HomeMy WebLinkAboutDRC-2019-002465 - 0901a068809eab26UTAH DIVISION OF WASTE MANAGEMENT AND RADIATION CONTROL
RML # UT1900479
ENERGY FUELS RESOURCES WHITE MESA MILL
INSPECTION MODULE EM-01
SEMI-ANNUAL EFFLUENT MONITORING REPORT
REPORTING PERIOD: July 1, 2018 throug_h December 3 L 2018
D C. -20 i
References: Utah Administrative Code R313-24-4;
10CFR40.65;
Radioactive Materials License UT1900479;
10CFR20 Table II of Appendix B;
NRC Regulatory Guide 4.14;
2007 License Renewal Application
Inspector Russ Topham Date March 6, 2019
10CFR40.65(a)(1) requires the licensee to submit a report within 60 days after January 1 and July 1 of
each year. The report must specify the quantity of each of the principal radionuclides released to
unrestricted areas in liquid and in gaseous effluents during the previous six months of operation.
1. Did the licensee submit the report within 60 days of the end of the reporting period i.e., January 1st or
July 1st? (10CFR40.65(a)(1))
Yes Z No El
Comments:
The Semi-Annual Effluent Monitoring Report for the 2nd half of 2018 for the White Mesa Mill was
submitted on February 26, 2019
Page 1 of 8
2. Were the stack samples analyzed for U-nat, 230Th, 226Ra and 210Pb? (NRC Reg Guide 4.14) and Th-
228, Th-232 and Ra-228 (L.C. 11.9)
Yes [E] No LI Comments:
Stack sampling occurred only during quarters when the stack was operated.
3. Were site boundary effluent air samples analyzed for U-nat, 230Th, 226Ra and 210Pb? (NRC Reg
Guide 4.14) and Th-232 (L.C. 11.9)
Yes Noill
10CFR20 Appendix B Table 2 first paragraph states "The columns in Table 2 of this appendix captioned
"Effluents," "Air," and "Water," are applicable to the assessment and control of dose to the public,
particularly in the implementation of the provisions of § 20.1302. The concentration values given in
Columns 1 and 2 of Table 2 are equivalent to the radionuclide concentrations which, if inhaled or
ingested continuously over the course of a year, would produce a total effective dose equivalent of
0.05 rem (50 millirem or 0.5 millisieverts)."
Comments:
Sampling results were below ECLs for all analyzed isotopes at all monitoring locations for the last four
quarters, and for the year. See the attached Particulate, Radon and Gamma Screening analysis for a
summary of quarterly and annual data and a calculated dose at each of the high-volume air stations.
Page 2 of 8
1 OCFR20 Table II of Appendix B, ECL's:
.9.0E14 µCi/m1 in air
2.0E14 µCi/m1 in air
9.3E13 µCi/m1 in air
6.0E13 µCi/m1 in air
.....25% = 2.25E14 µCi/m1 in air
.....25% = 5.1 5E15 µCi/m1 in air
.....25% = 2.33E13 µCi/m1 in air
.....25% = 1.50E13 µCi/ml in air
U-nat 230Tb
226Ra 21opb
4. Were the site boundary effluent air sample results within applicable limits for U-nat, 2301.'n , 226 Ra and
210Pb? (1 OCFR20 Table II of Appendix B)
230Th 226Ra 9.3E13 tiCi/m1 in air 210pb 6 0E13 µCi/m1 in air
Yes Z No
Comments:
5. Did the results of the effluent monitoring for this reporting period achieve the site's ALARA
objective of 25% of the ECUs? (2007 License Renewal Application Vol. 1 Section 6.5; 1 OCFR20 Table
II of Appendix B)
Yes Z No El
Comments:
See the attached Particulate, Radon and Gamma Screening analysis for a summary of quarterly and
annual data and a calculated dose at each of the high-volume air stations. The summary compares total
dose to the mill's ALARA goal and to the annual 100 mrem exposure limit
1 OCFR20 Table II of Appendix B, ECUs:
U-nat .9.0E µCi/m1 in air
2 0E14 liCi/m1 in air
Page 3 of 8
6. Were Gamma Measurements (Minus Background) Collected at each Monitoring Station?
Yes No 0
Comments:
See the attached Particulate, Radon and Gamma Screening analysis for a summary of quarterly and
annual data and a calculated dose at each of the high-volume air stations.
7. Were soil samples analyzed for U-nat, 226Ra and 210Pb? (NRC Reg Guide 4.14)
Yes 0 No E] N/A III
Comments:
Soil sampling occurred during the first half of the year.
8. Were vegetation samples analyzed for 226Ra and 210Pb? (NRC Reg Guide 4.14) and U-Nat and Th-
232 (LC??)
