HomeMy WebLinkAboutDDW-2025-010025Sanitary Survey - Deficiency Report
PWS Number:UTAH20039 Deficiency Points:25 Survey Date:10/15/2025
Survey Name:MIA SHALOM RECREATION
CAMP
Surveyor:Ryan Dearing
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS005 | SPRING #5
131A. Vent is down-turned.
Rule: R309-515-7(7)(d), R309-545-15(1)All vents on junction and collection boxes shall comply with R309-545 and be
downturned a minimum of 2 inches below any opening and shielded to prevent the
entrance of contaminants. This significant deficiency must be corrected within 120 days
of notification or have a corrective action plan approved by DDW.
Notes:The elevated vent pipe was bent over from heavy snow.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS16 SPRING BOX VENT NOT DOWNTURNED