HomeMy WebLinkAboutDAQ-2024-0073991
DAQC-333-24
Site ID 10917 (B4)
MEMORANDUM
TO: STACK TEST FILE – COMPASS MINERALS INTERNATIONAL – Ogden
Production Plant
THROUGH: Harold Burge, Major Source Compliance Section Manager
FROM: Paul Morris, Environmental Scientist
DATE: April 12, 2024
SUBJECT: Source: AH-513
Contact: Holly Hurst: 801-732-3251
Location: 765 North 10500 West, Ogden, Weber County, Utah
FRS ID#: UT0000004905700001
Test Contractor: Alliance Technical Group, LLC.
Permit/AO#: Title V permit 5700001004, dated June 10, 2021, Date of Last
Revision: December 15, 2023
Action Code: 3A
Subject: Review of Stack Test Report dated April 11, 2024
On April 11, 2024, Utah Division of Air Quality (DAQ) received a test report (email copy) for retesting of
the above listed unit following a test failure on October 11, 2023. Testing was performed February 15 and
16, 2024, to demonstrate compliance with the emission limits found in Title V permit condition II.B.5.b. The
calculated test results are:
Source Test Date Test Method Pollutant DAQ Result Result Limit
AH-513 2/15-16/2024 5/202 PM 2.5 0.0014 gr/dscf 0.0015 gr/dscf 0.0114 gr/dscf
0.23 lb/hr 0.23 lb/hr 1.49 lb/hr
PM 10 0.54 lb/hr 0.55 lb/hr 1.49 lb/hr
Particle sizing was conducted using electron microscopy to determine PM10 and PM2.5
DEVIATIONS: No deviations were reported during this testing.
CONCLUSION: The stack test report appears to be acceptable.
RECOMMENDATION: Send a settlement agreement to resolve the stack test failure on October 11,
2023.
ATTACHMENTS: DAQ stack test review excel spreadsheets, Compass Minerals stack test
report.
6 , 3
Source Information
Division of Air Quality
Compliance Demonstration
Source Information
Company Name Compass Minerals - AH-513
Company Contact:Holly Hurst
Contact Phone No.(801) 732-3251
Source Designation:AH-513
Test & Review Dates
Test Date: 2/15-16/2024
Review Date: 4/11/2024 Tabs Are Shown
Observer:
Reviewer:Paul Morris
Particulate Emission Limits
lbs/MMBtu lbs/hr gr/dscf
1.490 0.011
Emission Rates - "Front Half"
lbs/MMBtu lbs/hr gr/dscf
0.0602 0.0004
Test Information
Stack_I.D._inches As ft^2 Y Dl H @ Cp Pbar Pq (static)Dn
51.00 14.19 0.9950 1.853 0.84 25.59 -0.32 0.28
Contractor Information
Contracting Company: Alliance Technical Group
Contact: Charles Horton
Phone No.: 464-352-7568
Project No.:
Circular
10100
9780
9860
9190
8710
8710
8710
10540
10640
11950
320
10610
10200
10390
1970
1800
1910
1420
1040
1190
1250
F factor usedF factors for Coal, Oil, and Gas
Anthrocite 2
Lignite
Natural
Propane
Butane
COAL
OIL
GAS
Bituminous 2
Fd Fw Fc
scf/MMBtu scf/MMBtu scf/MMBtu
O2
CO2
lbs/MMBtu
Page 1
Summary
Division of Air Quality
Reference Methods 5 - TSP
Compliance Demonstration of
Compass Minerals - AH-513
Testing Results Lab Data - grams collected
Test Date 2/15-16/2024 2/15-16/2024 2/15-16/2024 2/15-16/2024 Lab Data Probe Filter Back
Circular Run 1 Run 2 Run 3 Run 4 Run 1 0.0053 0.0625 0.0028 1.6%
As ft^2 14.19 14.19 14.19 Run 2 0.0031 0.0256 0.0021 2.3%
Pbar 25.59 25.59 25.59 Run 3 0.0036 0.0258 0.0022 2.6%
Pq (static)-0.32 -0.32 -0.32 Run 4
Ps 25.57 25.57 25.57
Avg. Ts F 122.79 116.83 114.21 Front Half Emissions Summary
CO2 - FCO2 3.00 3.00 3.00 Run 1 Run 2 Run 3 Run 4 Avg.
O2 16.00 16.00 16.00 gr./dscf 0.0005 0.0003 0.0003 0.00038
N2+C 81.00 81.00 81.00 lbs/hr 0.0770 0.0484 0.0553 0.0602
Md 29.12 29.12 29.12 lbs/MMBtu
Ms 27.50 27.95 27.86
Y 1.00 1.00 1.00
Cp 0.84 0.84 0.84 Total Emissions Summary w/back half condensable
Vm cf 38.12 38.60 39.10 Run 1 Run 2 Run 3 Run 4 Avg.
Vlc 124.50 84.70 94.00 gr./dscf 0.0018 0.0013 0.0013 0.0014
AVG. Tm F 46.79 54.42 47.08 lbs/hr 0.2758 0.2026 0.2144 0.2309
Vm std 33.90 33.82 34.76 lbs/MMBtu
Vw std 5.86 3.99 4.42
Bws 0.15 0.11 0.11
S Bws 0.15 0.12 0.11
Avg. Sqrt
Dlp 0.49 0.49 0.50
Vs 32.32 31.50 32.03 F factor used
scfm wet 21297.52 20972.34 21421.02
acfm 27510.48 26813.47 27262.49
Qsd dscfh 1091343.01 1125637.96 1140135.31
# Sample
Points 24.00 24.00 24.00
Dn 0.280 0.280 0.280
An 4.28E-04 4.28E-04 4.28E-04
Start Time 0:00 0:00 0:00
End Time 0:00 0:00 0:00
Total Test
time 60.00 60.00 60.00
Time @ point 2.50 2.50 2.50
PM 2.5 fraction
80.00
90.00
100.00
110.00
120.00
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
%
I
s
o
k
i
n
e
t
i
c
Points
Run 1 PxP Isokinetic
80.00
90.00
100.00
110.00
120.00
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
%
I
s
o
k
i
n
e
t
i
c
Sample Points
Run 2 PxP Isokinetic
80.00
90.00
100.00
110.00
120.00
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
%
I
s
o
k
i
n
e
t
i
c
Sample Points
Run 3 PxP Isokinetic
O2
CO2
lbs/MMBtu
80.00
90.00
100.00
110.00
120.00
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
Sample Points
Run 4 PxP Isokinetic
Page 1
Run 1
Compass Minerals - AH-513 Flow & Moisture Test Date 2/15-16/2024
As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms
14.19 25.59 -0.32 25.57 123 3.00 16.00 81.00 29.12 27.50
Y Cp Vm cf Vlc Avg. Tm F Vm std Vw std Bws S Bws 0.1460
0.9950 0.84 38.120 124.50 46.79 33.900 5.860 0.1474 0.1460 0.999
Avg. Sqrt
Dlp Vs scfm wet acfm Qsd dscfh
# Sample
Points Dn
Total Test
time (minutes)
Time @ point
(minutes)Avg. Dlh
0.494 32.32 21,298 27,510 1.09E+06 24 0.28 60 2.50 1.192500
TRUE
Point No.Meter (cf) dl "p" dl "h" ts F tm F (in) tm F (out) Imp. Liquid Collected
1 800.976 0.44 2.00 123 50 Wt. (Final) Wt. (Initial) lc
2 803.020 0.45 2.10 123 48 574.60 483.00 91.6
3 805.130 0.46 2.10 123 47 649.70 637.20 12.5
4 807.250 0.48 2.20 123 48 578.50 573.90 4.6
5 809.430 0.44 2.00 124 47 738.20 733.40 4.8
6 811.530 0.42 2.00 123 46 995.1 984.1 11.0
7 813.570 0.32 1.60 124 47
8 815.510 0.24 1.10 123 47 Isokinetics 103.3
