HomeMy WebLinkAboutDDW-2025-009605Sanitary Survey - Deficiency Report
PWS Number:UTAH21020 Deficiency Points:145 Survey Date:09/22/2025
Survey Name:CANYON FUEL COMPANY
LLC
Surveyor:Chris Martin
Sanitary Survey Category: MR
SDWIS Severity Code: Recommendation
Management and Operations | DS001 | UTAH21020 DISTRIBUTION SYSTEM
35. For a community water system or a non-transient non-community water system, did you make your initial service line inventory available to
the public? (if a transient system, enter NA)
Rule: 40 CFR 141.84 (a)(8)The rule requires that the service line materials inventory be publicly accessible.
(a)(8)(ii) The rule requires that water systems serving greater than 50,000 persons
make the publicly accessible inventory available online. (a)(9) The rule requires that
when a water system has no lead, galvanized requiring replacement, or lead status
unknown service lines (regardless of ownership) in its inventory, it may comply with
the requirements using a written statement, in lieu of the inventory, declaring that the
distribution system has no lead service lines or galvanized requiring replacement
service lines. The statement must include a general description of all applicable sources
used to make this determination.
Notes:System has not made it available to the public.
Deficiency Points: 0
Days until points become effective on IPS: 0
SDWIS Deficiency Description: R006 FAILURE TO MAKE THE LEAD SERVICE LINE INVENTORY PUBLICLY
ACCESSIBLE
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH21020 DISTRIBUTION SYSTEM
40. Does the water system have records of on-going enforcement activities? (test history, enforcement activities, hazard assessments)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes test history and documentation of on-going enforcement activities.
Notes:Needs a year of documenting program.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M007 CCC-LACKS ON-GOING ENFORCEMENT IMPLEMENTATION
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | LOWER SPRING
80. No roots seen in collection boxes and junctions.
Rule: R309-105-10(4)(a), R309-515-8(1)(a)Spring collection areas shall be periodically (preferably annually) cleared of deep-
rooted vegetation to prevent root growth from clogging collection lines. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Roots in collection box #2.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS08 ROOTS IN SPRING COLLECTION PIPES
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | LOWER SPRING
81F. All openings/penetrations in the spring collection box are sealed.
Rule: R309-515-7(7)(d), R309-545-9(1) and (2)All junction and collection boxes shall comply with R309-545 and shall have suitable
watertight roofs and sidewalls that exclude birds, animals, insects, and excessive dust.
All openings shall be kept to a minimum and be watertight. Pipes that may contain
water of lesser quality than drinking water shall not penetrate the spring box. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:Corner of junction box needs to be sealed where concrete is broken.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS20 UNSEALED OPENINGS IN SPRING COLLECTION BOX
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP001 | LOWER SPRING CHLORINATOR
158. If continuous disinfection is needed, automatic switch over of chlorine cylinders is provided.
Rule: R309-520-7(2)(a), R309-520-6(1)Rule requires automatic switch over of chlorine cylinders be provided if continuous
disinfection is required.
Notes:Does not have auto switch over.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD01 CONTINUOUS DISINFECTION IS REQUIRED BUT CHLORINATOR LACKS
AUTOMATIC SWITCHOVER
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Gaseous Chlorination | TP001 | LOWER SPRING CHLORINATOR
161. Chlorine vent line discharges outside and above grade and is screened with #14 mesh screen.
Rule: R309-520-7(2)(e)Rule requires the chlorine vent line to discharge outside, above grade, at a point least
susceptible to vandalism, and to have the end covered with a #14 mesh non-corrodible
screen. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:Screen needs to be fixed.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TD13 CHLORINE VENT LINE NOT DISCHARGED OUTSIDE ABOVE GRADE OR LACKS
NO. 14 SCREEN
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP001 | LOWER SPRING CHLORINATOR
166B. Bottle of ammonium hydroxide (56 % ammonia solution) is available for chlorine leak detection
Rule: R309-520-7(2)(l)(i)Rule requires a bottle of ammonium hydroxide (56% ammonia solution) to be available
for leak detection.
Notes:Need bottle
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD14 NO AMMONIA HYDROXIDE SOLUTION FOR CHLORINE LEAK DETECTION