HomeMy WebLinkAboutDDW-2025-010243
Mailing Address: P.O. Box 144830 • Salt Lake City, UT 84114-Telephone (801) 536-4200 • Fax (801-536-4211 • T.D.D. (801) 536-
www.deq.utah.gov Printed on 100% recycled paper
State of Utah
Governor DEIDRE HENDERSON Lieutenant Governor
Department of Environmental Quality
Tim Davis Executive Director
DIVISION OF DRINKING WATER Nathan Lunstad, Ph.D., P.E. Director
October 22, 2025 CERTIFIED MAIL
Lisa Chauvin Dammeron Valley Water Works LLC 1 Dammeron Vly East Dammeron Valley, UT 84783
Subject: NOTICE OF VIOLATION – Failure to Fix Significant Deficiency Treatment Technique Violation, Water System #UTAH27030 Lisa Chauvin:
Our records indicate that your system is in violation of the State of Utah Public Drinking Water Rules as follows: On May 8, 2025, Dammeron Valley Water Works LLC received three significant deficiencies. The system was notified of these deficiencies on May 10, 2025. Two of these deficiencies remain
uncorrected:
• V011 End of storage tank overflow lacks a clearance of between 12 and 24 inches from ground surface ST002
• V011 End of storage tank overflow lacks a clearance of between 12 and 24 inches from ground surface ST003
Utah Public Drinking Water Rules require all significant deficiencies to be corrected within 120 days of the date of notification or the system must enter a corrective action plan (CAP) with the
Division to address the significant deficiencies as specified in R309-215-16(3)(a)(v). The system chose not to request a corrective action plan or submit a correction for this deficiency within the given timeframe. This results in the system being assessed a treatment technique violation in accordance with R309-215-16(4)(a) and the assessment of 50 Improvement Priority System (IPS) points to the system’s IPS Report. Be advised this could adversely affect
your water system’s rating (R309-400).
As a result of this Tier 2 violation, the system must provide public notice as soon as practical, but no later than 30 days after the system learns of the violation. If the public notice is posted, the notice must remain in place for as long as the violation or situation persists, but in no case for less than seven days, even if the violation or situation is resolved (see R309-220-6(1)(a) and R309-
220-6(1)(b)). This public notice requirement cannot be waived once a violation occurs. Proof of
Lisa Chauvin Page 2 of 2
public notification must be provided to the Division at (ddwreports@utah.gov) within 30 days of notifying the water system customers and resubmitted each quarter the deficiencies remain unresolved. Failure to submit quarterly public notification may result in a public notice violation and an additional 50 points on the IPS report.
If any of the above deficiencies have been corrected, please complete the enclosed IPS Deficiency
Correction Notice and submit the information to the Division at ddwips@utah.gov immediately. We ask that you respond to this letter as soon as possible. Please contact Jennifer Yee at (385) 515-1501 or ddwips@utah.gov if you have questions or need assistance. Sincerely,
Helen Lau
Compliance Section Manager Enclosures: IPS Report Deficiency Correction Form Tier 2 Public Notice Template
cc: Jeremy Roberts, Southwest Utah Public Health Departmentjroberts@swuhealth.gov Paul Wright, P.E., District Engineer,pwright@utah.gov
Helen Lau (Oct 22, 2025 16:15:06 MDT)
Utah Department Of Environmental Quality
Division Of Drinking Water
Admin Contacts
IPS 2020 Report
IPS Report
DAMMERON VALLEY
WATER WORKS LLC
PWS ID: UTAH27030 Rating: Approved 05/23/1989 Active
Legal Contact
DAMMERON VALLEY WTR WORKS
LISA CHAUVIN
1 DAMMERON VLY EAST
DAMERON VALLEY, UT 84783
Phone: 435-574-2295
County: WASHINGTON COUNTY
System Type: Community
Population: 885
Site Updates
Last Inventory Update: 09/03/2025
Last Surveyor Update: 05/08/2025
Surveyor: CHRIS BOWLES
Operating Period: 1/1 - 12/31
Last IPS Update: 10/22/2025 14:22:26
Consumptive Use Zone
Irrigation Zone: null
Date:
Name Title Office Emergency Email
CHAUVIN, LISA 435-574-2295 water@dammeronvalley.com
IPS Summary Total IPS Pts: 190
Admin & Physical Facilities Quality & Monitoring Significant Deficiency
90 0 100.0
DEQ | Drinking Water
Run Date: 10/22/2025 16:07:57 | Rating: Approved UTAH27030 DAMMERON VALLEY WATER WORKS LLC page 1 of 3
Physical Facility Points 2020 Total Pts: 90
Facility Facility Name Status Points Effective
DS001 UTAH27030 DISTRIBUTION SYSTEM A 30.0
Code Description Severity Comments Determined Date Not
Assessed Assessed
M019 FAILURE TO SUBMIT
REQUIRED WATER
USE DATA ANNUALLY
OR VERIFY DATA
ACCURACY
MIN DUE DATE NOVEMBER 30,
2023
10/01/2022 15
M007 CCC-LACKS ON-
GOING
ENFORCEMENT
IMPLEMENTATION
MIN Needs to create a bigger
inventory of connections and
create a Letter to mail to
customers to start and
continue enforcement.