9 817.130 0.18 0.84 123 48 Test Date 2/15-16/2024
10 818.490 0.17 0.79 123 49 Start Time enter
11 819.850 0.17 0.79 123 48 End Time
12 821.210 0.17 0.79 123 48 Run 1
13 822.535 0.18 0.84 123 47
14 823.880 0.20 0.93 123 47
15 825.330 0.22 1.02 123 46
16 826.810 0.24 1.11 122 46
17 828.430 0.26 1.21 122 46
18 829.960 0.22 1.02 121 46
19 831.440 0.18 0.84 122 46
20 832.800 0.15 0.70 122 46
21 834.390 0.15 0.70 122 45
22 835.390 0.15 0.69 123 45
23 836.690 0.14 0.65 123 45
24 837.930 0.13 0.60 123 45
25 839.096
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Page 1
Run 2
Compass Minerals - AH-513 Flow & Moisture Test Date 2/15-16/2024
As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms
14.19 25.59 -0.32 25.57 117 3.00 16.00 81.00 29.12 27.95
Y Cp Vm cf Vlc Avg. Tm F Vm std Vw std Bws S Bws 0.1237
0.9950 0.84 38.600 84.70 54 33.818 3.987 0.1055 0.1237 0.999
Avg. Sqrt
Dlp Vs scfm wet acfm Qsd dscfh
# Sample
Points Dn
Total Test
time (minutes)
Time @ point
(minutes)Avg. Dlh
0.488 31.50 20,972 26,813 1.13E+06 24 0.28 60 2.50 1.19
TRUE
Point No.Meter (cf) dl "p" dl "h" ts F tm F (in) tm F (out) Imp. Liquid Collected
1 839.466 0.44 2.10 116.0 58.0 Wt. (Final) Wt. (Initial) lc
2 841.580 0.45 2.10 116.0 57.0 575.40 499.20 76.2
3 843.740 0.47 2.20 117.0 59.0 637.00 634.10 2.9
4 845.930 0.46 2.20 118.0 59.0 643.60 643.40 0.2
5 848.110 0.46 2.20 119.0 60.0 736.90 742.90 -6.0
6 850.270 0.42 2.00 119.0 60.0 985.6 974.2 11.4
7 852.360 0.25 1.20 118.0 61.0
8 853.990 0.21 0.99 118.0 61.0 Isokinetics 99.7
9 855.490 0.18 0.85 118.0 58.0 Test Date 2/15-16/2024
10 856.890 0.17 0.80 117.0 58.0 Start Time
11 858.270 0.18 0.85 117.0 57.0 End Time
12 859.690 0.16 0.76 117.0 56.0 Run 2
13 861.020 0.13 0.62 114.0 55.0
14 862.230 0.13 0.62 114.0 52.0
15 863.460 0.13 0.62 114.0 52.0
16 864.690 0.14 0.67 115.0 51.0
17 865.950 0.14 0.66 116.0 51.0
18 867.210 0.16 0.76 116.0 50.0
19 868.580 0.18 0.85 117.0 50.0
20 870.010 0.32 1.50 117.0 49.0
21 871.880 0.23 1.10 117.0 49.0
22 873.450 0.22 1.00 118.0 48.0
23 875.030 0.21 0.99 118.0 48.0
24 876.550 0.20 0.95 118.0 47.0
25 878.066
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Page 1
Run 3
Compass Minerals - AH-513 Flow & Moisture Test Date 2/15-16/2024
As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms
14.19 25.59 -0.32 25.57 114 3.00 16.00 81.00 29.12 27.86
Y Cp Vm cf Vlc Avg. Tm F Vm std Vw std Bws S Bws 0.1149
0.9950 0.84 39.101 94.00 47 34.760 4.425 0.1129 0.1149 0.999
Avg. Sqrt
Dlp Vs scfm wet acfm Qsd dscfh
# Sample
Points Dn
Total Test
time (minutes)
Time @ point
(minutes)Avg. Dlh
0.497 32.03 21,421 27,262 1.14E+06 24 0.28 60 2.50 1.27
TRUE
Point No.Meter (cf) dl "p" dl "h" ts F tm F (in) tm F (out) Imp. Liquid Collected
1 616.414 0.47 2.20 115.0 44.0 Wt. (Final) Wt. (Initial) lc
2 618.670 0.46 2.20 113.0 45.0 555.9 483.7 72.2
3 620.930 0.50 2.40 114.0 45.0 642.9 639.2 3.7
4 623.420 0.49 2.40 114.0 45.0 575.3 576.3 -1.0
5 625.490 0.48 2.30 113.0 46.0 740.5 736.8 3.7
6 627.720 0.42 2.00 114.0 46.0 991.1 975.7 15.4
7 629.795 0.26 1.30 115.0 46.0
8 631.530 0.21 1.00 115.0 47.0 Isokinetics 101.2
9 633.030 0.20 0.97 115.0 47.0 Test Date 2/15-16/2024
10 634.520 0.19 0.92 114.0 47.0 Start Time
11 635.925 0.18 0.88 115.0 48.0 End Time
12 637.330 0.17 0.83 114.0 48.0 Run 3
13 638.662 0.13 0.64 114.0 45.0
14 639.845 0.12 0.59 115.0 46.0
15 640.965 0.13 0.64 115.0 46.0
16 642.145 0.14 0.69 114.0 46.0
17 643.350 0.14 0.69 115.0 47.0
18 644.570 0.16 0.79 113.0 48.0
19 645.920 0.30 1.50 114.0 48.0
20 647.680 0.28 1.40 114.0 48.0
21 649.465 0.24 1.20 115.0 50.0
22 651.075 0.22 1.10 114.0 50.0
23 652.630 0.19 0.93 114.0 51.0
24 654.100 0.19 0.93 113.0 51.0
25 655.515
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Page 1
Source Information
Division of Air Quality
Compliance Demonstration
Source Information
Company Name Compass Minerals - AH-513
Company Contact:Holly Hurst
Contact Phone No.(801) 732-3251
Source Designation:AH-513
Test & Review Dates
Test Date: 2/15-16/2024
Review Date: 4/12/2024 Tabs Are Shown
Observer:
Reviewer:Paul Morris
Particulate Emission Limits
lbs/MMBtu lbs/hr gr/dscf
1.490 0.011
Emission Rates - "Front Half"
lbs/MMBtu lbs/hr gr/dscf
0.3726 0.0023
Test Information
Stack_I.D._inches As ft^2 Y Dl H @ Cp Pbar Pq (static)Dn
51.00 14.19 0.9950 1.853 0.84 25.59 -0.32 0.28
Contractor Information
Contracting Company: Alliance Technical Group
Contact: Charles Horton
Phone No.: 464-352-7568
Project No.:
Circular
10100
9780
9860
9190
8710
8710
8710
10540
10640
11950
320
10610
10200
10390
1970
1800
1910
1420
1040
1190
1250
F factor usedF factors for Coal, Oil, and Gas
Anthrocite 2
Lignite
Natural
Propane
Butane
COAL
OIL
GAS
Bituminous 2
Fd Fw Fc
scf/MMBtu scf/MMBtu scf/MMBtu
O2
CO2
lbs/MMBtu
Page 1
Summary
Division of Air Quality
Reference Methods 5 - TSP
Compliance Demonstration of
Compass Minerals - AH-513
Testing Results Lab Data - grams collected
Test Date 2/15-16/2024 2/15-16/2024 2/15-16/2024 2/15-16/2024 Lab Data Probe Filter Back
Circular Run 1 Run 2 Run 3 Run 4 Run 1 0.0053 0.0625 0.0028 11.8%
As ft^2 14.19 14.19 14.19 Run 2 0.0031 0.0256 0.0021 15.0%
Pbar 25.59 25.59 25.59 Run 3 0.0036 0.0258 0.0022 11.0%
Pq (static)-0.32 -0.32 -0.32 Run 4
Ps 25.57 25.57 25.57
Avg. Ts F 122.79 116.83 114.21 Front Half Emissions Summary
CO2 - FCO2 3.00 3.00 3.00 Run 1 Run 2 Run 3 Run 4 Avg.
O2 16.00 16.00 16.00 gr./dscf 0.0036 0.0020 0.0014 0.00235
N2+C 81.00 81.00 81.00 lbs/hr 0.5679 0.3160 0.2339 0.3726
Md 29.12 29.12 29.12 lbs/MMBtu
Ms 27.50 27.95 27.86
Y 1.00 1.00 1.00
Cp 0.84 0.84 0.84 Total Emissions Summary w/back half condensable
Vm cf 38.12 38.60 39.10 Run 1 Run 2 Run 3 Run 4 Avg.
