HomeMy WebLinkAboutDERR-2024-006693 WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PRODUCT PIPING INTEGRITY TESTING
Facility Name: Point of the Mountain Fueling Facility Owner: Geneva Rock Products, Inc.
Address: 15547 South 300 West Address: 730 North 1500 West
City, State, Zip: Draper, Utah 84020 City, State, Zip: Orem, Utah 84057
Facility I.D.#: 4002207 Phone #: 801-802-6954
Testing Company: Westech Phone #: 801-266-2545 Date: 4/10/24
This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester.
Tank Number 1 & 2 Sat. 1 Sat. 6 3
Product Stored DSL DSL DSL Off-Road DSL
Piping Run Shared Satellite Satellite Only
Piping Type Flex Flex Flex Flex
Test Pressure (PSI) 50 50 50 50
Test Duration (minutes) 30 30 30 30
Leak Rate (GPH) 0.002 0.000 0.000 0.001
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
Diesel
Off-Road Diesel
Diesel
Diesel
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PRODUCT PIPING INTEGRITY TESTING
Facility Name: Point of the Mountain Fueling Facility Owner: Geneva Rock Products, Inc.
Address: 15547 South 300 West Address: 730 North 1500 West
City, State, Zip: Draper, Utah 84020 City, State, Zip: Orem, Utah 84057
Facility I.D.#: 4002207 Phone #: 801-802-6954
Testing Company: Westech Phone #: 801-266-2545 Date: 4/10/24
This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester.
Tank Number 4
Product Stored DSL
Piping Run Only
Piping Type Flex
Test Pressure (PSI) 50
Test Duration (minutes) 30
Leak Rate (GPH) 0.003
Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
Diesel
Off-Road Diesel
Diesel
Diesel
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
MECHANICAL AND ELECTRONIC LINE LEAK DETECTOR PERFORMANCE TESTS
Facility Name: Point of the Mountain Fueling Facility Owner: Geneva Rock Products, Inc.
Address: 15547 South 300 West Address: 730 North 1500 West
City, State, Zip: Draper, Utah 84020 City, State, Zip: Orem, Utah 84057
Facility I.D.#: 4002207 Phone #: 801-802-6954
Testing Company: Westech Phone #: 801-266-2545 Date: 4/10/24
This data sheet can be used to test the mechanical line leak detector (MLLD) and electronic line leak detector (ELLD) with submersible turbine
pump (STP) systems. See PEI/RP 1200 Sections 9.1 and 9.2 for test procedures.
Line Number 1 2 3 4
Product Stored DSL DSL Red DSL DSL
Leak Detector Manufacturer Red Jacket Red Jacket Red Jacket Red Jacket
Leak Detector Model FX1DV FX1DV FX1DV FX1DV
Type Of leak Detector
☒MLLD
☐ELLD
☒MLLD
☐ELLD
☒MLLD
☐ELLD
☒MLLD
☐ELLD
MLLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG)
STP full operating pressure 31 31 35 31
Check valve holding pressure 18 19 24 5
Line resiliency (ml) (line bleedback volume as measured
from check valve holding pressure to 0 psig) 130 130 95 10
Step through time in seconds (time the MLLD hesitates at
metering pressure before going to full operating pressure as
measured from 0 sig with no leak induced on the line)
1 1 1 3
Metering pressure (STP pressure when simulated leak rate 3
gph at 10 psig) 10 11 12 11
Opening time in seconds (the time the MLLD opens to allow
full pressure after simulated leak is stopped) 29 3 10 6
Does the STP pressure remain at or below the metering
pressure for at least 60 seconds when the simulated leak is
induced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
Does the leak detector reset (trip) when the line pressure is
bled off to zero psig? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
Does STP properly clycle on/off under normal fuel system
operating conditions? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
A "No" answer to any of the above questions indicates that the MLLD fails the test.
ELLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG)
STP full operating pressure
How many test cycles are observed before alarm/shutdown
occurs?
Does the simulated leak cause on alarm? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
A "No" answer to the above question indicates that the ELLD fails the test.