05/08/2025 15
ST002 NORTH RIDGE TANK A 25.0
Code Description Severity Comments Determined Date Not
Assessed Assessed
V011 END OF STORAGE
TANK OVERFLOW
LACKS A CLEARANCE
OF BETWEEN 12 AND
24 INCHES FROM
GROUND SURFACE
SIG Flows to dry creek next to
road no Air Gap
05/08/2025 25
ST003 NORTH RIDGE TANK #2 A 25.0
Code Description Severity Comments Determined Date Not
Assessed Assessed
V011 END OF STORAGE
TANK OVERFLOW
LACKS A CLEARANCE
OF BETWEEN 12 AND
24 INCHES FROM
GROUND SURFACE
SIG No Air Gap where it
discharges to Dry creek bed,
evidence of wash and silt
from storm run off water in
dry creek bed. Photo's will be
attached on follow up email
05/08/2025 25
WS004 NORTH RIDGE 3A A 5.0
Code Description Severity Comments Determined Date Not
Assessed Assessed
S024 NO CHECK VALVE ON
WELL DISCHARGE
PIPING
MIN Missing the check valve 10/06/2022 5
WS005 NORTH RIDGE #4 A 5.0
Code Description Severity Comments Determined Date Not
Assessed Assessed
S024 NO CHECK VALVE ON
WELL DISCHARGE
PIPING
MIN No check valve visible.05/08/2025 5
Significant Deficiency Violations Total Pts: 100
ID Violation Code Deficiency Determined Point Effective
ST002 45 FAILURE ADDRESS
DEFICIENCY (GWR)
V011 END OF STORAGE TANK
OVERFLOW LACKS A
CLEARANCE OF BETWEEN
12 AND 24 INCHES FROM
GROUND SURFACE
10/22/2025 50.0
ST003 45 FAILURE ADDRESS
DEFICIENCY (GWR)
V011 END OF STORAGE TANK
OVERFLOW LACKS A
CLEARANCE OF BETWEEN
12 AND 24 INCHES FROM
GROUND SURFACE
10/22/2025 50.0
DEQ | Drinking Water
Run Date: 10/22/2025 16:07:57 | Rating: Approved UTAH27030 DAMMERON VALLEY WATER WORKS LLC page 2 of 3
Operator Certification
Type Level Required Highest Certificate
Distribution Dist 1 Dist 4
Treatment Treat 1
Open Compliance Schedule
Type Required Activities Severity Created Due
Complete PFAS Initial Monitoring SUBMIT PFAS INITIAL MONITORING
SAMPLES
04/26/2024 04/26/2027
Physical deficiency schedule END OF STORAGE TANK OVERFLOW
LACKS A CLEARANCE OF BETWEEN 12
AND 24 INCHES FROM GROUND
SURFACE
SIG 05/10/2025 09/07/2025
Physical deficiency schedule END OF STORAGE TANK OVERFLOW
LACKS A CLEARANCE OF BETWEEN 12
AND 24 INCHES FROM GROUND
SURFACE
SIG 05/10/2025 09/07/2025
Corrective Action Agreement CAA INSTALL EQUIPMENT 11/30/2023
Corrective Action Agreement CAA SUBMIT PLANS 11/30/2022
Corrective Action Agreement CAA COLLECT AND RECORD WATER
USE DATA
MIN 11/30/2023
DEQ | Drinking Water
Run Date: 10/22/2025 16:07:57 | Rating: Approved UTAH27030 DAMMERON VALLEY WATER WORKS LLC page 3 of 3