Vlc 124.50 84.70 94.00 gr./dscf 0.0049 0.0029 0.0024 0.0034
AVG. Tm F 46.79 54.42 47.08 lbs/hr 0.7667 0.4701 0.3930 0.5433
Vm std 33.90 33.82 34.76 lbs/MMBtu
Vw std 5.86 3.99 4.42
Bws 0.15 0.11 0.11
S Bws 0.15 0.12 0.11
Avg. Sqrt
Dlp 0.49 0.49 0.50
Vs 32.32 31.50 32.03 F factor used
scfm wet 21297.52 20972.34 21421.02
acfm 27510.48 26813.47 27262.49
Qsd dscfh 1091343.01 1125637.96 1140135.31
# Sample
Points 24.00 24.00 24.00
Dn 0.280 0.280 0.280
An 4.28E-04 4.28E-04 4.28E-04
Start Time 0:00 0:00 0:00
End Time 0:00 0:00 0:00
Total Test
time 60.00 60.00 60.00
Time @ point 2.50 2.50 2.50
PM 2.5 fraction
80.00
90.00
100.00
110.00
120.00
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
%
I
s
o
k
i
n
e
t
i
c
Points
Run 1 PxP Isokinetic
80.00
90.00
100.00
110.00
120.00
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
%
I
s
o
k
i
n
e
t
i
c
Sample Points
Run 2 PxP Isokinetic
80.00
90.00
100.00
110.00
120.00
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
%
I
s
o
k
i
n
e
t
i
c
Sample Points
Run 3 PxP Isokinetic
O2
CO2
lbs/MMBtu
80.00
90.00
100.00
110.00
120.00
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
Sample Points
Run 4 PxP Isokinetic
Page 1
Run 1
Compass Minerals - AH-513 Flow & Moisture Test Date 2/15-16/2024
As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms
14.19 25.59 -0.32 25.57 123 3.00 16.00 81.00 29.12 27.50
Y Cp Vm cf Vlc Avg. Tm F Vm std Vw std Bws S Bws 0.1460
0.9950 0.84 38.120 124.50 46.79 33.900 5.860 0.1474 0.1460 0.999
Avg. Sqrt
Dlp Vs scfm wet acfm Qsd dscfh
# Sample
Points Dn
Total Test
time (minutes)
Time @ point
(minutes)Avg. Dlh
0.494 32.32 21,298 27,510 1.09E+06 24 0.28 60 2.50 1.192500
TRUE
Point No.Meter (cf) dl "p" dl "h" ts F tm F (in) tm F (out) Imp. Liquid Collected
1 800.976 0.44 2.00 123 50 Wt. (Final) Wt. (Initial) lc
2 803.020 0.45 2.10 123 48 574.60 483.00 91.6
3 805.130 0.46 2.10 123 47 649.70 637.20 12.5
4 807.250 0.48 2.20 123 48 578.50 573.90 4.6
5 809.430 0.44 2.00 124 47 738.20 733.40 4.8
6 811.530 0.42 2.00 123 46 995.1 984.1 11.0
7 813.570 0.32 1.60 124 47
8 815.510 0.24 1.10 123 47 Isokinetics 103.3
9 817.130 0.18 0.84 123 48 Test Date 2/15-16/2024
10 818.490 0.17 0.79 123 49 Start Time enter
11 819.850 0.17 0.79 123 48 End Time
12 821.210 0.17 0.79 123 48 Run 1
13 822.535 0.18 0.84 123 47
14 823.880 0.20 0.93 123 47
15 825.330 0.22 1.02 123 46
16 826.810 0.24 1.11 122 46
17 828.430 0.26 1.21 122 46
18 829.960 0.22 1.02 121 46
19 831.440 0.18 0.84 122 46
20 832.800 0.15 0.70 122 46
21 834.390 0.15 0.70 122 45
22 835.390 0.15 0.69 123 45
23 836.690 0.14 0.65 123 45
24 837.930 0.13 0.60 123 45
25 839.096
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Page 1
Run 2
Compass Minerals - AH-513 Flow & Moisture Test Date 2/15-16/2024
As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms
14.19 25.59 -0.32 25.57 117 3.00 16.00 81.00 29.12 27.95
Y Cp Vm cf Vlc Avg. Tm F Vm std Vw std Bws S Bws 0.1237
0.9950 0.84 38.600 84.70 54 33.818 3.987 0.1055 0.1237 0.999
Avg. Sqrt
Dlp Vs scfm wet acfm Qsd dscfh
# Sample
Points Dn
Total Test
time (minutes)
Time @ point
(minutes)Avg. Dlh
0.488 31.50 20,972 26,813 1.13E+06 24 0.28 60 2.50 1.19
TRUE
Point No.Meter (cf) dl "p" dl "h" ts F tm F (in) tm F (out) Imp. Liquid Collected
1 839.466 0.44 2.10 116.0 58.0 Wt. (Final) Wt. (Initial) lc
2 841.580 0.45 2.10 116.0 57.0 575.40 499.20 76.2
3 843.740 0.47 2.20 117.0 59.0 637.00 634.10 2.9
4 845.930 0.46 2.20 118.0 59.0 643.60 643.40 0.2
5 848.110 0.46 2.20 119.0 60.0 736.90 742.90 -6.0
6 850.270 0.42 2.00 119.0 60.0 985.6 974.2 11.4
7 852.360 0.25 1.20 118.0 61.0
8 853.990 0.21 0.99 118.0 61.0 Isokinetics 99.7
9 855.490 0.18 0.85 118.0 58.0 Test Date 2/15-16/2024
10 856.890 0.17 0.80 117.0 58.0 Start Time
11 858.270 0.18 0.85 117.0 57.0 End Time
12 859.690 0.16 0.76 117.0 56.0 Run 2
13 861.020 0.13 0.62 114.0 55.0
14 862.230 0.13 0.62 114.0 52.0
15 863.460 0.13 0.62 114.0 52.0
16 864.690 0.14 0.67 115.0 51.0
17 865.950 0.14 0.66 116.0 51.0
18 867.210 0.16 0.76 116.0 50.0
19 868.580 0.18 0.85 117.0 50.0
20 870.010 0.32 1.50 117.0 49.0
21 871.880 0.23 1.10 117.0 49.0
22 873.450 0.22 1.00 118.0 48.0
23 875.030 0.21 0.99 118.0 48.0
24 876.550 0.20 0.95 118.0 47.0
25 878.066
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Page 1
Run 3
Compass Minerals - AH-513 Flow & Moisture Test Date 2/15-16/2024
As ft^2 Pbar Pq (static) Ps Avg. Ts F CO2 - FCO2 O2 N2+C Md Ms
14.19 25.59 -0.32 25.57 114 3.00 16.00 81.00 29.12 27.86
Y Cp Vm cf Vlc Avg. Tm F Vm std Vw std Bws S Bws 0.1149
0.9950 0.84 39.101 94.00 47 34.760 4.425 0.1129 0.1149 0.999
Avg. Sqrt
Dlp Vs scfm wet acfm Qsd dscfh
# Sample
Points Dn
Total Test
time (minutes)
Time @ point
(minutes)Avg. Dlh
0.497 32.03 21,421 27,262 1.14E+06 24 0.28 60 2.50 1.27
TRUE
Point No.Meter (cf) dl "p" dl "h" ts F tm F (in) tm F (out) Imp. Liquid Collected
1 616.414 0.47 2.20 115.0 44.0 Wt. (Final) Wt. (Initial) lc
2 618.670 0.46 2.20 113.0 45.0 555.9 483.7 72.2
3 620.930 0.50 2.40 114.0 45.0 642.9 639.2 3.7
4 623.420 0.49 2.40 114.0 45.0 575.3 576.3 -1.0
5 625.490 0.48 2.30 113.0 46.0 740.5 736.8 3.7
6 627.720 0.42 2.00 114.0 46.0 991.1 975.7 15.4
7 629.795 0.26 1.30 115.0 46.0
8 631.530 0.21 1.00 115.0 47.0 Isokinetics 101.2
9 633.030 0.20 0.97 115.0 47.0 Test Date 2/15-16/2024
10 634.520 0.19 0.92 114.0 47.0 Start Time
11 635.925 0.18 0.88 115.0 48.0 End Time
12 637.330 0.17 0.83 114.0 48.0 Run 3
13 638.662 0.13 0.64 114.0 45.0
14 639.845 0.12 0.59 115.0 46.0
15 640.965 0.13 0.64 115.0 46.0
16 642.145 0.14 0.69 114.0 46.0
17 643.350 0.14 0.69 115.0 47.0
18 644.570 0.16 0.79 113.0 48.0
19 645.920 0.30 1.50 114.0 48.0
20 647.680 0.28 1.40 114.0 48.0
21 649.465 0.24 1.20 115.0 50.0
22 651.075 0.22 1.10 114.0 50.0
23 652.630 0.19 0.93 114.0 51.0
24 654.100 0.19 0.93 113.0 51.0
25 655.515
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Page 1
Source Test Report
Compass Minerals
765 North 10500 West
Ogden, UT 84404
Sources Tested: One (1) Scrubber: AH-513
Test Dates: February 15 & 16, 2024
Project No. AST-2024-0698
Prepared By
Alliance Technical Group, LLC
3683 W 2270 S, Suite E
West Valley City, UT 84120
Source Test Report
Test Program Summary
AST-2024-0698 Compass – Ogden, UT Page i
Regulatory Information
Permit Nos. Title V #5700001003
DAQE-AN1091070039-20
Source Information
Source Name Source ID Target Parameters
Salt Dryer (D-501) AH-513 PM, PM10, PM2.5
Contact Information
Test Location Test Company Analytical Laboratories
Compass Minerals Ogden, Inc.
