HomeMy WebLinkAboutDDW-2025-009795Sanitary Survey - Deficiency Report
PWS Number:UTAH16014 Deficiency Points:40 Survey Date:09/09/2025
Survey Name:COYOTES AND COWBOYS
LINE CAMP
Surveyor:Peter Keers
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH16014 DISTRIBUTION SYSTEM
32. Does your Emergency Response Plan address cybersecurity? (only required for systems over 3,300 population, otherwise mark NA)
Rule: R309-105-7, 8 & 18, R309-100 through
605
Trigger for regulatory followup to address concerns.
Notes:Nothing connected to computer or internet.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS
Sanitary Survey Category: PU
SDWIS Severity Code: Significant Deficiency
Pump Stations | PF001 | BOOSTER PUMPS
97. If the pump station is used to pressurize the distribution system, does it have at least two functioning pumping units? ... if yes, answer the
following question(s)
Rule: R309-540-5(4)(b)Rule states inline booster pumps, withdrawing water directly from distribution lines
without storage and feeding water directly into distribution lines, shall have at least two
pumping units. This significant deficiency must be corrected within 120 days of
notification or have a corrective action plan approved by DDW.
Notes:not at this time
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: PS18 IN-LINE BOOSTER PUMP STATION LACKS REDUNDANCY TO MEET PEAK
DEMAND WITH ONE PUMP OUT OF SERVICE