HomeMy WebLinkAboutDAQ-2024-007732 1 DAQC-402-24 Site ID 10238 (B5) MEMORANDUM TO: FILE – PACIFICORP HUNTINGTON POWER PLANT THROUGH: Harold Burge, Major Source Compliance Section Manager FROM: Rob Leishman, Environmental Scientist DATE: April 30, 2024 SUBJECT: PacifiCorp Huntington Power Plant (Huntington), Major, NSPS, Title V, Emery County FRS #UT00000049001501001 INSPECTION TYPE: State Electronic Data Report (SEDR) Review REVIEW DATE: April 30, 2024 SOURCE LOCATION: Huntington Canyon/Emery County SOURCE CONTACT: Russ Wilson - 435-687-4331 APPLICABLE REGULATIONS: Title V Operating Permit PERMIT NUMBER: 1501001005 DATE OF PERMIT: January 22, 2020 Date of Last Revision: August 26, 2021 SOURCE INSPECTION EVALUATION: With the exception of sources that only monitor for opacity, quarterly report memoranda will only address the findings of the quarterly report. Approval Order and Title V permit conditions addressing continuous emission monitoring requirements will be addressed in Huntington’s relative accuracy performance specification test review memorandum. SOURCE REVIEW EVALUATION: First Quarter 2024 % Monitor Availability (MA) Performance Test Dates (N/A to Opacity) Summary of Excess Emissions During Point Source Operation Point Source Op. hrs. Channel MA CGA Lin RATA Point Source Channel Hrs. Limitation 1 2184 SO2 100% 01/17/24 04/13/23 1 SO2 0.00 0.12 lb/MMBtu - 30 DRA 1 2184 NOx 100% 01/17/24 04/13/23 1 SO2 0.00 595 (lb/hr) - 30 DRA 1 2184 CO2 100% 01/17/24 04/13/23 1 SO2 0.00 0.2 lb/MMBtu - 30 DRA 1 2184 Opacity 99% 1 NOx 0.00 0.26 lb/MMBtu - 30 DRA 1 8 2 2 First Quarter 2024 % Monitor Availability (MA) Performance Test Dates (N/A to Opacity) Summary of Excess Emissions During Point Source Operation Point Source Op. hrs. Channel MA CGA Lin RATA Point Source Channel Hrs. Limitation 1 2184 CO 100% 01/18/24 04/13/23 1 NOx 0.00 1290 (lb/hr) - 30 DRA 2 2184 SO2 100% 01/24/24 04/14/23 1 Opacity 0.00 20 Percent - 6 min 2 2184 NOx 100% 01/24/24 04/14/23 1 CO 0.00 0.34 lb/MMBtu - 30 DRA 2 2184 CO2 100% 01/24/24 04/14/23 1 CO 0.00 1686 (lb/hr) - 30 DRA 2 2184 Opacity 100% 2 SO2 0.00 0.12 lb/MMBtu - 24 hr Block 2 SO2 0.00 0.2 lb/MMBtu - 30 DRA 2 NOx 0.00 0.26 lb/MMBtu - 30 DRA 2 Opacity 0.00 20 Percent - 6 min Excess Emission Report - Hourly Summary Point Source Channel Startup & Shutdown Control Equipment Problems Process Problems Other Known Causes Unknown Causes Emission Limit 1 SO2 0 0 0 0 0 0.12 lb/MMBtu - 30 DRA 1 SO2 0 0 0 0 0 595 (lb/hr) - 30 DRA 1 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA 1 NOx 0 0 0 0 0 0.26 lb/MMBtu - 30 DRA 1 NOx 0 0 0 0 0 1290 (lb/hr) - 30 DRA 1 Opacity 0 0 0 0 0 20 Percent - 6 min 1 CO 0 0 0 0 0 0.34 lb/MMBtu - 30 DRA 1 CO 0 0 0 0 0 1686 (lb/hr) - 30 DRA 2 SO2 0 0 0 0 0 0.12 lb/MMBtu - 24 hr Block 2 SO2 0 0 0 0 0 0.2 lb/MMBtu - 30 DRA 2 NOx 0 0 0 0 0 0.26 lb/MMBtu - 30 DRA 2 Opacity 0 0 0 0 0 20 Percent - 6 min CMS Performance Summary - Hourly Summary Point Source Channel Monitor Malfunction Non-monitor Malfunction QA Calibrations Other Known Causes Unknown Causes 1 SO2 0 0 4 0 0 1 NOx 0 0 4 0 