765 North 10500 West
Ogden, UT 84404
Holly Hurst
hursth@compassminerals.com
(801) 732-3251
Vikrant Chavan
chavanv@compassminerals.com
(801) 648-2005
Alliance Technical Group, LLC
3683 W 2270 S, Suite E
West Valley City, UT 84120
Project Manager
Charles Horton
charles.horton@alliancetg.com
(352) 663-7568
Field Team Leader
Tobias Hubbard
tobias.hubbard@alliancetg.com
(605) 645-8562
QA/QC Manager
Kathleen Shonk
katie.shonk@alliancetg.com
(812) 452-4785
Report Coordinator
Indah Rahmadina
indah.rahmadina@alliancetg.com
Report Reviewer
Sarah Perry
sarah.perry@alliancetg.com
Alliance Technical Group, LLC
5530 Marshall Street
Arvada, CO 80002
Eric Grosjean
eric.grosjean@alliancetg.com
(303) 420-5949
Particle Technology Labs
555 Rogers Street
Downers Grove, IL 60515
Oliver Urbanek
ourbanek@particlelabs.com
(630) 969-2703
Source Test Report
Certification Statement
AST-2024-0698 Compass – Ogden, UT Page ii
Alliance Technical Group, LLC (Alliance) has completed the source testing as described in this report. Results
apply only to the source(s) tested and operating condition(s) for the specific test date(s) and time(s) identified within
this report. All results are intended to be considered in their entirety, and Alliance is not responsible for use of less
than the complete test report without written consent. This report shall not be reproduced in full or in part without
written approval from the customer.
To the best of my knowledge and abilities, all information, facts and test data are correct. Data presented in this
report has been checked for completeness and is accurate, error-free and legible. Onsite testing was conducted in
accordance with approved internal Standard Operating Procedures. Any deviations or problems are detailed in the
relevant sections in the test report.
This report is only considered valid once an authorized representative of Alliance has signed in the space provided
below; any other version is considered draft. This document was prepared in portable document format (.pdf) and
contains pages as identified in the bottom footer of this document.
Charles Horton, QSTI
Alliance Technical Group, LLC
Date
4/11/2024
Source Test Report
Table of Contents
AST-2024-0698 Compass – Ogden, UT Page iii
TABLE OF CONTENTS
1.0 Introduction ................................................................................................................................................. 1-1
1.1 Process/Control System Descriptions .......................................................................................................... 1-1
1.2 Project Team ............................................................................................................................................... 1-1
1.3 Site Specific Test Plan & Notification ........................................................................................................ 1-1
2.0 Summary of Results .................................................................................................................................... 2-1
3.0 Testing Methodology .................................................................................................................................. 3-1
3.1 U.S. EPA Reference Test Methods 1 and 2 – Sampling/Traverse Points and Volumetric Flow Rate ........ 3-1
3.2 U.S. EPA Reference Test Method 3/3A – Oxygen/Carbon Dioxide ........................................................... 3-1
3.3 U.S. EPA Reference Test Method 4 – Moisture Content ............................................................................ 3-1
3.4 U.S. EPA Reference Test Methods 5 and 202 – Total Particulate Matter ................................................... 3-1
3.5 Quality Assurance/Quality Control – U.S. EPA Reference Test Method 3/3A .......................................... 3-2
LIST OF TABLES
Table 1-1: Project Team ........................................................................................................................................... 1-1
Table 2-1: Summary of Results ................................................................................................................................ 2-1
Table 3-1: Source Testing Methodology .................................................................................................................. 3-1
APPENDICES
Appendix A Sample Calculations
Appendix B Field Data
Appendix C Laboratory Data
Appendix D Quality Assurance/Quality Control Data
Appendix E Process Operating/Control System Data
Introduction
Source Test Report
Introduction
AST-2024-0698 Compass – Ogden, UT Page 1-1
1.0 Introduction
Alliance Technical Group, LLC (Alliance) was retained by Compass Minerals Ogden Inc. (Compass) to conduct
compliance testing at the Ogden, Utah facility. The facility is subject to provisions of the Title V Operating Permit
#5700001003. Testing was conducted to determine the emission rates of particulate matter (PM), particulate matter
less than 2.5 microns (PM2.5), and particulate matter less than 10 microns (PM10) from the exhaust of one (1)
scrubber designated as AH-513.
Due to stack diameter and/or entrained water limitations of AH-513, Methods 5 and 202 were conducted in lieu of
method 201A and 202. Particle sizing was conducted using scanning electron microscopy to determine PM10 and
PM2.5.
1.1 Process/Control System Descriptions
Compass operates a mineral recovery facility on the eastern shore of the south arm of the Great Salt Lake near
Ogden, Utah in Weber County. This facility produces sodium chloride (NaCl), sulfate of potash (SOP) (K2SO4),
and magnesium chloride (MgCl2). The process uses crystallized salts, including halite (sodium chloride) and a
mixed salt containing potassium sulfate and magnesium sulfate from solar evaporation ponds. The raw halite is
washed, wet-screened, dried, cooled, dry-screened, packages, and shipped. The mixed salt is washed, slurried,
thickened, crystallized, and converted to schoenite which is then filtered, dried, screened, half granulated/compacted
and shipped as sulfate of potash.
1.2 Project Team
Personnel involved in this project are identified in the following table.
Table 1-1: Project Team
Compass Personnel Vikrant Chavan
Alliance Personnel
Tobias Hubbard
Finn Townsley
Alan Barrios
Dillon Brown
1.3 Site Specific Test Plan & Notification
Testing was conducted in accordance with the Site-Specific Test Plan (SSTP) submitted to UDAQ by Compass.
Summary of Results
Source Test Report
Summary of Results
AST-2024-0698 Compass – Ogden, UT Page 2-1
2.0 Summary of Results
Alliance conducted compliance testing at the Compass facility in Ogden, Utah on February 15 and 16, 2024.
Testing consisted of determining the emission rates of PM, PM2.5, and PM10 from the exhaust of one (1) scrubber
designated as AH-513.
Table 2-1 provides a summary of the emission testing results with comparisons to the applicable UDAQ permit
limits. Any difference between the summary results listed in the following table and the detailed results contained in
appendices is due to rounding for presentation.
