HomeMy WebLinkAboutDERR-2025-007466Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name Big Mountain Lodge
Address 15 N State St.
FERRON, UT 84523
Contact Big Mountain Lodge
Phone
Email bjbenson@hotmail.com
TANK LOCATION
Name Big Mountain Lodge
Address 15 N STATE ST
FERRON, UT 84523
A Operator None
Phone None
B Operator SAME
Phone SAME
Facility ID: 5000138 Inspection Date: 10/08/2025
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
1 - 1/2 Gas/Diesel No None None No No None None
2 - 3/4 Gas/Diesel No None None No No None None
3 - 5 Gas/Diesel No None None No No None None
TANK DETAILS
Tank ID/Alt ID 17 / 17
E-Gen/AST No / Yes
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Jan. 1, 1996 / 10000 /
Substance
Stored Gasoline / Regular
Tank Material-
Mod
Asphalt Coated or Bare Steel-
Secondary Containment
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Flexible Plastic / Double-
Walled
Pipe type/STP Cont Pressurized / No
STP Flex Connectors
LLD Model
Spill/Overfill/Sm
Delivery Dry Connect Fitting / / No
PST Fund/Other Type Yes / None
Tank/Pipe Rel Det TankTightness
PipeLineTightness
CP Tank Test None
CP Pipe Test None
Tank ID/Alt ID 18 / 18
E-Gen/AST No / Yes
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Jan. 1, 1990 / 7700 /
Substance
Stored Diesel / Diesel #2 (U.L.S.)
Tank Material-
Mod
Asphalt Coated or Bare Steel-
Secondary Containment
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Flexible Plastic / Double-
Walled
Pipe type/STP Cont Pressurized / Yes
STP Flex Connectors Steel Flex in Sump
LLD Model
Spill/Overfill/Sm
Delivery Dry Connect Fitting / / No
PST Fund/Other Type Yes / None
Tank/Pipe Rel Det TankTightness
PipeLineTightness
CP Tank Test None
CP Pipe Test None
2025-10-08 Page 1 of 5
Tank ID/Alt ID 19 / 19
E-Gen/AST No / Yes
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Jan. 1, 1996 / 5500 /
Substance
Stored Gasoline / Non-Ethanol
Tank Material-
Mod
Asphalt Coated or Bare Steel-
Secondary Containment
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Flexible Plastic / Double-
Walled
Pipe type/STP Cont Pressurized / No
STP Flex Connectors
LLD Model
Spill/Overfill/Sm
Delivery Dry Connect Fitting / / No
PST Fund/Other Type Yes / None
Tank/Pipe Rel Det TankTightness
PipeLineTightness
CP Tank Test None
CP Pipe Test None
Tank ID/Alt ID 20 / 20
E-Gen/AST No / Yes
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Jan. 1, 1990 / 5500 /
Substance
Stored Gasoline / Premium
Tank Material-
Mod
Asphalt Coated or Bare Steel-
Secondary Containment
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Flexible Plastic / Double-
Walled
Pipe type/STP Cont Pressurized / Yes
STP Flex Connectors Bare Steel Swing
LLD Model
Spill/Overfill/Sm
Delivery Dry Connect Fitting / / No
PST Fund/Other Type Yes / None
Tank/Pipe Rel Det TankTightness
PipeLineTightness
CP Tank Test None
CP Pipe Test None
INSPECTION COMMENTS
None
2025-10-08 Page 2 of 5
FACILITY RESPONSES
The above accurately represents the
facility's release detection records Yes
Financial Responsibility
Financial responsibility method is ok?Yes
TANK RESPONSES
Tank 17 Pressure Piping Leak Detection
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
No
Tank 18 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank 18 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Tank 19 Pressure Piping Leak Detection
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
No
Tank 20 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank 20 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Tank 17 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank 17 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Tank 18 Pressure Piping Leak Detection
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
No
Tank 19 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank 19 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Tank 20 Pressure Piping Leak Detection
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
No
DISPENSER RESPONSES
2025-10-08 Page 3 of 5
Dispenser 3/4
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 1/2
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 5
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
MONTHLY LEAK DETECTION MONITORING
Oct '24 Nov '24 Dec '24 Jan '25 Feb '25 Mar '25 Apr '25 May '25 Jun '25 Jul '25 Aug '25 Sep '25
Tank 17 Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 18 Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 19 Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 20 Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
NON-COMPLIANCE ITEMS
TANK 17
No Photos
Question:Does the pressurized piping system have a valid annual line tightness test or valid monthly
monitoring?
Comments:None
TANK 18
No Photos
Question:Does the pressurized piping system have a valid annual line tightness test or valid monthly
monitoring?
Comments:None
TANK 19
No Photos
Question:Does the pressurized piping system have a valid annual line tightness test or valid monthly
monitoring?
Comments:None
TANK 20
No Photos
Question:Does the pressurized piping system have a valid annual line tightness test or valid monthly
monitoring?
Comments:None
2025-10-08 Page 4 of 5
Prepared by fueloperator.com
Inspection Information
Inspector:Warner, Sean
Record Created:Oct. 8, 2025, 10:58 a.m.
Inspection Date:Oct. 8, 2025
2025-10-08 Page 5 of 5