Yes 111 No El
Comments:
Vegetation sampling occurred during the first half of the year.
Page 4 of 8
9. Were radon samples (minus background) taken at Sample Stations BHV-1, BHV-2, BHV-4, BHV-
5, BHV-6, BHV-7 and BHV-8? (NRC Reg Guide 4.14)
Yes Z No 0
Comments:
ECLs in 10 CFR 20 Appendix B Table 2 assume either no daughters present or 100% ingrowth.
Calculated ECLs account for partial ingrowth using methodology in EPA 520/1-88-009 p. 2-20.
Calculated ECLs result in maximum exposure of 25 mrem/yr vs. 50 mrem/yr using Table 2 value.
Regulatory limit is 100 mrem/yr. See the attached Particulate, Radon and Gamma Screening analysis
for a summary of quarterly and annual data and a calculated dose at each of the high-volume air stations.
10. Were radon samples analyzed for 222Rn9 (NRC Reg Guide 4.14)
Yes Z No El
Comments:
11. Were the 222Rn results within the calculated ECL's for the yearly average results for the last four
quarters?
Yes Z No El
Comments:
See the attached Particulate, Radon and Gamma Screening analysis for a summary of quarterly and
annual data and a calculated dose at each of the high-volume air stations.
Page 5 of 8
License Condition 11.2.D requires the licensee to utilize lower limits of detection in accordance with
Section 5 of the NRC Regulatory Guide 4.14, as amended, for analysis of effluent and environmental
samples.
12. Were lower limits of detection (LLD) for analysis of stack effluent samples 10% or less of the
limits found in 10CFR20 Table II of Appendix B for U-nat, 230Th, 226Ra and 210pb?
(NRC Reg Guide 4.14)
10CFR20 Table II of Appendix B. ECL's:
.9.0E14 1.iCi/m1
2 0E14 1..tCi/m1
U-nat
230Th 226Ra 9.3E13 • [tCl/m1 210pb 6 0E13 µ,Ci/m1
10% = 9.0E15 p.Ci/m1
10% = 2.0E15 µCi/m1
10% = 9.3E14 µCi/ml
10% = 6.0E14 plCi/m1
Yes Z No0
Comments:
LLDs in the analytical reports are called CRDL or RLs and they are identical to the numbers listed
above.
13. Were lower limits of detection (LLD) for analysis of site boundary air effluents within the limits
listed in NRC Regulatory Guide 4.14 Section 5 for U-nat, 230Th, 226Ra and 210Pb? (NRC Reg Guide
4.14)
NRC Regulatory Guide 4.14 Section 5 LLD values (in air):
1.0E16 1..tCi/m1
1 0E16 tiCi/m1
1 0E16 tiCi/m1
2 0E15 liCi/m1
Yes Z No 0
Comments:
The LLDs from documented in the analytical report are: U-nat 1E-16, Th-230 1E-16; Ra-226 1E-16 ,&
Pb-210 2E-15
U-nat 230Th
226Ra 210pb
Page 6 of 8
14. Were lower limits of detection (LLD) for analysis of site boundary soil samples within the limits
listed in NRC Regulatory Guide 4.14 Section 5 for U-nat, 226Ra and 210pb?
NRC Regulatory Guide 4.14 Section 5 LLD values (in soil):
U-nat 2.0E7 µCilg 226Ra 2 0E7 µCi/g 210pb 2 0E7 µCi/g
Yes Z No 0 NIA 0
Comments:
15. Were lower limits of detection (LLD) for analysis of site boundary vegetation samples within the
limits listed in NRC Regulatory Guide 4.14 Section 5 for 226Ra and 210pb?
NRC Regulatory Guide 4.14 Section 5 LLD values (in vegetation):
U-nat 2.0E7 µCi/kg 226Ra 5 0E8 µCi/kg 210pb 1 0E6 µCi/kg
Yes Z No Z
Comments:
Page 7 of 8
(Date)
(Date)
16. Were lower limits of detection (LLD) for analysis of radon samples within the limits listed in NRC
Regulatory Guide 4.14 Section 5 for 222Rn?
NRC Regulatory Guide 4.14 Section 5 LLD values for radon: 222Rn -10 2 OE 1.1.Ci/m1 (0.2pCi/L)
Yes El No 111
Comments:
White Mesa Environmental Protection Manual Section 1.4, STACK EMMISIONS MONITORING
PROCEDURES, sub-section 1.0, INTRODUCTION, states, "These sampling methods are also
consistent with guidance contained in the U.S. Nuclear Regulatory Commission's Regulatory Guide
4.14, "Radiological Effluent and Environmental Monitoring at Uranium Mills."
