HomeMy WebLinkAboutDDW-2024-007397Contacts
Type: Administrative Contact
Name: KENNY ENGLAND
Office: 801-525-4430
Emergency:
Email:
kenny.england@clearfieldcity.org
Site Information
Legal Contact: CLEARFIELD CITY
Address: 55 S STATE ST ,
CLEARFIELD, UT 84015
Phone: 801-525-2700
County: DAVIS COUNTY
System Type: Community
Certification Required: D4
Total Population: 33540
Local Health District: Davis County
Health Department
Site Updates
Last Inventory Update: 12/20/2023
Last Surveyor Update:
Surveyor:
Operating Period: / - /
Last IPS Update: 04/18/2024 18:03:15
Political Districts
Representative: 14
Senate: 21
Water Usage Information per ERC
Total Ips Points: 105
Public Water System IPS ReportDEQ | Drinking Water
Clearfield City Water System PWS ID: UTAH06002 Rating: Approved 03/04/1980 Status: Active
IPS SUMMARY Total IPS Points: 105
Admin & Physical Facilities Quality & Monitoring Significant Deficiency Violations
55 0 50
PHYSICAL FACILITY POINTS Total Pts: 55
Facility Facility Name Status Points Effective Details
DS001 DISTRIBUTION SYSTEM A 15 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending Assessed
A025
Administrative issues -
see notes for specific
details
MIN WATER USE DATA -INFORMATION NECESSARY TO
ESTABLISH THE SYSTEM SPECIFIC STANDARDS 01/01/2020 0 15
ST002 HILL AIR FORCE BASE TANK A 25 Hide Details ( 4 )
Code Description Severity Comments Determined
Date Pending Assessed
V011
END OF STORAGE
TANK OVERFLOW
LACKS A
CLEARANCE OF
BETWEEN 12 AND 24
INCHES FROM
GROUND SURFACE
SIG Could not see 10/02/2023 25
25*
(group-
35)
V012
END OF STORAGE
TANK OVERFLOW
PIPE LACKS NO. 4
SCREEN
SIG Could not see 10/02/2023 0 25
V013
STORAGE TANK
OVERFLOW PIPE IS
CONNECTED TO OR
DISCHARGES TO
SANITARY SEWER
SIG Could not see 10/02/2023 50 0
V016
END OF TANK DRAIN
LINE LACKS A
CLEARANCE OF AT
LEAST 12 INCHES
SIG Could not see 10/02/2023 25 0
ST006 NEW FREEPORT TANK A 0 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending Assessed
V011
END OF STORAGE
TANK OVERFLOW
LACKS A
CLEARANCE OF
BETWEEN 12 AND 24
INCHES FROM
GROUND SURFACE
SIG Over flow line is in a receiving basin below ground surface 10/02/2023 25
25*
(group-
35)
TP001 700 SOUTH FLUORIDATION A 15 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending Assessed
TF44
NO SAMPLE TAP
AVAILABLE FOR
TESTING FL LEVEL
IN TREATED WATER
MIN 10/02/2023 0 15
WS001 RESERVOIR WELL I 0 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending Assessed
S009
PUMP TO WASTE
LINE LACKS
PROPER AIR GAP
SIG Discharges to storm drain.10/02/2023 25 0
WS006 HILL AFB WELL I 0 Hide Details ( 1 )
PHYSICAL FACILITY POINTS Total Pts: 55
Facility Facility Name Status Points Effective Details
Code Description Severity Comments Determined
Date Pending Assessed
S024
NO CHECK VALVE
ON WELL
DISCHARGE PIPING
MIN Did not have a check valve.09/29/2020 5
SIGNIFICANT DEFICIENCY VIOLATIONS Total Pts: 50
ID Violation Code Deficiency Determined
Points
Effective
ST002
45 FAILURE ADDRESS DEFICIENCY
(GWR)
V012
END OF STORAGE TANK OVERFLOW PIPE LACKS NO.
4 SCREEN
04/18/2024 50
LEAD COPPER MONITORING AND QUALITY VIOLATIONS Total Pts: 0
Violation No.Period Code Description/Name Points Effective
CHEMICAL MONITORING RULE VIOLATIONS Total Pts: 0
Facility Violation No Period Code Violation Type Analyte Group Determined Seasonality Points Effective
TREATMENT VIOLATIONS Total Pts: 0
Facility Violation No Period Code Violation Type Analyte Group Determined Points Effective
MICROBIAL RULE VIOLATIONS
Date Range Start: 04/01/2023
Total Pts: 0
Determine Date Compliance Period Code Violation Type Return To Compliance Points Effective
OPERATOR CERTIFICATION
Type Level Required Highest Certificate
Distribution Dist 4 Dist 4
Treatment
CONSUMER CONFIDENCE REPORT Total Effective Points: 0
Violation No.Period Code Description/Name Points Effective
PUBLIC NOTIFICATION VIOLATIONS Total Pts: 0
Violation No.Date Code Description/Name Points Effective
IPS COMPLIANCE SCHEDULES
Type Required Activities Severity Created Due
CCR SCHEDULES Submit Consumer Confidence Report 01/01/2024 07/01/2024
CCR SCHEDULES Submit CCR Certification Letter 01/01/2024 10/01/2024
CORRECTIVE ACTION
PLAN
END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN SIG 10/13/2023 03/15/2024
CORRECTIVE ACTION
PLAN
END OF TANK DRAIN LINE LACKS A CLEARANCE OF AT LEAST 12 INCHES SIG 10/13/2023 12/01/2024
CORRECTIVE ACTION
PLAN
END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12
AND 24 INCHES FROM GROUND SURFACE
SIG 10/13/2023 12/01/2024
CORRECTIVE ACTION
PLAN
PUMP TO WASTE LINE LACKS PROPER AIR GAP SIG 10/13/2023 12/01/2024
CORRECTIVE ACTION
PLAN
END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12
AND 24 INCHES FROM GROUND SURFACE
SIG 10/13/2023 12/01/2024
CORRECTIVE ACTION
PLAN
STORAGE TANK OVERFLOW PIPE IS CONNECTED TO OR DISCHARGES TO
SANITARY SEWER
SIG 10/13/2023 12/01/2024
Lead Copper Rule
Revisions
SUBMIT LEAD SERVICE LINE INVENTORY 12/16/2021 10/16/2024
Lead Copper Rule
Revisions
COMPLETE INITIAL LSL INVENTORY 12/16/2021 10/16/2024