0 1 CO2 0 0 4 0 0 1 Opacity 0 0 11 0 0 3 CMS Performance Summary - Hourly Summary Point Source Channel Monitor Malfunction Non-monitor Malfunction QA Calibrations Other Known Causes Unknown Causes 1 CO 0 0 4 0 0 2 SO2 0 0 2 1 0 2 NOx 0 0 2 1 0 2 CO2 0 0 2 1 0 2 Opacity 0 0 9 0 0 Type Code 280 (COMS Attenuator Filters) Procedure 3 Point Source & Location Attenuator I.D. Attenuator Certification Date Certified Attenuator Opacity OPLR, SECR, or PLCF, Corrected Opacity Value Range Low, Mid, & High Certification 1-year or 5- year 1 - A YN-91 10/9/23 11.70 0.63 14.56 L 1 1 - A YN-92 10/9/23 18.50 0.63 22.72 M 1 1 - A YN-93 10/9/23 28.40 0.63 34.43 H 1 1 - B YN-91 10/9/23 11.70 0.63 14.56 L 1 1 - B YN-92 10/9/23 18.50 0.63 22.72 M 1 1 - B YN-93 10/9/23 28.40 0.63 34.43 H 1 2 - 2 VL-84 10/9/23 28.90 0.25 15.36 L 1 2 - 2 VL-85 10/9/23 45.20 0.25 25.52 M 1 2 - 2 VL-86 10/9/23 69.90 0.25 44.48 H 1 Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error) Point Source Location Audit Date Opacity Monitor Response (Average of 5) Mean Difference Calibration Error (≤ 3%) Low Mid High 1 A 2/1/24 15 0.170 1 A 2/1/24 23 -0.050 1 A 2/1/24 35 0.200 1 B 1/31/24 14 -0.190 1 B 1/31/24 22 -0.320 1 B 1/31/24 34 -0.030 2 2 2/6/24 15 -0.040 2 2 2/6/24 25 -0.150 2 2 2/6/24 45 0.400 4 Type Code 282 (Annual Zero Alignment Audit) Procedure 3 Point Source Location Audit Date Alternative Zero Alignment (Yes or No) COM Clear Condition Zero Response (CCZR) COM Simulated Zero Response (CSZR) Zero Alignment Error Difference (CCZR)- (CSZR) Adjustment to COM Simulated Zero Response (CSZR) (Yes or No) 1 A 2/1/24 yes 0.60 0 1 yes 1 B 1/31/24 yes -0.10 0 0 yes 2 2 2/6/24 yes 0.20 0 0 yes Pollutant Concentration Exceeded Span of CEM Monitor Outage During Point Source Operation Alternate Sampling CEM Modifications 0 Hours 45 Hours 0 Hours 0 Events SOURCE INSPECTION SUMMARY EVALUATION: Huntington maintains its CEMS as required in R307-170 and 40 CFR 60.13. CURRENT RECOMMENDATIONS: All deviations appear to be a result of breakdown or process related problems that do not warrant issuing a violation. Huntington was in compliance during this reporting period. No further compliance action is recommended. Huntington’s NSPS monitoring system meets the performance standards of 40 CFR 60, Appendix B Performance Specifications. Huntington’s acid rain monitoring system meets the performance standards of 40 CFR 75 Acid Rain Performance Specifications. Periods of excess emissions that were recorded by the CMS in service on each point source during this reporting period are summarized in the SEDR and described in Pivot Table 400 “Excess Emissions Review.” HIGH PRIORITY VIOLATOR (HPV): No RECOMMENDATION FOR NEXT INSPECTION: Check DAS for daily zero and span drift. Check the QC program to ensure that monitor drift is being tracked that the source can identify excessive drift. ATTACHMENTS: Excel spreadsheet review Pacificorp Huntington EER 1Q2024 Point Source Information Late Expired Cal. Gas Valid Cal. Gas Days Yes No 1 Type Code 100 (Company Information)Type Code Company Manager Company