Table 2-1: Summary of Results
Run Number Run 1 Run 2 Run 3 Average
Date 2/15/24 2/15/24 2/16/24 --
Filterable Particulate Matter less than 2.5 Microns Data
Concentration, grain/dscf 0.00050 0.00030 0.00034 0.00038
Emission Rate, lb/hr 0.078 0.048 0.056 0.061
Filterable Particulate Matter less than 10 Microns Data
Concentration, grain/dscf 0.0037 0.0020 0.0014 0.0024
Emission Rate, lb/hr 0.58 0.32 0.24 0.38
Condensable Particulate Matter
Concentration, grain/dscf 0.0013 0.0010 0.0010 0.0011
Emission Rate, lb/hr 0.20 0.15 0.16 0.17
Total Particulate Matter less than 2.5 Microns Data 1
Concentration, grain/dscf 0.0018 0.0013 0.0013 0.0015
Emission Limit, grain/dscf -- -- -- 0.0114
Percent of Limit, % -- -- -- 13
Emission Rate, lb/hr 0.28 0.20 0.22 0.23
Emission Limit, lb/hr -- -- -- 1.49
Percent of Limit, % -- -- -- 16
Total Particulate Matter less than 10 Microns Data 2
Concentration, grain/dscf 0.0050 0.0029 0.0024 0.0035
Emission Rate, lb/hr 0.78 0.47 0.40 0.55
Emission Limit, lb/hr -- -- -- 1.49
Percent of Limit, % -- -- -- 37
1 Total PM2.5 is the summation of filterable PM2.5 and condensable PM.
2 Total PM10 is the summation of filterable PM10 and condensable PM.
Testing Methodology
Source Test Report
Testing Methodology
AST-2024-0698 Compass – Ogden, UT Page 3-1
3.0 Testing Methodology
The emission testing program was conducted in accordance with the test methods listed in Table 3-1. Method
descriptions are provided below while quality assurance/quality control data is provided in Appendix D.
Table 3-1: Source Testing Methodology
Parameter U.S. EPA Reference
Test Methods Notes/Remarks
Volumetric Flow Rate 1 & 2 Full Velocity Traverses
Oxygen / Carbon Dioxide 3 / 3A Integrated Bag / Instrumental Analysis
Moisture Content 4 Gravimetric Analysis
Total Particulate Matter 5 / 202 Isokinetic Sampling
3.1 U.S. EPA Reference Test Methods 1 and 2 – Sampling/Traverse Points and Volumetric Flow Rate
The sampling location and number of traverse (sampling) points were selected in accordance with U.S. EPA
Reference Test Method 1. To determine the minimum number of traverse points, the upstream and downstream
distances were equated into equivalent diameters and compared to Figure 1-1 in U.S. EPA Reference Test Method 1.
Full velocity traverses were conducted in accordance with U.S. EPA Reference Test Method 2 to determine the
average stack gas velocity pressure, static pressure and temperature. The velocity and static pressure measurement
system consisted of a pitot tube and inclined manometer. The stack gas temperature was measured with a K-type
thermocouple and pyrometer.
Stack gas velocity pressure and temperature readings were recorded during each test run. The data collected was
utilized to calculate the volumetric flow rate in accordance with U.S. EPA Reference Test Method 2.
3.2 U.S. EPA Reference Test Method 3/3A – Oxygen/Carbon Dioxide
The oxygen (O2) and carbon dioxide (CO2) testing was conducted in accordance with U.S. EPA Reference Test
Method 3/3A. One (1) integrated Tedlar bag sample was collected during each test run. The bag samples were
analyzed on site with a gas analyzer. The remaining stack gas constituent was assumed to be nitrogen for the stack
gas molecular weight determination. The quality control measures are described in Section 3.5.
3.3 U.S. EPA Reference Test Method 4 – Moisture Content
The stack gas moisture content (BWS) was determined in accordance with U.S. EPA Reference Test Method 4. The
gas conditioning train consisted of a series of chilled impingers. Prior to testing, each impinger was filled with a
known quantity of water or silica gel. Each impinger was analyzed gravimetrically before and after each test run on
the same balance to determine the amount of moisture condensed.
3.4 U.S. EPA Reference Test Methods 5 and 202 – Total Particulate Matter
The total particulate matter (filterable and condensable PM) testing was conducted in accordance with U.S. EPA
Reference Test Methods 5 and 202. The complete sampling system consisted of a stainless-steel nozzle, glass-lined
probe, pre-weighed quartz filter, coil condenser, un-weighed Teflon filter, gas conditioning train, pump and
calibrated dry gas meter. The gas conditioning train consisted of a coiled condenser and five (5) chilled impingers.
The first, second and third impingers were initially empty, the fourth contained 100 mL of de-ionized water and the
Source Test Report
Testing Methodology
AST-2024-0698 Compass – Ogden, UT Page 3-2
last impinger contained 200-300 grams of silica gel. The un-weighed 90 mm Teflon filter was placed between the
second and third impingers. The probe liner heating system was maintained at a temperature of 248 ±25°F, and the
impinger temperature was maintained at 68°F or less throughout testing. The temperature of the Teflon filter was
maintained greater than 65°F but less than or equal to 85°F.
Following the completion of each test run, the sampling train was leak checked at a vacuum pressure greater than or
equal to the highest vacuum pressure observed during the run. Condensate was collected in the first dry impinger,
therefore the front-half of the sample train (the nozzle, probe, and heated pre-weighed filter) was removed in order
to purge the back-half of the sample train (coil condenser, first and second impingers and CPM filter). A glass
bubbler was inserted into the first impinger. If needed, de-ionized ultra-filtered (DIUF) water was added to the first
impinger to raise the water level above the bubbler, then the coil condenser was replaced. Zero nitrogen was
connected to the condenser, and a 90-minute purge at 14 liters per minute was conducted. After the completion of
the nitrogen purge the impinger contents were measured for moisture gain.
The pre-weighed quartz filter was carefully removed and placed in container 1. The probe, nozzle and front half of
the filter holder were rinsed three (3) and six (6) times with acetone to remove any adhering particulate matter and
these rinses were recovered in container 2. All containers were sealed, labeled and liquid levels marked for
transport to the identified laboratory for filterable particulate matter analysis.
The contents of impingers 1 and 2 were recovered in container CPM Cont. #1. The back half of the filterable PM
filter holder, the coil condenser, impingers 1 and 2 and all connecting glassware were rinsed with DIUF water and
then rinsed with acetone, followed by hexane. The water rinses were added to container CPM Cont. #1 while the
solvent rinses were recovered in container CPM Cont. #2. The Teflon filter was removed from the filter holder and
placed in container CPM Cont. #3. The front half of the condensable PM filter holder was rinsed with DIUF water
and then with acetone, followed by hexane. The water rinse was added to container CPM Cont. #1 while the solvent
rinses were added to container CPM Cont. #2. All containers were sealed, labeled and liquid levels marked for
transport to the identified laboratory for condensable particulate matter analysis.
3.5 Quality Assurance/Quality Control – U.S. EPA Reference Test Method 3/3A
Cylinder calibration gases used met EPA Protocol 1 (+/- 2%) standards. Copies of all calibration gas certificates can
be found in the Quality Assurance/Quality Control Appendix.
Low-Level gas was introduced directly to the analyzer. After adjusting the analyzer to the Low-Level gas
concentration and once the analyzer reading was stable, the analyzer value was recorded. This process was repeated
for the High-Level gas. For the Calibration Error Test, Low, Mid, and High-Level calibration gases were
sequentially introduced directly to the analyzer. All values were within 2.0 percent of the Calibration Span or 0.5%
absolute difference.
At the completion of testing, the data was also saved to the Alliance server. All data was reviewed by the Field
Team Leader before leaving the facility. Once arriving at Alliance’s office, all written and electronic data was
relinquished to the report coordinator and then a final review was performed by the Project Manager.
