HomeMy WebLinkAboutDERR-2024-006415Underwood Environmental Consulting, Inc. 9475 N. Silver Creek Road  Park City, Utah 84098  Phone 801-831-6966  Fax 888-472-0977 March 22, 2024 Mr. Hong-Lei Tao Department of Environmental Quality Division of Environmental Response and Remediation P.O. Box 144840 Salt Lake City, Utah 84114-4840 Re: Corrective Action Plan Summary Letter Western Petroleum Inc. / Naples Bulk Plant 1521 South 1500 East, Naples, Utah Facility ID# 9000171, Release Site KMX Introduction This outline presents the Corrective Action Plan (CAP) for Release Site KMX at Western Petroleum, Inc. in Naples, Utah (project site) (Figure 1). Release site KMX consisted of two underground storage tanks (USTs) (500-gallon unleaded gasoline and diesel day tanks) located within the containment area of a former bulk plant housing several above ground storage tanks (ASTs) and two loading racks. The USTs were removed in 1998 while the ASTs were removed in 2007. The CAP summary Letter has been prepared on behalf of 1521 South 1500, LLC by Underwood Environmental Consulting, Inc. (UEC). The general scope for the CAP is to perform limited over-excavation of petroleum hydrocarbon- impacted soil and transporting that soil to either the Uintah County landfill or the East Carbon Development Company (ECDC) landfill. The handling of contaminated groundwater pumped from the excavation, if any, is uncertain at this time, although re-injection back to an open excavation under permit-by-rule is preferable. Background The project site is located in Uintah County, Utah southeast of the intersection of 1500 East and U.S. highway 40 in Naples, Utah (Figure 1). Adjacent properties include Pilot Thomas Logistics, LLC (Pilot) to the west and south, a petroleum products storage and wholesale business. Fuel dispensers and product lines at the Pilot property are located upgradient of the project site and have had documented petroleum releases to the environment. Based on the timing of tank removals at the project site and discovery of petroleum release(s) upgradient (2013), it is reasonable to conclude that contamination from upgradient source(s) has overprinted subsurface contamination from release site KMX. The existing Western Petroleum warehouse was constructed following excavation of hydrocarbon impacted soil from the area of the building footprint (2007). CAP Summary Letter Western Petroleum Inc. / Naples Bulk Plant, Naples, UT Facility ID# 9000171, Release Site KMX Underwood Environmental Consulting, Inc. 2 Environmental sample results and UEC observations during monitoring well installation identified hydrocarbon impacts to native soil to 12 feet below grade in some locations. The water table is approximately 9 feet below grade. Free product was observed in monitoring wells during the last groundwater monitoring event (2018). Hydrocarbon impacts to vadose zone soils are likely at the former location of the UST-AST containment area. Following approval of the CAP and completion of the public notification process, a work plan and bids for the excavation work and site restoration would be procured. Release site KMX was determined previously to be 100% eligible for cost reimbursement from the Utah Petroleum Storage Tank Fund (PST Fund). Corrective Action Alternatives The following corrective action alternatives were considered (Figure 2): 1) Option 1 – Over-excavation of overburden and hydrocarbon-impacted soil from estimated release KMX footprint (~9,500 CY), including de-watering, if necessary. Disposal of ~3,000 CY soil at Uintah County Class I landfill or ECDC landfill, with reuse of ~6,000 CY of material for backfilling. Disposition of groundwater unknown. 2) Option 2 – Limited over-excavation of hydrocarbon-impacted soil from vadose zone at former UST-AST containment area (~1,200 CY). No groundwater pumping or handling. Long-term natural attenuation. 3) Option 3 – Permeable bio-wall, or “funnel and gate”, either upgradient of former UST-AST containment area or downgradient along eastern property line. 4) Option 4 – High vacuum extraction with emphasis on free product recovery. Selected Corrective Action Rationale The general consensus for corrective action at the project site favors Option 2 (limited over-excavation of hydrocarbon impacted soil from vadose zone at the former UST-AST containment area) (Figure 2). The corrective action selection was based on the following considerations: 1) Upgradient source(s): Hydrocarbon impacts from release KMX in the subsurface are likely overprinted by hydrocarbon contamination from upgradient source(s). 2) Contaminants of concern: Total petroleum hydrocarbons (TPH) as gasoline and diesel, benzene, toluene, ethylbenzene, xylenes. 3) Depth to groundwater: Approximately 9 feet below grade (2018). 4) Depth of hydrocarbon impacts: Approximately 4-12 feet below grade at former UST-AST containment area. Approximately 7-10 feet below grade upgradient and approximately 9-12 feet below grade downgradient. 5) Site lithology: Native soil includes clay, silt, sand, gravel, and cobbles. Cobbles are most prevalent at approximately 9 feet below grade. Site conditions are generally not favorable for remedial methodologies, such as SVE, air sparging, dual-phase high vacuum extraction (option 4), or other. 6) Per Tri-County Health Dept., the Uintah County landfill facility requires soil be “dry” for acceptance at the facility. Implies no direct load and haul. CAP Summary Letter Western Petroleum Inc. / Naples Bulk Plant, Naples, UT Facility ID# 9000171, Release Site KMX Underwood Environmental Consulting, Inc. 3 7) Disposition of groundwater pumped from excavation or wells: Considerable uncertainty, although re-injection of treated groundwater to open excavation preferable. The following permits and approvals are anticipated to be obtained for this work: 1) DERR work plan approval(s), 2) Tri-County Health Dept. (soil disposal at Uintah Co. landfill), or ECDC waste profile. 3) DWQ permit-by-rule for treated groundwater discharge back to excavation, if necessary. 4) DAQ? Landfarming to dry out soil prior to disposal at Uintah co. landfill. Upon approval of this CAP Summary Letter, a Public Notice would be prepared for approval and distribution. A bid document for the remedial work would also be prepared and bids solicited. Respectfully, James A. McReel, P.G. Certified UST Consultant #CC-0044 Attachments: Figure 1 Site Map cc: Mr. Mark Caldwell, 1521 South 1500 East, LLC CAP Options FIGURE 2 Funnel & Gate - Option 3 Proposed Excavation - Option 1 Proposed Excavation - Option 2 Groundwater Flow Direction (April 28, 2015) Proposed Excavation Area Option 1 Funnel & Gate Option 3 Hi-Vac Extraction Option 4 Proposed Excavation Area Option 2 Sanitary Sewer Telephone Lines Natural Gas Water Line Property Line Buried Power Line Buried Propane Line MW-5 SB-21 MW-9 Destroyed Monitoring Well (10/7/00) Release NCE Soil Boring (January 2014) UST Closure Samples (June 1998) Irrigation Monitoring Well (6/11/14) Monitoring Well (8/18/11) MW-2 SS4 WS4 MW-17 Monitoring Well (4/6-7/15) Monitoring Well (Pangean Installed 2014) GW-1 DP-1 Soil Boring (4/7/15) Soil Boring (Pangean 7/15/14) SB-1 3/19/2024 ? Sewer Manhole Sewer Manhole Western Petroleum Building/ Warehouse Former Naples Truck Stop Canopy AST’s and Containment AST’s and Containment AST’s and Containment 1500 South 16 2 5 E a s t Former Warehouse Quonset Hut Former Shop Former StorageFormer Storage Fo r m e r O f fi c e Former USTs (see inset map) Pond Fo r m e r AS T s a n d C o n t a i n m e n t Propane Tank Former 4,000 Gallon Used Oil UST Pilot Logistics Fueling Area Pilot Logistics Fueling Area Truck Loading Rack Approximate Locations of 2007 Pacific West Excavations SB-20 SB-21 SB-22 SB-23 SB-31 SB-24 SB-17 SB-16 SB-15 SB-14 SB-18 SB-25 SB-26 SB-27 MW-12 MW-10 MW-7 MW-9 MW-13 MW-14 MW-15 MW-6 MW-3 MW-2 MW-1 MW-5 MW-11 MW-8 MW-4 MW-16 MW-18 MW-19 MW-20 MW-17 MW-21 DP-1 DP-2 GW-1 GW-2 GW-3 GW-4 GW-5 GW-7 GW-6 GW-8 GW-9 GW-10 SB-1 SS3 WS3 SS4 WS4Product Line Trenches (to former ASTs) Communication Line Trench (to former card reader) February 2013 - Discovery of Gasoline Product Line Failure/Release Naples Bulk Plant 1521 S. 1500 E. Naples, UT 84078 Facility ID# 9000171 Release Code: KMX NORTH approx. scale in feet 00 35 70 140105 LEGEND Original Drawing 11” X 17”, Adjust Scale Accordingly