Name AIRS # Phone Number Environmental Contact 1 100 Laren Huntsman 01501001 435-687-4000 Russ Willson 1 100 0 0 0 0 1 Type Code 110 (Point Source Identification)Type Code Point Source Quarter 1 - 4 Year Point Source Operating Hrs. in Quarter 1 110 1 2024 2184 1 110 1 2024 2184 1 110 0 0 0 1 Type Code 200 (Monitor Identification)Type Code Point Source Channel Manufacturer Model No. Monitor SN Low Span High Span Installation Date Monitor Location 1 200 CO THERMO 48iQ-ACN 12108511485 0 1000 6/15/2021 Stack 1 200 CO2 THERMO 410iQ-ACN 12108511478 0 20 6/15/2021 Stack 1 200 NOx THERMO 42iQ-ACANN 12108511481 0 400 6/15/2021 Stack 1 200 Opacity Land Instr. 4500 MkIII 232342 81 0 100 10/11/2018 Scrubber Inlet Duct A - stack 1 200 Opacity Land Instr. 4500 MkIII 236573 83 0 100 10/11/2018 Scrubber Inlet Duct B - stack 1 200 SO2 THERMO 43iQ-ACN 12108511483 0 800 6/15/2021 Stack 1 200 CO2 THERMO 410iQ-ACN 12108511479 0 20 6/17/2021 Stack 1 200 NOx THERMO 42iQ-ACANN 12108511480 0 400 6/17/2021 Stack 1 200 Opacity Land Instr. 4500 MkIII 241977 92 0 100 10/15/2019 Inlet Duct - 1 200 SO2 THERMO 43iQ-ACN 12108511482 0 800 6/17/2021 Stack 1 200 0 0 0 0 0 0 1/0/1900 0 1 Type Code310 (Excess Emissions) SUMMARY REPORT Type Code Channel Total Hours of Excess Emissions Excess Emissions - % of Total Operating Hours RC 701 Hours - start up/Shutdown RC 702 Hours- Control Equipment Problems RC 703 Hours - Process Problems RC 704, 706, 707 Hours -Other Known Causes RC 705 Hours - Unknown Causes Emission Limitation Emission Limitation Units Emission Limitation Averaging Period 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 595 (lb/hr) 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.26 lb/MMBtu 30 DRA 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 1290 (lb/hr) 30 DRA 1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 0.34 lb/MMBtu 30 DRA 1 TRUE 310 CO 0 0.00% 0 0 0 0 0 1686 (lb/hr) 30 DRA 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.12 lb/MMBtu 24 hr Block 1 TRUE 310 SO2 0 0.00% 0 0 0 0 0 0.2 lb/MMBtu 30 DRA 1 TRUE 310 NOx 0 0.00% 0 0 0 0 0 0.26 lb/MMBtu 30 DRA 1 TRUE 310 Opacity 0 0.00% 0 0 0 0 0 20 Percent 6 min 1 310 0 0 0 0 0 0 0 0 0 1 Type Code 300 (CMS Performance Summary) Type Code Channel Point Source Operating Hours Downtime - % of Total Operating Hours Total CMS Downtime RC 721 Hours - Monitor Malfunction RC 722 Hours - Non-monitor Malfunction RC 723 Hours - QA Calibrations RC 724 Hours - Other Known Causes RC 725 Hours - Unknown Causes 1 TRUE 300 SO2 2184 0.18% 4 0 0 4 0 0 1 TRUE 300 NOx 2184 0.18% 4 0 0 4 0 0 1 TRUE 300 CO2 2184 0.18% 4 0 0 4 0 0 1 TRUE 300 Opacity 2184 0.50% 10.94 0 0.1 10.84 0 0 1 TRUE 300 CO 2184 0.18% 4 0 0 4 0 0 1 TRUE 300 SO2 2184 0.14% 3 0 0 2 1 0 1 TRUE 300 NOx 2184 0.14% 3 0 0 2 1 0 1 TRUE 300 CO2 2184 0.14% 3 0 0 2 1 0 1 TRUE 300 Opacity 2184 0.41% 9.05 0 0.1 8.95 0 0 1 300 0 0 0 0 0 0 1 Type Code 250 (Performance Specification RATA Results) Type Code Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units of Measurement CEM Value Reference Method Value Relative accuracy Pass/ Fail 1 262 