17. Were the yellowcake dryer and packaging stacks sampled in accordance with Regulatory Guide 4.14
Section 2.1.1?
Quarterly samples at North Yellowcake Dryer and Yellowcake Baghouse for:
U-nat
Semi-annual samples at North Yellowcake Dryer and Yellowcake Baghouse for: 230Th
226Ra
210ph
Yes El Nofl
Comments:
Stack sampling occurred during the first and third quarters only. The mill did not process ore during the
2' and 4 quarters of 2015.
Russ Topham Prepared By:
(Print Name)
Reviewed By:
(Print Name) (Signature)
Phil Goble
Page 8 of 8
Year Endin 31-Dec-18
PARTICULATE, RADON AND GAMMA SCREENING
Quarter Ending Analysis of Annual Dose Constituent Location 31-Mar-18 30-Jun-18 30-Sep-18 31-Dec-18 Annual ECL Below ECL? mrem/yr
Ra
dio
a
c
tiv
e
Pa
r
tic
u
la
te
s
UNAT
0.1Ci/mL)
BHV-1 1.9E-16 8.0E-16 4.0E-16 1.5E-15 7.2E-16 9.00E-14 Yes 0.40
0 15 BHV-2 6.7E-17 3.8E-16 1.0E-16 5,0E-16 2,6E-16 9.00E-14 Yes BHV-4 6.8E-16 1.5E-15 2.2E-15 3.4E-15 1.9E-15 9.00E-14 Yes 1.08 BHV-5 7.1E-16 2.6E-15 2.2E-15 6.0E-15 2,9E-15 9.00E-14 Yes 1.60
2.11 BHV-6 1.2E-15 3.0E-15 3.1E-15 7.9E-15 3.8E-15 9.00E-14 Yes
BHV-7 4.1E-16 1.6E-15 1.0E-15 1.9E-15 1,2E-15 9.00E-14 Yes 0.68 BHV-8 2.3E-16 9.4E-16 6.0E-16 1,5E-15 8.2E-16 9.00E-14 Yes 0.45
230Th
(pCi/mL)
BHV-1 5.3E-17 1.2E-16 9.0E-17 5.0E-17 7.8E-17 2.00E-14 Yes 0.20
BHV-2 1,4E-17 4,6E-17 2.0E-17 2.0E-17 2.5E-17 2.00E-14 Yes 0.06 BHV-4 1.2E-16 8.2E-17 2.0E-16 2.0E-16 1.5E-16 2.00E-14 Yes 0.38 BHV-5 1.7E-16 2.4E-16 3.0E-16 3.0E-16 2.5E-16 2.00E-14 Yes 0.63
BHV-6 1.1E-16 9,7E-17 2.0E-16 2.0E-16 1.5E-16 2.00E-14 Yes 0.38
BHV-7 1.2E-16 2.2E-16 2.0E-16 1.0E-16 1.6E-16 2.00E-14 Yes 0.40
BHV-8 5.8E-17 1.2E-16 9.0E-17 7.0E-17 8.5E-17 2.00E-14 Yes 0.21
2"Ra
(pCi/mL)
BHV-1 . - 2.5E-16 7.0E-17 2.0E-17 1.1E-16 9.00E-13 Yes 0.01
BHV-2 4.0E-17 1.2E-16 3.0E-17 1.0E-17 5.0E-17 9.00E-13 Yes 0.00
0 00 BHV-4 5.7E-17 3.7E-17 1.0E-16 4.0E-17 5.9E-17 9.00E-13 Yes BHV-5 1.5E-16 5.9E-16 1.0E-16 1.0E-16 2.4E-16 9.00E-13 Yes 0.01
BHV-6 1.1E-16 1.0E-16 5.0E-17 3.0E-17 7.3E-17 9,00E-13 Yes 0.00
BHV-7 2.6E-16 1.3E-16 1.0E-16 2.0E-17 1.3E-16 9.00E-13 Yes 0.01
BHV-8 8.3E-17 3.0E-16 6.0E-17 3.0E-17 1.2E-16 9.00E-13 Yes 0.01
210pb
(pCi/mL)
BHV-1 1.5E-14 1.2E-14 1.0E-14 2,0E-14 1.4E-14 6.00E-131
6.00E-13
Yes
Yes
1.19
1.15 BHV-2 1.2E-14 1.3E-14 1.0E-14, 2.0E-14 1.4E-14
BHV-4 1.4E-14 1.1E-14 1.0E-14 2.0E-14 1.4E-14 6.00E-13 Yes 1.15
BHV-5 1.4E-14 1,2E-14 1.0E-14 2.0E-14 1.4E-14 6.00E-13 Yes 1.17
