Loading...
HomeMy WebLinkAboutDDW-2025-009869Sanitary Survey - Deficiency Report PWS Number:UTAH20009 Deficiency Points:50 Survey Date:09/19/2025 Survey Name:STERLING TOWN WATER SYSTEM Surveyor:Luke Sieverts Sanitary Survey Category: DS SDWIS Severity Code: Significant Deficiency Distribution | DS001 | UTAH20009 DISTRIBUTION SYSTEM 45C. Chamber has drain to daylight, gravel-filled adsorption pit if not subject to flooding, or sump pump. Rule: R309-550-6(6)(b) and (7)(b)Rule states chambers shall be provided with a drain to daylight, if possible. Where this is not possible, underground gravel-filled absorption pits may be used if the site is not subject to flooding and conditions will assure adequate drainage. Sump pumps may also be considered if a drain to daylight or absorption pit is not feasible. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Need to vent outside of box. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: D007 AIR RELIEF VALVE OR CHAMBER SUBJECT TO FLOODING Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS001 | COVE HOLE SPRING 66B. Spring box lid is gasketed Rule: R309-515-7(7)(d), R309-545-14 (2)Access openings shall comply with R309-545 and be provided with a cover furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Needs new gasket. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS10 SPRING BOX LID LACKS A GASKET