Days 250 SO2 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil. 0.057 0.061 9.60% Pass 1 262 Days 250 NOx 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil. 0.204 0.197 4.40% Pass 1 262 Days 250 CO2 04/13/23 07/25/22 8.61 Percent 10.8 11 3.10% Pass 1 262 Days 250 CO 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil. 0.169 0.171 4.00% Pass 1 262 Days 250 CO 04/13/23 07/25/22 8.61 #/hr 770.9 823.2 9.70% Pass 1 289 Days 250 CO2 04/14/23 06/29/22 9.5 Percent 10.7 10.5 3.10% Pass 1 289 Days 250 NOx 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil. 0.228 0.225 2.00% Pass 1 289 Days 250 SO2 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil. 0.074 0.074 0.50% Pass 1 0 Days 250 0 01/00/00 01/00/00 0 0 0 0 0.00% 0 1 1 1 1 2 1 2 0 0 PacifiCorp Huntington 0 1 1 1 1 1 1 2 2 2 2 0 1 1 1 2 2 1 1 1 1 1 1 1 2 2 2 2 2 1 1 1 2 2 0 1 2 0 Point Source Point Source Point Source Pacificorp Huntington EER 1Q2024 1 Type Code 260 (CGA Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 Valid Cal. Gas 260 CO 01/18/24 low DT0016226 06/11/24 0 ppm 252.9 250 1.10% Pass 0 1 Valid Cal. Gas 260 CO 01/18/24 mid DT0027667 02/08/27 0 ppm 545.1 547 -0.30% Pass 0 1 260 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 270 (Linearity Test Results)Type Code Channel Date Audit Point No. Cylinder ID Cylinder Expiration Date Type of Certification Units of Measurement CEM Value Cylinder Value Precision %Pass/ Fail Range - High or Low 1 Valid Cal. Gas 270 CO2 01/17/24 low DT0035319 04/05/30 P1 percent 5 5 0.70% Pass 0 1 Valid Cal. Gas 270 CO2 01/17/24 mid DT0019792 11/10/30 P1 percent 11 11 0.00% Pass 0 1 Valid Cal. Gas 270 CO2 01/17/24 high SA12912 02/04/30 P1 percent 17.9 18.1 0.90% Pass 0 1 Valid Cal. Gas 270 NOx 01/17/24 low DT0035319 04/05/30 P1 ppm 101.3 100.9 0% Pass 0 1 Valid Cal. Gas 270 NOx 01/17/24 mid DT0019792 11/10/30 P1 ppm 218.3 218 0% Pass 0 1 Valid Cal. Gas 270 NOx 01/17/24 high SA12912 02/04/30 P1 ppm 356.8 363 2% Pass 0 1 Valid Cal. Gas 270 SO2 01/17/24 low DT0035319 04/05/30 P1 ppm 203.4 199.9 1.70% Pass High 1 Valid Cal. Gas 270 SO2 01/17/24 mid DT0019792 11/10/30 P1 ppm 438.4 441 0.60% Pass High 1 Valid Cal. Gas 270 SO2 01/17/24 high SA12912 02/04/30 P1 ppm 672.7 705 4.60% Pass High 1 Valid Cal. Gas 270 CO2 01/24/24 low DT0035319 04/05/30 P1 percent 4.9 5 2.00% Pass 0 1 Valid Cal. Gas 270 CO2 01/24/24 mid CC2949 11/07/30 P1 percent 11.1 11 0.90% Pass 0 1 Valid Cal. Gas 270 CO2 01/24/24 high SA12912 02/04/30 P1 percent 18.3 18.1 1.30% Pass 0 1 Valid Cal. Gas 270 NOx 01/24/24 low DT0035319 04/05/30 P1 ppm 101.8 100.9 0.90% Pass 0 1 Valid Cal. Gas 270 NOx 01/24/24 mid CC2949 11/07/30 P1 ppm 215.6 214 0.80% Pass 0 1 Valid Cal. Gas 270 NOx 01/24/24 high SA12912 02/04/30 P1 ppm 360.8 363 0.60% Pass 0 1 Valid Cal. Gas 270 SO2 01/24/24 low DT0035319 04/05/30 P1 ppm 204.3 199.9 2% Pass High 1 Valid Cal. Gas 270 SO2 01/24/24 mid CC2949 11/07/30 P1 ppm 435.8 437 0% Pass High 1 Valid Cal. Gas 270 SO2 01/24/24 high SA12912 02/04/30 P1 ppm 682.5 705 3% Pass High 1 270 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0 1 