Loading...
HomeMy WebLinkAboutDRC-2021-017941 - 0901a06880f940022.02.1 - DO% -1 RMINSPECTION REPORT Inspection Module: RADMOD-PEM: Surveys/Posting/Exit Monitoring Inspection Location:. Energy Fuels - White Mesa Uranium Mill, Blanding Utah. Inspection Items: Radiological Postings, Routine Surveys and Employee Exit Monitoring Inspection Date: September 7 & 8, 2021 Inspectors: Ryan Johnson, Utah Division of Waste Management and Radiation Control (DWMRC) Personnel Contacted: Garrin Palmer, Radiation Safety Officer (RSO) Justin Perkins, RST Governing Documents: • UAC R313-15 • Radioactive Materials License (RML) UT1900479 • Applicable Mill procedures and manuals Opening Meeting Energy Fuels Resources: Garrin Palmer (RST) Utah DWMRC: Ryan Johnson (Health Physics Inspector) During the opening meeting, the inspectors discussed the inspection items for the inspection. The Mill staff reminded the inspector of the safety requirements for the Mill. DWMRC Meters Used Model Serial Number Calibration Due Date Dose Rate Ludlum 19 101673 5/11/2022 Contamination Ludlum 3002 25017719 9/17/2021 Inspection Summary The inspection consisted of: • Observing radiological postings around the Mill; • Observing Mill personnel perform exit surveys: • Reviewing documentation of: o Weekly Alpha surveys; o Monthly Gamma surveys; and • Taking dose rate and contamination measurements around the Mill. The following discussion provides more detail of each inspection items. Item 1. Radiological Postings: Observations: During the Mill Tour the inspector observed the following posted areas: 1 of Page 4 \\Cbwfp2\shw\Shared\RAD\COMMON\Uranium mills\UT1900479 EnergyFuets Res - White Mesa UMill \HP Inspection modules\2021\2021 Inspection Reports \Inspection Report RADMOD-PEM 9-8-202 I.docx Posting Locations Observed Postings Observed Dose Rates Yellowcake Storage Area , Caution Radiation Area 4,000 µR/hr (Inside area) Laboratory Caution Radioactive Materials 60 pR/hr Laboratory Sample Storage (aka Balance) Room Caution Radiation Area 80 µR/hr Doors leading to the restricted area from the Administration building Any Area within this Mill May Contain Radioactive Material Not Measured Sample Preparation Room Caution Airborne Area 60 µR/hr Perimeter fence Caution Radiation Area Not Measured Perimeter gates Any Area within this Mill May Contain Radioactive Material Not Measured Ore Pad No Posting 100-300 µR/hr Mill No Posting 50-150 µR/hr Solvent Extraction Building No Posting 60 µR/hr Scale house No Posting 125 µR/hr Lunchroom No Posting 35 pR/hr Lunchroom #2 No Posting 25 µR/hr Note: Due to no uranium production at the time of the inspection there are fewer posted areas in the Mill. The Inspector also collected large area swipe samples in six areas within the restricted area. Location Alpha (dpm/100cm) Beta (dpm/100cm2) Scale House Below Background Below Background Lunch Room 1 Below Background Lunch Room #2 1 Below Background Locker Room Below Background Below Background Sample Prep Room 11 6 Control Room 1 3 Deficiencies: None Item 2. Exit Surveys: The Inspector observed employees survey themselves out of the restricted area and checked the alpha metersused. Observations: The Mill uses Alpha scintillators for exit surveys. The Inspector checked the settings of the survey instruments and found that they were set properly. Meters are calibrated annually. The Mill personnel that were observed performing exit surveys, did the surveys appropriately. The Mill's RSTs also perform random checks on exit surveys. Meter Location Model Meter Serial # Probe Serial # Cal. Due Alarm Setting West Admin Door Ludlum 177 322833 PR342603 3/4/2022 80 East Admin. Door Ludlum 177 322900 PR359856 3/2/2022 80 Lab Admin Door Ludlum 177 185038 RN17632 11/12/2021 80 Lunch Room Ludlum 177 265743 RN16489 9/23/2021 80 Lunch Room #2 Ludlum 177 159170 PR192467 3/4/2022 80 2 of Page 4 \\Cbwfp2 \shw\ Shared\RAD\ COMMON \Uranium mills\UT1900479 EnergyFuels Res - White Mesa UMill \HP Inspection modules\2021\2021 Inspection Reports \Inspection Report RADMOD-PEM 9-8-2021.docx (Date) Recommendation for Next Inspection None Prepared By: Reviewed By: 9/10/2021 East Decon Gate Ludlum 177 159117 PR16489-1A 3/3/2022 80 Deficiencies: None Item 3. Radiological Surveys and Monitoring: The Inspector reviewed the weekly surveys done around the Mill. Observations: The Inspector reviewed the radiological monitoring documentation performed at the Mill site. The documentation indicated that: • All areas of the Mill are being survey for radiological conditions; • Surveys indicate that the Mill is being maintained within regulatory radiological parameters • Documentation is legible, complete and using appropriate units; and • "Clean" areas are being maintained. The Inspector also looked at dosimeter usage. The inspector observed: • Mill personnel were properly wearing their dosimeters on the torso of the their bodies; • Dosimetery was being properly stored in the locker room and administration building; and • Each employee is assigned a dosimeter. Meter Type Model Meter Serial # Probe Serial # Cal. Due Meter Condition Alpha Scintillator Ludlum 3 235288 PR281511 8/25/2022 Good Side Window G/M Ludlum 3 337582 RN24946 6/8/2022 Good Alpha Scintillator Ludlum 2200 17534 43-10 8/24/2022 Good Closeout Meeting Energy Fuels: Garrin Palmer (RST) Utah DWMRC: Ryan Johnson (Health Physics Inspector) Recommendations None 3 of Page 4 \\Cbwfp2\shw\Shared\RAD\COMMON\Uranium mills\UT1900479 EnergyFuels Res - White Mesa UM111\HP Inspection modules\2021. \202I Inspection Reports \Inspection Report RADMOD-PEM 9-8-2021.docx