1.40 BHV-6 1.5E-14 1.2E-14 _ 2.0E-14 2.0E-14 .7E-14 6.00E-13 Yes BHV-7 1.8E-14 1.2E-14 2.0E-14 1.0E-14 1,5E-14 6.00E-13 Yes 1.25
BHV-8 1.3E-14 8.8E-15 1.0E-14 1.0E-14 1.0E-14 6.00E-13 Yes 0.87
232Th
mL) (pCi/
BHV-1 5.3E-18 9.3E-18 1.0E-17 3,0E-18 6.9E-18 4.00E-15
Yes
Yes 0.09
0 10 BHV-2 5.3E-18 1.5E-17 7.0E-18 4.0E-18 7.8E-18 4.00E-15 BHV-4 4.0E-18 1.2E-17 1.0E-17 6.0E-18 8.0E-18 4.00E-15 Yes 0.10
BHV-5 2.0E-17 9.4E-18 8.0E-18 9.0E-18 1.2E-17 4.00E-15 Yes 0.15
BHV-6 9.0E-18 1.4E-17 1.0E-17 3.0E-18 9.0E-18 4.00E-15 Yes 0 11
BHV-7 8.7E-18 1.7E-17 1.0E-17 5.0E-18 1.0E-17 4.00E-15 Yes 0.13
BHV-8 5.1E-18 8.5E-18 6.0E-18 3.0E-18 5.7E-18 4.00E-15 Yes 0.07
I
Di
r
e
c
t R
a
dia
tio
n
v (mrem)
BHV-1 1 0E+00 0.0E+00 3.6E+00 2.6E+00 7.2E+00 1.00E+02 Yes 7.20 BHV-2 1.0E-01 2.2E+00 0.0E+00 1.2E+00 3.5E+00 1 00E+02 Yes 3.50
BHV-4 0.0E+00 7.0E-01 5.4E+00 9.0E-01 7.0E+00 1.00E+02 Yes 7.00
BHV-5 2.0E+00 1.2E+00
0.0E+00
5.3E+00 0.0E+00 8.5E+00 1.00E+02 Yes
Yes
8.50
1.20 BHV-6 0.0E+00 1.2E+00 0.0E+00 1.2E+00 1.00E+02
BHV-7 0.0E+00 0.0E+00 0.0E+00 1.5E+00 1.5E+00 1 00E+02 Yes 1.50 BHV-8 0.0E+00 0.0E+00 0.0E+00 0.0E+00 0 0E+00 1 00E+02 Yes 0.00
Ra
do
n
-
22
2
222Rn
(pCi/L)
BHV-1 3.5E+01 3.9E+01 3.8E+01 4.0E+01 3 8E+01 7.10E-02 Yes 0.05 BHV-2 3.4E+01 3.9E+01 3.4E+01 3.7E+01 3.6E+01
3.4E+01
3.40E-01
5.00E-01
Yes 0 05
BHV-4 3.1E+01 3 7E+01 3.5E+01 3.3E+01 Yes 0 07
BHV-5 3.0E+01 3.8E+01 3.3E+01 3.6E+01 3 4E+01 1.43E+00 Yes 0.06
BHV-6 1.0E-01 2.2E+00 0.0E+00 1.2E+00 8.8E-01 8.30E-01 Yes 0.06 BHV-7 2.0E+00 1.2E+00 5.3E+00 0.0E+00 2.1E+00 1.12E+00 Yes 0.04 BHV-8 0.0E+00 0.0E+00 0.0E+00 1 5E+00 3.8E-0 7.10E-01 Yes 13.20
Su
mm
a
ry
Estimated
Dose
and Comparison
to
Screening
Values
( mrem/yr)
Location Dose
ALARA
Goal
ALARA
Goal Met?
Exposure
Limit Compliant?
BHV-1 9.13 25 Yes 100 Yes BHV-2 5.00 25 Yes 100 Yes BHV-4 9.78 25 Yes 100 Yes
BHV-5
BHV-6
12 11 25 Yes 100 Yes
Yes 5.27 25 Yes 100
BHV-7 4.00 25 Yes 100 Yes BHV-8 14.82 25 Yes 100 Yes
Notes: Regulatory limit is 100 mrem/yr.
Energy Fuels' ALARA goal is not to maintain exposures below 25 mrem/yr
ECLs are based on 50 mrem/yr except radon which uses 25 mrem/yr. ECLs for radon were calculated using distance and wind speed from assumed stack source to BHV stations.
Calculated ECLs provide inclusion of ingrowth of daughters.
Annual values reflect averaging dose rates for the four quarters, except for gamma, which is the sum of four quarterly values.