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code Channel Start Date Start Time End Date End Time Hours 1 0 0 0 1/0/00 0:00 1/0/00 0:00 1 1 None Reported 1 0 TC 220 Hours 44.90 TC 220 Hours 0.00 TC 230 Hours 0.00 Events 0.00 Hours 0.00 Events 0.00 0.00 1 44.99 TC 300 Hours 0.09 FALSE 0 2 0 1 1 1 1 2 1 1 1 1 1 2 2 2 2 0 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) Type Code 220 (Monitor Outage During Point Source Operation) Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) Type Code 240 (CEM Modifications) Type Code 530 (Excess Emissions During Emergency Conditions) Type Code 450 (Data Excluded) Type Code 550 (Changes in Operation in Control Equipment When CEM Data Not Available) Type Code 500 (Boiler Operating Days w/o 18 Hours of Data) 1 1 Point Source Point Source Point Source Yes None Reported None Reported None Reported None Reported None Reported None Reported 2 2 2 Pacificorp Huntington EER 1Q2024 Relative Accuracy Overview Point Source Channel Date of Most Current RATA Date of Preceding RATA Months Between RATA's Units Measured CEM Value Reference Method Value Relative Accuracy Pass/ Fail 2024 1 SO2 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil.0.057 0.06 9.60% Pass 1 NOx 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil.0.204 0.20 4.40% Pass 1 CO2 04/13/23 07/25/22 8.61 Percent 10.8 11.00 3.10% Pass 1 CO 04/13/23 07/25/22 8.61 #/MMBtu,CO2dil.0.169 0.17 4.00% Pass 1 CO 04/13/23 07/25/22 8.61 #/hr 770.9 823.20 9.70% Pass 2 CO2 04/14/23 06/29/22 9.5 Percent 10.7 10.50 3.10% Pass 2 NOx 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil.0.228 0.23 2.00% Pass 2 SO2 04/14/23 06/29/22 9.5 #/MMBtu,CO2dil.0.074 0.07 0.50% Pass * NSPS CGA First 2024 Audit Gas Ranges Audit Gas Ranges AP1 Low AP2 Low AP1 High AP2 High 1 CO 1/18/24 1000 250 200 to 300 1 CO 1/18/24 1000 547 500 to 600 * Acid Rain Audit Linearity First 2024 Low Span Gas Ranges High Span Gas Ranges Low Mid High Low Mid High 1 CO2 1/17/24 20 5 4 to 6 1 CO2 1/17/24 20 11 10 to 12 1 CO2 1/17/24 20 18.1 16 to 20 1 NOx 1/17/24 400 100.9 80 to 120 1 NOx 1/17/24 400 218 200 to 240 1 NOx 1/17/24 400 363 320 to 400 1 SO2 1/17/24 800 199.9 160 to 240 1 SO2 1/17/24 800 441 400 to 480 1 SO2 1/17/24 800 705 640 to 800 2 CO2 1/24/24 20 5 4 to 6 2 CO2 1/24/24 20 11 10 to 12 2 CO2 1/24/24 20 18.1 16 to 20 2 NOx 1/24/24 400 100.9 80 to 120 2 NOx 1/24/24 400 214 200 to 240 2 NOx 1/24/24 400 363 320 to 400 2 SO2 1/24/24 800 199.9 160 to 240 2 SO2 1/24/24 800 437 400 to 480 2 SO2 1/24/24 800 705 640 to 800 * Audit Gas Used High Span Audit Gas Used High SpanAudit Gas Used Point Source Channel Audit Date Low Span Point Source Channel Audit Date Low Span Audit Gas Used Pacificorp Huntington EER 1Q2024 Type Code 280 (COMS Attenuator Filters) Procedure 3 Point Source Location Attenuator I.D. Attenuator Certification Date Certified Attenuator Opacity OPLR, SECR, or PLCF, Corrected Opacity Value Range Low, Mid, & High Certification 1-year or 5-year 1 A YN-91 10/9/23 12 0.632 14.56 L 1 1 A YN-92 10/9/23 19 0.632 22.72 M 1 1 A YN-93 10/9/23 28 0.632 34.43 H 1 1 