HomeMy WebLinkAboutDDW-2025-009869Sanitary Survey - Deficiency Report
PWS Number:UTAH20009 Deficiency Points:50 Survey Date:09/19/2025
Survey Name:STERLING TOWN WATER
SYSTEM
Surveyor:Luke Sieverts
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH20009 DISTRIBUTION SYSTEM
45C. Chamber has drain to daylight, gravel-filled adsorption pit if not subject to flooding, or sump pump.
Rule: R309-550-6(6)(b) and (7)(b)Rule states chambers shall be provided with a drain to daylight, if possible. Where this
is not possible, underground gravel-filled absorption pits may be used if the site is not
subject to flooding and conditions will assure adequate drainage. Sump pumps may
also be considered if a drain to daylight or absorption pit is not feasible. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Need to vent outside of box.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D007 AIR RELIEF VALVE OR CHAMBER SUBJECT TO FLOODING
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | COVE HOLE SPRING
66B. Spring box lid is gasketed
Rule: R309-515-7(7)(d), R309-545-14 (2)Access openings shall comply with R309-545 and be provided with a cover furnished
with a gasket between the lid and frame. This significant deficiency must be corrected
within 120 days of notification or have a corrective action plan approved by DDW.
Notes:Needs new gasket.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS10 SPRING BOX LID LACKS A GASKET