Appendix A
Appendix A
Example Calculations
Location:
Source:
Project No.:
Run No.:
Parameter:
Meter Pressure (Pm), in. Hg
where,
Pb 25.50 = barometric pressure, in. Hg
ΔH 1.191 = pressure differential of orifice, in H2O
Pm 25.59 = in. Hg
Absolute Stack Gas Pressure (Ps), in. Hg
where,
Pb 25.50 = barometric pressure, in. Hg
Pg -0.30 = static pressure, in. H2O
Ps 25.48 = in. Hg
Standard Meter Volume (Vmstd), dscf
where,
Y 0.995 = meter correction factor
Vm 38.120 = meter volume, cf
Pm 25.59 = absolute meter pressure, in. Hg
Tm 514.5 = absolute meter temperature, oR
Vmstd 33.267 = dscf
Standard Wet Volume (Vwstd), scf
where,
Vlc 124.5 = weight of H2O collected, g
Vwstd 5.871 = scf
Moisture Fraction (BWSsat), dimensionless (theoretical at saturated conditions)
where,
Ts 122.8 = stack temperature, °F
Ps 25.48 = absolute stack gas pressure, in. Hg
BWSsat 0.145 = dimensionless
Moisture Fraction (BWS), dimensionless (measured)
where,
Vwstd 5.871 = standard wet volume, scf
Vmstd 33.267 = standard meter volume, dscf
BWS 0.150 = dimensionless
Moisture Fraction (BWS), dimensionless
where,
BWSsat 0.145 = moisture fraction (theoretical at saturated conditions)
BWSmsd 0.150 = moisture fraction (measured)
BWS 0.145
Compass Minerals - Ogden, UT
Scrubber - AH-513
AST-2024-0064-S
1
PM/CPM
Pm = Pb + Δ H
13.6
Ps = Pb + Pg
13.6
= 17.636 × Y × Vm × Pm
Vwstd = 0.04716 × Vlc
BWSsat = 10 . ,
Ps
BWS = Vwstd
(Vwstd + Vmstd)
BWS = BWSmsd unless BWSsat <BWSmsd
Appendix A
Example Calculations
Location:
Source:
Project No.:
Run No.:
Parameter:
Compass Minerals - Ogden, UT
Scrubber - AH-513
AST-2024-0064-S
1
PM/CPM
Molecular Weight (DRY) (Md), lb/lb-mole
where,
CO2 3.6 = carbon dioxide concentration, %
O2 15.1 = oxygen concentration, %
Md 29.18 = lb/lb mol
Molecular Weight (WET) (Ms), lb/lb-mole
where,
Md 29.18 = molecular weight (DRY), lb/lb mol
BWS 0.145 = moisture fraction, dimensionless
Ms 27.56 = lb/lb mol
Average Velocity (Vs), ft/sec
where,
Cp 0.840 = pitot tube coefficient
Δ P1/2 0.495 = velocity head of stack gas, (in. H2O)1/2
Ts 582.5 = absolute stack temperature, °R
Ps 25.48 = absolute stack gas pressure, in. Hg
Ms 27.56 = molecular weight of stack gas, lb/lb mol
Vs 32.4 = ft/sec
Average Stack Gas Flow at Stack Conditions (Qa), acfm
where,
Vs 32.4 = stack gas velocity, ft/sec
As 14.19 = cross-sectional area of stack, ft2
Qa 27,559 = acfm
Average Stack Gas Flow at Standard Conditions (Qs), dscfm
where,
Qa 27,559 = average stack gas flow at stack conditions, acfm
BWS 0.145 = moisture fraction, dimensionless
Ps 25.48 = absolute stack gas pressure, in. Hg
Ts 582.5 = absolute stack temperature, °R
Qs 18,172 = dscfm
Md = (0.44 × % CO ) + (0.32 × % O2) + (0.28 (100 − % CO − % O2))
Ms = Md (1 − BWS) + 18.015 (BWS)
Qa = 60 × Vs × As
Qs = 17.636 × Qa × (1 − BWS) × Ps
Ts
Vs = 85.49 × Cp × (Δ P / ) avg × Ts
Ps x Ms
Appendix A
Example Calculations
Location:
Source:
Project No.:
Run No.:
Parameter:
Compass Minerals - Ogden, UT
Scrubber - AH-513
AST-2024-0064-S
1
PM/CPM
Dry Gas Meter Calibration Check (Yqa), dimensionless
where,
Y 0.995 = meter correction factor, dimensionless
Θ 60 = run time, min.
Vm 38.120 = total meter volume, dcf
Tm 514.5 = absolute meter temperature, °R
ΔH@ 1.853 = orifice meter calibration coefficient, in. H2O
Pb 25.50 = barometric pressure, in. Hg
ΔH avg 1.191 = average pressure differential of orifice, in H2O
Md 29.18 = molecular weight (DRY), lb/lb mol
(Δ H)1/2 1.065 = average squareroot pressure differential of orifice, (in. H2O)1/2
Yqa 1.2 = percent
Volume of Nozzle (Vn), ft3
where,
Ts 582.5 = absolute stack temperature, °R
Ps 25.48 = absolute stack gas pressure, in. Hg
Vlc 124.5 = volume of H2O collected, ml
Vm 38.120 = meter volume, cf
Pm 25.59 = absolute meter pressure, in. Hg
Y 0.995 = meter correction factor, unitless
Tm 514.5 = absolute meter temperature, oR
Vn 50.721 = volume of nozzle, ft3
Isokinetic Sampling Rate (I), %
where,*
Vn 50.721 = nozzle volume, ft3
θ 60.0 = run time, minutes
An 0.00043 = area of nozzle, ft2
Vs 32.4 = average velocity, ft/sec
I 101.2 = %
Filterable PM2.5 Concentration (Cs), grain/dscf
where,
Mn 67.8 = filterable PM2.5 mass, mg
Vmstd 33.267 = standard meter volume, dscf
Cs 0.00050 = grain/dscf
C =M × 0.0154
Vmstd
Yqa =
Y − Θ
Vm 0.0319 × Tm × 29
Δ @ × Pb + Δ Havg.
13.6 ×
ΔH avg.
× 100
Vn =
0.002669 × +Vm × ×
Appendix A
Example Calculations
Location:
Source:
Project No.:
Run No.:
Parameter:
Compass Minerals - Ogden, UT
Scrubber - AH-513
AST-2024-0064-S
1
PM/CPM
Filterable PM Emission Rate (PMR), lb/hr
where,
Cs 0.00050 = filterable PM2.5 concentration, grain/dscf
Qs 18,172 = average stack gas flow at standard conditions, dscfm
PMR 0.078 = lb/hr
Condensable PM Concentration (CCPM), grain/dscf
where,
MCPM 2.8 = condensable PM mass, mg
Vmstd 33.267 = standard meter volume, dscf
CCPM 0.0013 = grain/dscf
Condensable PM Emission Rate (ERCPM), lb/hr
where,
CCPM 0.0013 = condensable PM concentration, grain/dscf
Qs 18,172 = average stack gas flow at standard conditions, dscfm
ERCPM 0.20 = lb/hr
Total PM2.5 Concentration (CTPM), grain/dscf
where,
Cs 0.00050 = filterable PM2.5 concentration, grain/dscf
CCPM 0.0013 = condensable PM2.5 concentration, grain/dscf
CTPM 0.0018 = grain/dscf
Total PM2.5 Emission Rate (ERTPM), lb/hr
where,
PMR 0.078 = filterable PM2.5 emission rate, lb/hr
ERCPM 0.20 = condensable PM2.5 emission rate, lb/hr
ERTPM 0.28 = lb/hr
PMR = C × Qs × 60
7.0E +03
C =M × 0.0154
Vmstd
ER =
C × Qs × 60
ℎ
7.0E +03
= +
= +
Appendix B
Emission Calculations
Location
Source
Project No.