B YN-91 10/9/23 11.7 0.632 14.56 L 1 1 B YN-92 10/9/23 18.5 0.632 22.72 M 1 1 B YN-93 10/9/23 28.4 0.632 34.43 H 1 2 2 VL-84 10/9/23 28.9 0.245 15.36 L 1 2 2 VL-85 10/9/23 45.2 0.245 25.52 M 1 2 2 VL-86 10/9/23 69.9 0.245 44.48 H 1 * Opacity Monitor Response (Average of 5) Low Range Mid Range High Range 1 A 2/1/24 15 0.170 0.060 0.140 0.000 1 A 2/1/24 23 -0.050 0.060 0.140 0.000 1 A 2/1/24 35 0.200 0.060 0.140 0.000 1 B 1/31/24 14 -0.190 0.060 0.140 0.000 1 B 1/31/24 22 -0.320 0.000 0.000 0.000 1 B 1/31/24 34 -0.030 0.000 0.000 0.000 2 2 2/6/24 15 -0.040 0.030 0.070 0.000 2 2 2/6/24 25 -0.150 0.060 0.140 0.000 2 2 2/6/24 45 0.400 0.030 0.070 0.000 * Point Source Location Audit Date Alternitive Zero Alignment (Yes or No) COM Clear Condition Zero Response (CCZR) COM Simulated Zero Response (CSZR) Zero Alignment Error Difference (CCZR)-(CSZR) Adjustment to COM Simulated Zero Response (CSZR) (Yes or No) 1 A 2/1/24 yes 0.600 0.000 0.600 yes 1 B 1/31/24 yes -0.100 0.000 -0.100 yes 2 2 2/6/24 yes 0.200 0.000 0.200 yes Type Code 282 (Procedure 3 - Annual Zero Alignment Audit) Point Source Location Audit Date Mean Difference Standard Deviation Confidence Coefficient Calibration Error (≤ 3%) Type Code 281 (Procedure 3 - COMS Filter Audit Calibration Error) Pacificorp Huntington EER 1Q2024 Monitoring Information TC 210, 230, & 240 Type Code 210 (Pollutant Concentration Exceeded Span of CEM) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank)0 0 Grand Total 0 0 * Type Code 230 (Manual Sample - Alternate Sampling During Monitor Outage) - 500 (All) * Sum of Hours Column Labels Row Labels (blank) Grand Total (blank)0 0 Grand Total 0 0 * Type Code 240 (CEM Modifications) - 100 (All) * Count of Channel Column Labels Row Labels (blank) Grand Total (blank) (blank) Grand Total Pacificorp Huntington EER 1Q2024 Type Code 220 (Monitor Outage During Point Source Operation) - 600 (All) * Sum of Hours Column Labels Row Labels 723 722 724 Grand Total 1 Opacity The monitor was unavailable during the daily monitor calibration as required by 40 CFR parts 60 and 75.7.58 7.58 An opacity monitor filter check and/or audit was conducted followed by a manual calibration.3.17 3.17 A manual calibration was performed which was then followed by an auto calibration to verify system accuracy.0.18 0.18 A loss/interuption of power or communication to the DCS and/or monitor resulted in a loss of data. Power/communication was restored and the monitor was returned to service. 0.08 0.08 SO2 Maintenance checks and adjustments recommended by the service rep. were performed. Calibration checks were then performed and the system was returned to service. 3.98 3.98 NOx Maintenance checks and adjustments recommended by the service rep. were performed. Calibration checks were then performed and the system was returned to service. 3.98 3.98 CO2 Maintenance checks and adjustments recommended by the service rep. were performed. Calibration checks were then performed and the system was returned to service. 