code 230
(Manual Sample - Alternate Sampling During Monitor Outage) - 500 (All)
*
Sum of Hours Column Labels
Row Labels (blank) Grand Total
(blank)0 0
Grand Total 0 0
*
Type Code 240
(CEM Modifications) - 100 (All)
*
Count of Channel Column Labels
Row Labels (blank) Grand Total
(blank)
(blank)
Grand Total
Pacificorp Huntington EER 1Q2024
Type Code 220
(Monitor Outage During Point Source Operation) - 600 (All)
*
Sum of Hours Column Labels
Row Labels 723 722 724 Grand Total
1
Opacity
The monitor was unavailable during the daily monitor calibration as
required by 40 CFR parts 60 and 75.7.58 7.58
An opacity monitor filter check and/or audit was conducted followed by
a manual calibration.3.17 3.17
A manual calibration was performed which was then followed by an
auto calibration to verify system accuracy.0.18 0.18
A loss/interuption of power or communication to the DCS and/or
monitor resulted in a loss of data. Power/communication was restored
and the monitor was returned to service.
0.08 0.08
SO2
Maintenance checks and adjustments recommended by the service rep.
were performed. Calibration checks were then performed and the
system was returned to service.
3.98 3.98
NOx
Maintenance checks and adjustments recommended by the service rep.
were performed. Calibration checks were then performed and the
system was returned to service.
3.98 3.98
CO2
Maintenance checks and adjustments recommended by the service rep.
were performed. Calibration checks were then performed and the
system was returned to service.
3.98 3.98
CO
Maintenance checks and adjustments recommended by the service rep.
were performed. Calibration checks were then performed and the
system was returned to service.
3.98 3.98
2
Opacity
The monitor was unavailable during the daily monitor calibration as
required by 40 CFR parts 60 and 75.7.58 7.58
An opacity monitor filter check and/or audit was conducted followed by
a manual calibration.1.38 1.38
A loss/interuption of power or communication to the DCS and/or
monitor resulted in a loss of data. Power/communication was restored
and the monitor was returned to service.
0.08 0.08
SO2
Maintenance checks and adjustments recommended by the service rep.
were performed. Calibration checks were then performed and the
system was returned to service.
1.98 1.98
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
0.98 0.98
NOx
Maintenance checks and adjustments recommended by the service rep.
were performed. Calibration checks were then performed and the
system was returned to service.
1.98 1.98
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
0.98 0.98
CO2
Maintenance checks and adjustments recommended by the service rep.
were performed. Calibration checks were then performed and the
system was returned to service.
1.98 1.98
Maintenance of another monitor required normal sampling to be
interrupted. The system was returned to service following the
maintenance.
0.98 0.98
Grand Total 41.78 0.17 2.95 44.90
Pacificorp Huntington EER 1Q2024
Sum of Hours Column Labels
Row Labels 723 722 724 Grand Total
Pacificorp Huntington EER 1Q2024
Opy *
Opy Count of Magnitude of Emissions Column Labels
Opy Row Labels Grand Total
Opy Grand Total
SO2 *
SO2 Type Code 410 (SO2) - 6000 (All)
SO2 *
SO2 Count of Magnitude of Emissions Column Labels
SO2 Row Labels Grand Total
SO2 Grand Total
NOx *
NOx Type Code 420 (NOx) - 6000 (All)
NOx *
NOx Count of Magnitude of Emissions Column Labels
NOx Row Labels Grand Total
NOx Grand Total
NOx d *
NOx d Type Code 421 (Daily NOx Emissions) - 500 (All)
NOx d *
NOx d Count of Reason Code Column Labels
NOx d Row Labels (blank)Grand Total
NOx d 1
NOx d 0
NOx d 2
NOx d 0
NOx d Grand Total
CO *
CO Type Code 440
(CO) - 6000 (All)
CO *
CO Count of Magnitude of Emissions Column Labels
CO Row Labels Grand Total
CO Grand Total
Pacificorp Huntington EER 1Q2024
Type Code 500
Before February 28, 2005 (Boiler Operating Days w/o 18 Hours of
Data) After February 28, 2005 (90% Operating Hours For each 30 BOD)
- 500
(All)
*
Count of Channel Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 510
(F-factor, Equations & Conversion Factors) - 500 (All)
Count of F-factor Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 520
(Minimum Data Not
Obtained <22/30 BODs) - 500
(All)
Count of Channel Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 530
(Excess Emissions During Emergency Conditions) - 500 (All)
Count of Date Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 540
(Fuel Pre-treatment Credit SO2) - 500 (All)
Count of Date Column Labels
Row Labels Grand Total
Grand Total
*
TypeCode 550
(Changes in Operation in Control Equipment When CEM Data Not
Available) - 500
(All)
Column Labels
Row Labels Grand Total
Grand Total