Parameter
Run Number Run 1 Run 2 Run 3 Average
Date 2/15/24 2/15/24 2/16/24 --
Start Time 13:30 16:40 10:05 --
Stop Time 15:05 17:55 11:19 --
Run Time, min (θ)60.0 60.0 60.0 60.0
Barometric Pressure, in. Hg (Pb)25.50 25.50 25.76 25.59
Meter Correction Factor (Y)0.995 0.995 0.995 0.995
Orifice Calibration Value (ΔH @)1.853 1.853 1.853 1.853
Meter Volume, ft3 (Vm)38.120 38.600 39.101 38.607
Meter Temperature, °F (Tm)54.8 54.0 53.1 54.0
Meter Temperature, °R (Tm)514.5 513.7 512.8 513.7
Meter Orifice Pressure, in. WC (ΔH)1.191 1.191 1.271 1.218
Volume H2O Collected, mL (Vlc)124.5 84.7 94.0 101.1
Nozzle Diameter, in (Dn)0.280 0.280 0.280 0.280
Area of Nozzle, ft2 (An)0.0004 0.0004 0.0004 0.0004
Filterable PM Mass, mg (Mn)67.8 28.7 29.4 42.0
SEM PM2.5 Fraction 1.6 2.3 2.6 2.2
Filterable PM2.5 Mass using SEM Analysis, mg (MFPM2.5)1.08 0.7 0.8 0.8
SEM PM10 Fraction 11.8 15.0 11.0 12.6
Filterable PM10 Mass using SEM Analysis, mg (MFPM10)8.0 4.3 3.2 5.2
Condensable PM Mass, mg (MCPM)2.8 2.1 2.2 2.4
Standard Meter Volume, ft3 (Vmstd)33.267 33.741 34.593 33.867
Standard Water Volume, ft3 (Vwstd)5.871 3.994 4.433 4.766
Moisture Fraction Measured (BWSmsd)0.150 0.106 0.114 0.123
Moisture Fraction @ Saturation (BWSsat)0.145 0.123 0.113 0.127
Moisture Fraction (BWS)0.145 0.106 0.113 0.121
Meter Pressure, in Hg (Pm)25.59 25.59 25.85 25.68
Volume at Nozzle, ft3 (Vn)50.721 48.410 49.332 49.49
Isokinetic Sampling Rate, (%)(I)101.2 99.8 100.4 100.5
DGM Calibration Check Value, (+/- 5%)(Yqa)1.2 2.7 1.4 1.8
Filterable PM2.5 Concentration, grain/dscf (Cs)0.00050 0.00030 0.00034 0.00038
Filterable PM2.5 Emission Rate, lb/hr (PMR2.5)0.078 0.048 0.056 0.061
Filterable PM10 Concentration, grain/dscf (Cs)0.0037 0.0020 0.0014 0.0024
Filterable PM10 Emission Rate, lb/hr (PMR10)0.58 0.32 0.24 0.38
Condensable PM Concentration, grain/dscf (CCPM)0.0013 0.0010 0.0010 0.0011
Condensable PM Emission Rate, lb/hr (ERCPM)0.20 0.15 0.16 0.17
Total PM10 Concentration, grain/dscf (Cs)0.0050 0.0029 0.0024 0.0035
Total PM10 Emission Rate, lb/hr (ERTPM10)0.78 0.47 0.40 0.55
Total PM2.5 Concentration, grain/dscf (CTPM)0.0018 0.0013 0.0013 0.0015
Total PM2.5 Emission Rate, lb/hr (ERTPM)0.28 0.20 0.22 0.23
Compass Minerals - Ogden, UT
Scrubber - AH-513
AST-2024-0064-S
EMISSION CALCULATIONS
ISOKINETIC DATA
INPUT DATA
PM/CPM
Emission Calculations
Location
Source
Project No.
Parameter
Run Number Run 1 Run 2 Run 3 Average
Date 2/15/24 2/15/24 2/16/24 --
Start Time 13:30 16:40 10:05 --
Stop Time 15:05 17:55 11:19 --
Run Time, min 60.0 60.0 60.0 60.0
Point 1 0.44 0.44 0.47 0.45
Point 2 0.45 0.45 0.46 0.45
Point 3 0.46 0.47 0.50 0.48
Point 4 0.48 0.46 0.49 0.48
Point 5 0.44 0.46 0.48 0.46
Point 6 0.42 0.42 0.42 0.42
Point 7 0.34 0.25 0.26 0.28
Point 8 0.24 0.21 0.21 0.22
Point 9 0.18 0.18 0.20 0.19
Point 10 0.17 0.17 0.19 0.18
Point 11 0.17 0.18 0.18 0.18
Point 12 0.17 0.16 0.17 0.17
Point 13 0.18 0.13 0.13 0.15
Point 14 0.20 0.13 0.12 0.15
Point 15 0.22 0.13 0.13 0.16
Point 16 0.24 0.14 0.14 0.17
Point 17 0.26 0.14 0.14 0.18
Point 18 0.22 0.16 0.16 0.18
Point 19 0.18 0.18 0.30 0.22
Point 20 0.15 0.32 0.28 0.25
Point 21 0.15 0.23 0.24 0.21
Point 22 0.15 0.22 0.22 0.20
Point 23 0.14 0.21 0.19 0.18
Point 24 0.13 0.20 0.19 0.17
Square Root of ΔP, (in. WC)1/2 (ΔP)0.495 0.488 0.497 0.493
Pitot Tube Coefficient (Cp)0.840 0.840 0.840 0.840
Barometric Pressure, in. Hg (Pb)25.50 25.50 25.76 25.59
Static Pressure, in. WC (Pg)-0.30 -0.33 -0.32 -0.32
Stack Pressure, in. Hg (Ps)25.48 25.48 25.74 25.56
Stack Cross-sectional Area, ft2 (As)14.19 14.19 14.19 14.19
Temperature, °F (Ts)122.8 116.8 114.2 117.9
Temperature, °R (Ts)582.5 576.5 573.9 577.6
Moisture Fraction Measured (BWSmsd)0.150 0.106 0.114 0.123
Moisture Fraction @ Saturation (BWSsat)0.145 0.123 0.113 0.127
Moisture Fraction (BWS)0.145 0.106 0.113 0.121
O2 Concentration, %(O2)15.07 15.08 15.75 15.30
CO2 Concentration, %(CO2)3.62 3.6 3.2 3.47
Molecular Weight, lb/lb-mole (dry)(Md)29.18 29.18 29.14 29.17
Molecular Weight, lb/lb-mole (wet)(Ms)27.56 28.00 27.88 27.81
Velocity, ft/sec (Vs)32.4 31.5 31.9 31.9
At Stack Conditions, acfm (Qa)27,559 26,829 27,155 27,181
At Standard Conditions, dscfm (Qs)18,172 18,696 19,048 18,639
Compass Minerals - Ogden, UT
Scrubber - AH-513
AST-2024-0064-S
VOLUMETRIC FLOW RATE
CALCULATED DATA
VELOCITY HEAD, in. WC
PM/CPM
Method 1 Data
Location
Source
Project No.
Date:
Vertical
Circular
57.00 in
6.00 in
51.00 in
14.19 ft2
2
4.3 ft
1.0 (must be ≥ 0.5)
10.0 ft
2.4 (must be ≥ 2)
24
24
1
Measurer (Initial and Date):JFT 2/14/24
Reviewer (Initial and Date):TCH 2/14/24
2 3 4 5 6 7 8 9 10 11 12
1 14.6 --6.7 --4.4 --3.2 --2.6 --2.1 1 2.1 1.07 7 1/16
2 85.4 --25.0 --14.6 --10.5 --8.2 --6.7 2 6.7 3.42 9 7/16
3 ----75.0 --29.6 --19.4 --14.6 --11.8 3 11.8 6.02 12
4 ----93.3 --70.4 --32.3 --22.6 --17.7 4 17.7 9.03 15
5 --------85.4 --67.7 --34.2 --25.0 5 25.0 12.75 18 3/4
6 --------95.6 --80.6 --65.8 --35.6 6 35.6 18.16 24 1/8
7 ------------89.5 --77.4 --64.4 7 64.4 32.84 38 7/8
8 ------------96.8 --85.4 --75.0 8 75.0 38.25 44 1/4
9 ----------------91.8 --82.3 9 82.3 41.97 48
10 ----------------97.4 --88.2 10 88.2 44.98 51
11 --------------------93.3 11 93.3 47.58 53 9/16
12 --------------------97.9 12 97.9 49.93 55 15/16
*Percent of stack diameter from inside wall to traverse point.
A =4.3 ft.
B =10 ft.
Depth of Duct =51 in.
Number of traverse points on a diameter
Stack Diagram
Cross Sectional Area
LOCATION OF TRAVERSE POINTS
Traverse
Point
% of
Diameter
Distance
from inside
wall
Distance
from
outside of
port
No. of Test Ports:
Number of Readings per Point:
Distance A:
Distance A Duct Diameters:
Distance B:
Distance B Duct Diameters:
Minimum Number of Traverse Points:
Actual Number of Traverse Points:
CIRCULAR DUCT
Duct Design:
Nipple Length:
Depth of Duct:
Cross Sectional Area of Duct:
Distance from Far Wall to Outside of Port:
Duct Orientation:
Compass Minerals - Ogden, UT
Scrubber - AH-513
AST-2024-0064-S
02/15/24
Stack Parameters
Upstream
Disturbance
Downstream
Disturbance
B
A
Cyclonic Flow Check
Location Compass Minerals - Ogden, UT
Source Scrubber - AH-513
Project No.AST-2024-0064-S
Date 02/15/24
Sample Point Angle (ΔP=0)
1 0
2 5
3 10
4 15
5 15
6 10
7 5
8 5
9 5
10 10
11 10
12 5
13 5
14 5
15 10
16 15
17 10
18 10
19 5
20 5
21 5
22 10
23 15
24 10
Average 8
Method 4 Data
Location
Source
Project No.