3.98 3.98 CO Maintenance checks and adjustments recommended by the service rep. were performed. Calibration checks were then performed and the system was returned to service. 3.98 3.98 2 Opacity The monitor was unavailable during the daily monitor calibration as required by 40 CFR parts 60 and 75.7.58 7.58 An opacity monitor filter check and/or audit was conducted followed by a manual calibration.1.38 1.38 A loss/interuption of power or communication to the DCS and/or monitor resulted in a loss of data. Power/communication was restored and the monitor was returned to service. 0.08 0.08 SO2 Maintenance checks and adjustments recommended by the service rep. were performed. Calibration checks were then performed and the system was returned to service. 1.98 1.98 Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 0.98 0.98 NOx Maintenance checks and adjustments recommended by the service rep. were performed. Calibration checks were then performed and the system was returned to service. 1.98 1.98 Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 0.98 0.98 CO2 Maintenance checks and adjustments recommended by the service rep. were performed. Calibration checks were then performed and the system was returned to service. 1.98 1.98 Maintenance of another monitor required normal sampling to be interrupted. The system was returned to service following the maintenance. 0.98 0.98 Grand Total 41.78 0.17 2.95 44.90 Pacificorp Huntington EER 1Q2024 Sum of Hours Column Labels Row Labels 723 722 724 Grand Total Pacificorp Huntington EER 1Q2024 Opy * Opy Count of Magnitude of Emissions Column Labels Opy Row Labels Grand Total Opy Grand Total SO2 * SO2 Type Code 410 (SO2) - 6000 (All) SO2 * SO2 Count of Magnitude of Emissions Column Labels SO2 Row Labels Grand Total SO2 Grand Total NOx * NOx Type Code 420 (NOx) - 6000 (All) NOx * NOx Count of Magnitude of Emissions Column Labels NOx Row Labels Grand Total NOx Grand Total NOx d * NOx d Type Code 421 (Daily NOx Emissions) - 500 (All) NOx d * NOx d Count of Reason Code Column Labels NOx d Row Labels (blank)Grand Total NOx d 1 NOx d 0 NOx d 2 NOx d 0 NOx d Grand Total CO * CO Type Code 440 (CO) - 6000 (All) CO * CO Count of Magnitude of Emissions Column Labels CO Row Labels Grand Total CO Grand Total Pacificorp Huntington EER 1Q2024 Type Code 500 Before February 28, 2005 (Boiler Operating Days w/o 18 Hours of Data) After February 28, 2005 (90% Operating Hours For each 30 BOD) - 500 (All) * Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 510 (F-factor, Equations & Conversion Factors) - 500 (All) Count of F-factor Column Labels Row Labels Grand Total Grand Total * Type Code 520 (Minimum Data Not Obtained <22/30 BODs) - 500 (All) Count of Channel Column Labels Row Labels Grand Total Grand Total * Type Code 530 (Excess Emissions During Emergency Conditions) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * Type Code 540 (Fuel Pre-treatment Credit SO2) - 500 (All) Count of Date Column Labels Row Labels Grand Total Grand Total * TypeCode 550 (Changes in Operation in Control Equipment When CEM Data Not Available) - 500 (All) Column Labels Row Labels Grand Total Grand Total