HomeMy WebLinkAboutDDW-2025-009893Sanitary Survey - Deficiency Report
PWS Number:UTAH20011 Deficiency Points:125 Survey Date:09/26/2025
Survey Name:EPHRAIM CITY Surveyor:Brian Pattee
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS008 | BIRCH SPRING
173B. Vent has #14 or finer non-corrodible mesh screen and a protective screen/covering if 6-inch diameter or greater.
Rule: R309-515-7(7)(d), R309-545-15(4) and (5)All vents on junction and collection boxes shall comply with R309-545 and be fitted
with No. 14 or finer non-corrodible mesh screen. Vents 6-inch diameter or larger shall
be fitted with additional heavy gage screen or substantial covering to protect the No. 14
mesh screen. This significant deficiency must be corrected within 120 days of
notification or have a corrective action plan approved by DDW.
Notes:Hole in screen - appears to be done with some type of tool
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS17 SPRING BOX VENT LACKS NO. 14 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS017 | NORTH WELL
320. There are no unprotected cross-connections in well discharge piping.
Rule: R309-105-12(1), R309-515-6(12)(d)(iii)Rule requires the well discharge piping to be protected against the entrance of
contamination. This significant deficiency must be corrected within 120 days of
notification or have a corrective action plan approved by DDW.
Notes:Artesion Drain Line Terminates below the flood Rim of the recieving basin/ditch , posing a
serious potential contamination source directly into your well, tide flex check valve cannot
be used as it creates to much back pressure as per DE.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S021 CROSS CONN EXISTS IN WELL HOUSE OR AT WELL HEAD
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST004 | I MILLION GALLON -3
378C. Vent covered with #14 or finer non-corrodible mesh screen.
Rule: R309-545-15(4)Rule requires a water storage tank vent to be fitted with #14 mesh or finer non-
corrodible screen and vents 6-inches or greater in diameter to be fitted with additional
heavy gauge screen or substantial covering to protect the #14 mesh screen from
vandalism or damage. This significant deficiency must be corrected within 120 days of
notification or have a compliance action plan approved by DDW.
Notes:Missing screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V007 STORAGE TANK VENT LACKS NO. 14 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST004 | I MILLION GALLON -3
385B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Missing screen - they have already fixed before survey was mailed and locked.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN