HomeMy WebLinkAboutDDW-2025-010223Sanitary Survey - Deficiency Report
PWS Number:UTAH26059 Deficiency Points:300 Survey Date:10/20/2025
Survey Name:WASATCH MOBILE HOME
PARK
Surveyor:Colt Smith
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Management and Operations | DS001 | UTAH26059 DISTRIBUTION SYSTEM
30B. System lacks more than 20% of required storage capacity (fire demand not included)
Rule: R309-510-8(1)(a)Rule requires a public water system to provide equalization storage volume (to meet
average day demands for indoor and irrigation water use), fire flow storage volume (if
equipped with fire hydrants for fire suppression or required by the local fire code
official), and emergency storage (if deemed appropriate by the water system or the
Director). This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:The system has an exception for this.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V034 SYSTEM LACKS MORE THAN 20% OF REQUIRED STORAGE CAPACITY (FIRE
DEMAND NOT INCLUDED)
Sanitary Survey Category: SM
SDWIS Severity Code: Recommendation
Management and Operations | DS001 | UTAH26059 DISTRIBUTION SYSTEM
31. Does your water system have an Emergency Response Plan?
Rule: R309-105-18 All suppliers are advised to develop contingency plans to cope with possible emergency
situations. In many areas of the state the possibility of earthquake damage shall be
realistically considered.
Notes:The system doesn't have an emergency response plan
Deficiency Points: 0
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M001 NO CURRENT EMERGENCY RESPONSE PROGRAM
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS001 | MHP WELL 1
57. Undocumented sources shall not be physically connected to the drinking water system. (IF SOURCE IS NOT IN SYSTEM INVENTORY
MARK "DEFICIENT")
Rule: R309-515-6(5), R309-515-7(4), R309-500-
9(2) and (3)
R309-105-6(1) requires plans and specifications for all public drinking water projects
to be approved in writing by the Director prior to the commencement of construction.
This significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:Exception still in place
Deficiency Points: 200
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S001 UNAPPROVED SOURCE IN SERVICE
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS001 | MHP WELL 1
59. Wellhead is sealed to prevent contamination.
Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and
maintained at the wellhead and discharge piping. This significant deficiency should be
corrected within 120 days of notification or have a corrective action plan approved by
Notes:Exception still in place
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL