Loading...
HomeMy WebLinkAboutDDW-2025-009795Sanitary Survey - Deficiency Report PWS Number:UTAH16014 Deficiency Points:40 Survey Date:09/09/2025 Survey Name:COYOTES AND COWBOYS LINE CAMP Surveyor:Peter Keers Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Management and Operations | DS001 | UTAH16014 DISTRIBUTION SYSTEM 32. Does your Emergency Response Plan address cybersecurity? (only required for systems over 3,300 population, otherwise mark NA) Rule: R309-105-7, 8 & 18, R309-100 through 605 Trigger for regulatory followup to address concerns. Notes:Nothing connected to computer or internet. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS Sanitary Survey Category: PU SDWIS Severity Code: Significant Deficiency Pump Stations | PF001 | BOOSTER PUMPS 97. If the pump station is used to pressurize the distribution system, does it have at least two functioning pumping units? ... if yes, answer the following question(s) Rule: R309-540-5(4)(b)Rule states inline booster pumps, withdrawing water directly from distribution lines without storage and feeding water directly into distribution lines, shall have at least two pumping units. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:not at this time Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: PS18 IN-LINE BOOSTER PUMP STATION LACKS REDUNDANCY TO MEET PEAK DEMAND WITH ONE PUMP OUT OF SERVICE