HomeMy WebLinkAboutDDW-2024-007414J. Paul Wright <pwright@utah.gov> Spring Creek Well REPL-1 (WS004) Equipping - Review Comments File #12623 James Saunders <james.s@jonesanddemille.com>Thu, Apr 25, 2024 at 5:35 PM To: "J. Paul Wright" <pwright@utah.gov>, Daniel Hawley <daniel.h@jonesanddemille.com> Cc: Heather Pattee <hpattee@utah.gov>, "tracyfeltner04@gmail.com" <tracyfeltner04@gmail.com>, Hunter Cornelius <hunter.c@jonesanddemille.com> Paul, Thanks for your review. We have addressed your comments and have made some clarifications to the drawings and the manual. We have talked with Heather and All Wells, and we intend to change order this work into All Wells well drilling contract. This will save the project time and cost from bidding this work out. Below are our responses to your comments. Thanks, James 1. Sheet C102 says that the 3" pump to waste line will be "reinstalled". Is there a detail of how this is configured? I need to be sure that at its discharge point it is downturned, has an adequate freefall to the ground or receiving basin, and that the end is covered with a #4 mesh screen. a. Detail D1 on Sheet C503 has been added for clarity. The discharge will be downturned and screened. 2. On Sheet C103, is the air valve that will be reinstalled downturned and with a #14 mesh screen on the end? a. Detail A1 on Sheet C103 has been updated to indicate a #14 mesh screen. 3. Is the sample tap to be reinstalled a smooth nosed sample tap? a. The sample tap is smooth nosed. Let me know if you have any questions. Thanks, James James Saunders, PE Project Engineer Jones & DeMille Engineering, Inc. p: (435) 637-8266 | m: (435) 757-0308 [Quoted text hidden] 5/1/24, 8:32 AM State of Utah Mail - Spring Creek Well REPL-1 (WS004) Equipping - Review Comments File #12623 https://mail.google.com/mail/u/0/?ik=f3bcb897f8&view=pt&search=all&permmsgid=msg-f:1797351715983629155&simpl=msg-f:1797351715983629155 1/3 From: J. Paul Wright <pwright@utah.gov> Sent: Wednesday, April 17, 2024 3:15 PM To: Daniel Hawley <daniel.h@jonesanddemille.com> Cc: James Saunders <james.s@jonesanddemille.com>; Heather Paee <hpattee@utah.gov>; tracyfeltner04@gmail.com Subject: Spring Creek Well REPL-1 (WS004) Equipping - Review Comments File #12623 Daniel and James, I have reviewed the plans that were submitted for equipping this replacement well. It appears, in general, that the plan is to use the discharge piping and valving from the existing well. I have a couple of comments/questions based on what was shown in the plans: 1) Sheet C102 says that the 3" pump to waste line will be "reinstalled". Is there a detail of how this is configured? I need to be sure that at its discharge point it is downturned, has an adequate freefall to the ground or receiving basin, and that the end is covered with a #4 mesh screen. 2) On Sheet C103, is the air valve that will be reinstalled downturned and with a #14 mesh screen on the end? 3) Is the sample tap to be reinstalled a smooth nosed sample tap? Once I have confirmation that these items are compliant, I can move forward with preparing the equipping plan approval letter. Paul On Mon, Mar 18, 2024 at 3:41 PM Daniel Hawley <daniel.h@jonesanddemille.com> wrote: Good Afternoon Paul, We have been working with Spring Creek to wrap up a project where they had drilled a new well. The last item remaining on the project is to tie the new well into the system. Sorry for the delay on this one. The Owner was investigating options to increase flow and put in a larger pump which would require larger power to the pump house. They don’t need that and with the remaining funding be tight they plan to just take the pump from the old well and install it and then just raise the existing piping in their building so that it is over 18 inches off the floor. Should we send that to you or go through Heather Pattee to send the drawings for review? Thanks Paul, 5/1/24, 8:32 AM State of Utah Mail - Spring Creek Well REPL-1 (WS004) Equipping - Review Comments File #12623 https://mail.google.com/mail/u/0/?ik=f3bcb897f8&view=pt&search=all&permmsgid=msg-f:1797351715983629155&simpl=msg-f:1797351715983629155 2/3 Daniel Hawley, PE Project Manager Jones & DeMille Engineering, Inc. p: (435) 637-8266 | m: (435) 201-2507 Shaping the Quality of Life. -- J. Paul Wright, P.E. | District Engineer | Southwest Utah District 435.986.2590 (office) | 435.680.0163 (cell) | 435.986.2595 (fax) 620 S 400 E #400, St. George, UT 84770 DEQ WEBSITE Emails to and from this email address may be considered public records and thus subject to Utah GRAMA requirements. 3 attachments 2009-071 Project Drawings.pdf 4619K 2009-071 Well Equipping Bid Schedule.pdf 13K 2009-071 Well Equipping Project Manual.pdf 2066K 5/1/24, 8:32 AM State of Utah Mail - Spring Creek Well REPL-1 (WS004) Equipping - Review Comments File #12623 https://mail.google.com/mail/u/0/?ik=f3bcb897f8&view=pt&search=all&permmsgid=msg-f:1797351715983629155&simpl=msg-f:1797351715983629155 3/3