Does the simulated leak cause an STP shutdown? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name: Point of the Mountain Fueling Facility Owner: Geneva Rock Products, Inc.
Address: 15547 South 300 West Address: 730 North 1500 West
City, State, Zip: Draper, Utah 84020 City, State, Zip: Orem, Utah 84057
Facility I.D.#: 4002207 Phone #: 801-802-6954
Testing Company: Westech Phone #: 801-266-2545 Date: 4/10/24
This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection
procedure. This procedure is applicable to tank monitor stems the touch the bottom of the tank when in place.
Tank Number 1 2 3 4
Product Stored DSL DSL Red DSL DSL
ATG Brand and Model TLS-300 TLS-300 TLS-300 TLS-300
1. Tank Volume, gallons 11,627 11,627 11,627 5,929
2. Tank Diameter, inches 92 92 92 92
3. After removing the ATG from the tank, it has been
inspected and any damaged or missing parts replaced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
4. Float moves freely on the stem without binding? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
5. Fuel float level agree with the value programmed
into the console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
6. Water float level agree with the value programmed
into the console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
7. Inch level from the bottom of the stem when 90%
alarm is triggered? 77 1/8 77 1/8 77 1/8 77
8. Inch level at which the overfill alarm activates
corresponds with the value programmed in the
gauge?
☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
9. Inch level from the bottom when the water float
first triggers an alarm? 2 2 2 2
10. Inch level at which the water float alarm activates
corresponds with the value programmed in the
gauge?
☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
If any answers in Lines 3, 4, 5, or 6 are "No" the system has failed the test.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
UST OVERFILL EQUIPMENT INSPECTION
AUTOMATIC SHUTOFF DEVICE AND BALL FLOAT VALVE
Facility Name: Point of the Mountain Fueling Facility Owner: Geneva Rock Products, Inc.
Address: 15547 South 300 West Address: 730 North 1500 West
City, State, Zip: Draper, Utah 84020 City, State, Zip: Orem, Utah 84057
Facility I.D.#: 4002207 Phone #: 801-802-6954
Testing Company: Westech Phone #: 801-266-2545 Date: 4/10/24
This data sheet is for inspecting automatic shutoff devices and ball float valve. See PEI/RP1200 Section 7 for inspection procedures.
Product Grade DSL DSL Red DSL DSL
Tank Number 1 2 3 4
Tank Volume, gallons 11,627 11,627 11,627 5,929
Tank Diameter, inches 92 92 92 92
Overfill Prevention Device Brand Franklin Franklin Franklin Franklin
Type ☒ Automatic
Shutoff Device
☐ Ball Float
Valve
☒ Automatic
Shutoff Device
☐ Ball Float
Valve
☒ Automatic
Shutoff Device
☐ Ball Float
Valve
☒ Automatic
Shutoff Device
☐ Ball Float
Valve
AUTOMATIC SHUTOFF DEVICE INSPECTION
1. Drop tube removed from tank? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
2. Drop tube and float mechanisms free of debris? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
3. Float moves freely without binding and poppet moves
into flow path? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
4. Bypass valve in the drop tube open and free of
blockage (if present)?
☐Yes ☐No
☒Not Present
☐Yes ☐No
☒Not Present
☐Yes ☐No
☒Not Present
☐Yes ☐No
☒Not Present
5. Flapper adjusted to shut off flow at 95% capacity? * ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
A "No" to any item in Lines 1-5 indicates a test failure.
BALL FLOAT VALVE INSPECTION**
1. Tank top fitting vapor-tight and leak free? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
2. Ball float cage free of debris? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
3. Ball free of holes and cracks and moves freely in cage? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
4. Vent hole in pipe open and near top of tank? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
5. Ball float pipe proper length to restrict flow to 90%
capacity? *** ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
A "No" to any item in Lines 1-5 indicates a test failure.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail
Comments:
*Use manufacturer’s suggested procedure for determining if automatic shutoff device will shut off flow at 95% capacity.
**If a ball float valve is found to fail the inspection, another method of overfill must be used.
***Use manufacturer’s suggested procedure for determining if flow restriction device will restrict flow at 90% capacity.
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature