HomeMy WebLinkAboutDDW-2025-010646Sanitary Survey - Deficiency Report
PWS Number:UTAH13032 Deficiency Points:25 Survey Date:10/14/2025
Survey Name:BRYCE-ZION CAMPGROUND Surveyor:Tom McOmie
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | HOPS SPRING
66B. Spring box lid is gasketed
Rule: R309-515-7(7)(d), R309-545-14 (2)Access openings shall comply with R309-545 and be provided with a cover furnished
with a gasket between the lid and frame. This significant deficiency must be corrected
within 120 days of notification or have a corrective action plan approved by DDW.
Notes:Gasket needs to be replaced.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS10 SPRING BOX LID LACKS A GASKET