Dear Mr. Roberts:
SUBJECT: November 30, 2010 DUSA Cell 4B Construction Quality Assurance [CQA] Report',
DRC Email dated December 14, 2010, Regarding GWDP Part I.H.I 1; December 21, 2010
GeoSyntec Letter, Response to Construction Deficiencies; DRC Letters dated December
9, 2010, November 24, 2010, and November 15, 2010, Conceming Cell 4B ConsUoiction
Inspections; Review of CeU 4B Construction and Request for Information
We received the subject November 30, 2010 DUSA Cell 4B Construction Quality Assurance [CQA]
Report. We have reviewed the subject report and items above, and have the following comments and
requests:
1. The Construction Drawings. The originally dated November 2009 Construction Drawings are
mentioned in the report, paragraph 3.2. Several design change notifications (DCN) are
provided in Appendix B. It appears that revisions of the original drawings, except for sheets 1
and 6 are included in the subject CQA Report. Please provide for these missing drawing
sheets 1 and 6, as revised for construction, in the report.
2. The Slimes Drain Header.
a. As discussed last month by telephone, please provide one or more photographs,*
demonstrating that the along the slimes drain header in the SE comer of the cell, that the
slimes drain header is ballasted continuously on both sides, as requested in the subject
DRC Email dated December 14, 2010.
b. In the subject GeoSyntec letter of December 21, 2010, photographs nos. 1 and 2 show
there are two separate sand bag lines crossing over the woven geotextile,, which covers the
slimes drain header. Also photograph no. 34 in Appendix A ofthe subject CQA Report
* All photographs need to be dated, and have descriptive labels, identification of location, and background ofthe surroundings (to
reference the location).
195 North 1950 West-Salt Lake City, UT
Mailing Address: P.O. Box 144850 • Salt Lake City, UT 84114-4850
Telephone (801) 536-4250- Fax (801) 533-4097'T.D.D: (801) 536-4414
www.deq.utah.gov .
Printed on 100% recycled paper
Page 2
show sandbags crossing Over the woven geotextile covering the slimes drain access pipe.
It appears these bags may have been placed to ballast woven geotextile joints without
sewing such joints. According to the subject CQA Plan paragraph 11.7 and the CQA
Report, paragraph 6.6.3.3, the woven geotextile is to be sewn at all joints. Please provide
photographs* to demonstrate that these locations, including examples of the other woven
geotextile joints, have been sewn in accordance with these specifications.
Strip Drains.
a. Page 7 of the subject CQA Report discusses design change notification (DCN) -006. It
states, 'This design change modifies the specificadons to allow the placement of additional
sand bags parallel and adjacent to the existing sand bags if the underlying strip composite
is visible." In contrast, the subject GeoSyntec letter of December 21, 2010, page 3, the
fifth paragraph, the first sentence contains a phrase which states, "...sand bags are no
longer placed along the sides of.. .bags, which have been rearranged to comply with
coverage and thickness requirements..." It appears the intent.of this statement may be to
cancel DCN-006, i.e. perhaps now there is no parallel and adjacent sand bags to strip-
drains installed on the project. However, this statement in the letter may be interpreted in
more than one way. Therefore, verbiage in the current CQA Report, regarding DCN-006
need to be clarified as to the preservation of any parallel sand bag placements adjacent to
strip drain lines.
b. As mentioned in a telephone conversation with you last month, we request a drawing or
manufacturer's catalog cuts, etc., showing the engineer's approved method, used during
this construction, to change the direction of the slimes strip drains.
(1) . There are several locations shown on the original plans requiring the direction of
the strip-drains to change. Please demonstrate the method used with example
photographs* of such use.
(2) . Numerous photographs of the strip-drain lines in Appendix M of the CQA Report
as well as some surveyed strip-drain lines in Appendix K demonstrate strip-drain
lines locations where the strip slimes drains have been tumed from their original
course to "short-cut intersect" the slimes drain header perpendicularly. Please
demonstrate the method used at these locations with example photographs* of such
use as well.
c. Specific Strip Drains. As you are aware, there have been several concems raised regarding
sand bags covering the strip drains. These concems are mentioned in the subject DRC
letters referenced at the beginning of this letter. DRC letter dated December 9, 2010 states
that, "each individual line of strip-drain and sandbag cover will be reviewed, corrected as
needed, and separately documented by GeoSyntec. Further, that an individual record for
each strip-drain will be made by GeoSyntec in the as-built report [the CQA Report], or as
an addendum thereto. This element will be critical to obtain final DRC approval of the
strip-drain/sand bag system."
In the construction inspection chronology, DUSA conveyed the subject CQA Report to
DRC via letter dated November 30, 2010. That date is the same date as a DRC _
* All photographs need to be dated, and have descriptive labels, identification of location, and background of the surroundings (to
reference the location).
Page 3
construction inspection, summarized by our mentioned letter dated December 9, 2010.
That letter stated some general concems regarding the strip drain sand bag placement. The
subject GeoSyntec response letter of December 21, 2010 was written to address these DRC
concems. However, the GeoSyntec letter, in general, was not specific to individual strip
drains, per the intent of the DRC letter of December 9, 2010. In our telephone
conversation last month, you mentioned that DUSA has strived to correcdy reorient errant
sand bag installation work.
The CQA Report, Appendix M, provides photographs pertaining to each strip drain. After
review of such, we request the following:
(1) . Photographs* of reworked strip-drains 31 and 51, demonstradng no "piggy-
backing" or "fallen dominoes" type stacking of those bags.
(2) . Photographs* of reworked strip-drains 15, 16, 17, 18, 19, 20, 21, 22, and 23
demonstrating the following:
(a) . The bags have been reoriented properly.
(b) . That if any parallel bags (per DCN-006) are used, the parallel bags are not
piggy-backed or fallen domino stacked onto the strip-drain sand bags. Our
previous comment in paragraph 3a above, discusses some concems with
respect to DCN-006.
4. We are unaware if a fence has been installed or contemplated to be installed surround the Cell 4B
site. A fence surrounding wastewater ponds is a requirement of UAC R317-3-10.8, which states,
"Fencing. The lagoon area shall be enclosed with not less than 6 feet high chain link fence to
prevent entering of livestock and to discourage trespassing. Fencing must not obstmct vehicle
traffic on top of the dikes. A vehicle access gate of sufficient width to accommodate all
maintenance equipment shall be provided. All access gates shall be provided with locks." We
anticipate that contingent use of Cell 4B may be authorized, if a fence is installed in a reasonable
period of time.
PJease review the above comments, and respond in writing, supplying the requested documentafion,
including photographs,* and needed adjustments, as an addendum to the CQA Report. The addendum must
be certified by a Utah-licensed Professional Engineer. Please include an electronic copy of the requested
information. DUSA's response time on this letter is left to DUSA's discretion, in as much as the approval
of Cell 4B CQA Report (As-Built Report) is a requirement of the Ground Water Discharge Permit, Part
I.H.9, for DRC authorizafion for use of Cell 4B. If you have questions on the above, please contact me.
Sincerely,
David A. Rupp, P.E.
Geotechnical Services' Section
DAR:LBM:dr
Cc: Mr. Greg Corcoran, GeoSyntec Consultants
F:\Cel) 4B\Constr\RFI 1 ConstrRevlew Jan-2011
* All photographs need to be dated, and have descriptive labels, identification of location, and background of the surroundings (to
reference the locations).