Loading...
HomeMy WebLinkAboutDDW-2025-010364Sanitary Survey - Deficiency Report PWS Number:UTAH27118 Deficiency Points:130 Survey Date:10/15/2025 Survey Name:KINGS ROW ESTATES Surveyor:Tom McOmie Sanitary Survey Category: SM SDWIS Severity Code: Significant Deficiency Management and Operations | DS001 | UTAH27118 DISTRIBUTION SYSTEM 23. There are no undocumented drinking water facilities (i.e. tanks, pump stations, treatment facilities, etc.) or recent modifications that have not gone through or in process of DDW review [LIST UNDOCUMENTED FACILITIES OR DESCRIBE MODIFICATIONS, IF APPLICABLE] [undocumented sources are covered in a different question] Rule: R309-100-5(2), R309-500-6, R309-500-9, R309-500-9(2) and (3) Rule requires complete plans & specification for all public drinking water projects to be approved in writing by the Director. Any facility found that has not started DDW review shall be considered unapproved. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:DDW hasn't received the paperwork yet approving Washington City as a consecutive connection. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: G001 UNAPPROVED FACILITY IN SERVICE Sanitary Survey Category: MR SDWIS Severity Code: Recommendation Management and Operations | DS001 | UTAH27118 DISTRIBUTION SYSTEM 35. For a community water system or a non-transient non-community water system, did you make your initial service line inventory available to the public? (if a transient system, enter NA) Rule: 40 CFR 141.84 (a)(8)The rule requires that the service line materials inventory be publicly accessible. (a)(8)(ii) The rule requires that water systems serving greater than 50,000 persons make the publicly accessible inventory available online. (a)(9) The rule requires that when a water system has no lead, galvanized requiring replacement, or lead status unknown service lines (regardless of ownership) in its inventory, it may comply with the requirements using a written statement, in lieu of the inventory, declaring that the distribution system has no lead service lines or galvanized requiring replacement service lines. The statement must include a general description of all applicable sources used to make this determination. Notes:New system Deficiency Points: 0 Days until points become effective on IPS: 0 SDWIS Deficiency Description: R006 FAILURE TO MAKE THE LEAD SERVICE LINE INVENTORY PUBLICLY ACCESSIBLE Sanitary Survey Category: SM SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH27118 DISTRIBUTION SYSTEM 36. Legally adopted authority statement Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program that includes a legally adopted and functional local authority to enforce the program (i.e., ordinance, bylaw, or policy). Notes:I WILL BE WORKING WITH JIM TO HELP HIM TRY AND GET INTO COMPLIANCE WITH THE CCC PROGRAM. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M003 CCC-LACKS LOCAL AUTHORITY Sanitary Survey Category: SM SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH27118 DISTRIBUTION SYSTEM 38. Documentation of personnel trained to manage the program (ALL COMUNITY WATER SYSTEMS REQUIRE A DDW CERTIFIED CCC PROGRAM ADMINISTRATOR. ALL OTHER WATER SYSTEMS REQUIRE AT A MINIMUM BACKFLOW 101 OR EQUIVALENT/ GREATER CCC TRAINING) Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program that includes an operator with adequate training in the area of cross connection control or backflow prevention. Notes:I WILL BE WORKING WITH JIM TO HELP HIM TRY AND GET INTO COMPLIANCE WITH THE CCC PROGRAM. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M005 CCC-LACKS OPERATOR TRAINING Sanitary Survey Category: OC SDWIS Severity Code: Significant Deficiency Cross Connection and Operator Certification | DS001 | UTAH27118 DISTRIBUTION SYSTEM 41. Operator meets required level of certification for water system. ( IF NO CERTIFIED OPERATOR IS REQUIRED MARK COMPLIANT ) Rule: R309-105-11, R309-300-5(3)Rule requires every community and NTNC water system and public water systems that utilize treatment/filtration to have at least one operator certified at the classified grade of the water system. Certification must be appropriate for the type of system operated (treatment and/or distribution). This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:I WILL BE WORKING WITH JIM TO HELP HIM TRY AND GET INTO COMPLIANCE WITH THE CCC PROGRAM. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: C001 SYSTEM DIRECT RESPONSIBLE CHARGE OPERATORS NOT CERTIFIED AT THE REQUIRED LEVEL Sanitary Survey Category: OC SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH27118 DISTRIBUTION SYSTEM 42. Certified operator is within 1 hour travel time of water system. ( IF NO CERTIFIED OPERATOR IS REQUIRED MARK COMPLIANT ) Rule: R309-300-5(14)Rule requires the operator to be within 1 hour travel time, under normal work and home conditions, of each drinking water system for which he is considered in direct responsible charge. Notes:I WILL BE WORKING WITH JIM TO HELP HIM TRY AND GET INTO COMPLIANCE WITH THE CCC PROGRAM. Deficiency Points: 0 Days until points become effective on IPS: 0 SDWIS Deficiency Description: C002 OPERATOR NOT AVAILABLE WITHIN 1 HOUR TRAVEL TIME