Loading...
HomeMy WebLinkAboutDDW-2025-010646Sanitary Survey - Deficiency Report PWS Number:UTAH13032 Deficiency Points:25 Survey Date:10/14/2025 Survey Name:BRYCE-ZION CAMPGROUND Surveyor:Tom McOmie Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS001 | HOPS SPRING 66B. Spring box lid is gasketed Rule: R309-515-7(7)(d), R309-545-14 (2)Access openings shall comply with R309-545 and be provided with a cover furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Gasket needs to be replaced. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS10 SPRING BOX LID LACKS A GASKET