Parameter
Analysis
Run 1 Date:2/15/24
Impinger No.1 2 3 4 5 Total
Contents Empty Empty Empty H2O Silica --
Initial Mass, g 483.0 637.2 573.9 733.4 984.1 3411.6
Final Mass, g 574.6 649.7 578.5 738.2 995.1 3536.1
Gain 91.6 12.5 4.6 4.8 11.0 124.5
Run 2 Date:2/15/24
Impinger No.1 2 3 4 5 Total
Contents Empty Empty Empty H2O Silica --
Initial Mass, g 499.2 634.1 643.4 742.9 974.2 3493.8
Final Mass, g 575.4 637.0 643.6 736.9 985.6 3578.5
Gain 76.2 2.9 0.2 -6.0 11.4 84.7
Run 3 Date:2/16/24
Impinger No.1 2 3 4 5 Total
Contents Empty Empty Empty H2O Silica --
Initial Mass, g 483.7 639.2 576.3 736.8 975.7 3411.7
Final Mass, g 555.9 642.9 575.3 740.5 991.1 3505.7
Gain 72.2 3.7 -1.0 3.7 15.4 94.0
Compass Minerals - Ogden, UT
Scrubber - AH-513
AST-2024-0064-S
PM/CPM
Gravimetric
Isokinetic Field Data
Location: Start Time:Source:
Date: VALID End Time:Project No.:AST-2024-0064-S PM/CPM
Moisture:14.5 % est.Est. Tm:60 °F Pb:25.50 in. Hg
Barometric:25.70 in. Hg Est. Ts:140 °F Pg:-0.30 in. WC
Static Press:-0.35 in. WC Est. ΔP:0.26 in. WC O2:15.1 %
Stack Press:25.67 in. Hg Est. Dn:0.304 in.CO2:3.6 %
CO2:3.0 %Target Rate:0.75 scfm Check Pt.Initial Final Corr.
O2:16.0 %LEAK CHECKS Pre Mid 1 Mid 2 Mid 3 Post Mid 1 (cf)--
N2/CO:81.0 %0.840 S-type Leak Rate (cfm):0.002 ------0.000 Mid 2 (cf)--
Md:29.12 lb/lb-mole A3 SS Vacuum (in Hg):15 ------8 Mid 3 (cf)--
Ms:27.51 lb/lb-mole Pitot Tube:Pass ------Pass --
Stack Probe Filter Imp Exit Aux
Amb.Amb.Amb.Amb.Amb.
Begin End 40 Ideal Actual 40 40 40 40
A1 0.00 2.50 0.44 123 2.03 2.00 5 243 250 50 83 98.1 43.27
2 2.50 5.00 0.45 123 2.07 2.10 5 242 251 48 81 100.1 43.76
3 5.00 7.50 0.46 123 2.12 2.10 5 255 254 47 80 99.3 44.24
4 7.50 10.00 0.48 123 2.21 2.20 6 248 252 48 79 100.0 45.19
5 10.00 12.50 0.44 124 2.03 2.00 6 254 254 47 77 100.6 43.30
6 12.50 15.00 0.42 123 1.94 2.00 6 252 255 46 76 99.8 42.27
7 15.00 17.50 0.34 124 1.57 1.60 5 244 253 47 78 105.4 38.07
8 17.50 20.00 0.24 123 1.11 1.10 4 243 254 47 80 104.6 31.95
9 20.00 22.50 0.18 123 0.84 0.84 3 244 253 48 77 101.1 27.67
10 22.50 25.00 0.17 123 0.79 0.80 3 249 254 49 76 104.0 26.89
11 25.00 27.50 0.17 123 0.79 0.80 3 250 254 48 75 103.8 26.89
12 27.50 30.00 0.17 123 0.79 0.80 3 251 255 48 75 101.1 26.89
B1 30.00 32.50 0.18 123 0.84 0.84 3 250 250 47 77 100.0 27.67
2 32.50 35.00 0.20 123 0.93 0.89 3 254 255 47 78 102.3 29.17
3 35.00 37.50 0.22 123 1.02 1.00 3 252 255 46 78 99.7 30.59
4 37.50 40.00 0.24 122 1.11 1.10 3 253 255 46 79 98.7 31.93
5 40.00 42.50 0.26 122 1.21 1.20 3 250 251 46 80 100.4 33.23
6 42.50 45.00 0.22 121 1.02 1.00 3 251 252 46 81 99.6 30.54
7 45.00 47.50 0.18 122 0.84 0.84 3 250 254 46 81 101.2 27.65
8 47.50 50.00 0.15 122 0.70 0.70 3 248 254 46 81 104.5 25.24
9 50.00 52.50 0.15 122 0.70 0.70 3 244 252 45 82 106.9 25.24
10 52.50 55.00 0.15 123 0.69 0.70 3 251 254 45 81 106.2 25.26
11 55.00 57.50 0.14 123 0.65 0.66 3 250 253 45 81 104.9 24.41
12 57.50 60.00 0.13 123 0.60 0.61 3 252 252 45 82 102.3 23.52
Final DGM:
Max
Vac %ISO BWS
60.0 min 38.120 ft3 0.26 in. WC 54.8 °F 122.8 °F 6 1.191 in. WC 101.2 0.145
glass
PR705-2
835.390
836.690
Mid-Point Leak Check Vol (cf):0.280
55
819.850
834.080
55
% ISO
837.930
54
832.800
P-420
Pitot Cp/Type:
809.430 54
55
ΔH @ (in.WC):
Probe ID:
Nozzle ID:
Nozzle Dn (in.):
831.440
Liner Material:
811.530
Pitot
Tube
ΔP
(in WC)
825.330
829.960
815.510
805.130
822.535
807.250
828.340
817.130
Pitot ID:
826.810
823.880
821.210
RE
S
U
L
T
S
839.096
VmRun Time ΔP Tm
1.2
YqaΔHTs
Scrubber - AH-513
STACK DATA (EST)
M5-27
Run 1
13:30
15:05
Compass Minerals - Ogden, UT
STACK DATA (EST)EQUIPMENT MOIST. DATA
Vlc (ml)
124.5
K-FACTOR
STACK DATA (FINAL)FILTER NO.
Parameter:2/15/24
0.995
1.853
Meter Box ID:
Y:
Sa
m
p
l
e
Pt
.
Gas Temperatures (°F)
DGM Average
Amb.
Sample Time
(minutes)
Dry Gas Meter
Reading
(ft3)
56
56
57
57
818.490
53
53
54
803.020
800.976
813.570
55
55
55
56
40
55
55
Vs
(fps)
Pump
Vac
(in. Hg)
Orifice Press.
ΔH
(in. WC)
Gas Temperatures (°F)
54
54
54
54
4.535
54
56
Isokinetic Field Data
Location: Start Time:Source:
Date: VALID End Time:Project No.:AST-2024-0064-S PM/CPM
Moisture:10.6 % est.Est. Tm:55 °F Pb:25.50 in. Hg
Barometric:25.70 in. Hg Est. Ts:123 °F Pg:-0.33 in. WC
Static Press:-0.35 in. WC Est. ΔP:0.26 in. WC O2:15.1 %
Stack Press:25.67 in. Hg Est. Dn:0.298 in.CO2:3.6 %
CO2:3.0 %Target Rate:0.75 scfm Check Pt.Initial Final Corr.
O2:16.0 %LEAK CHECKS Pre Mid 1 Mid 2 Mid 3 Post Mid 1 (cf)--
N2/CO:81.0 %0.840 S-type Leak Rate (cfm):0.004 ------0.000 Mid 2 (cf)--
Md:29.12 lb/lb-mole A3 SS Vacuum (in Hg):15 ------10 Mid 3 (cf)--
Ms:27.94 lb/lb-mole Pitot Tube:Pass ------Pass --
Stack Probe Filter Imp Exit Aux
Amb.Amb.Amb.Amb.Amb.
Begin End --Ideal Actual --------
A1 0.00 2.50 0.44 116 2.20 2.10 5 247 252 58 80 97.4 42.67
2 2.50 5.00 0.45 116 2.25 2.10 5 244 263 57 82 98.4 43.15
3 5.00 7.50 0.47 117 2.35 2.20 5 248 268 59 80 97.7 44.14
4 7.50 10.00 0.46 118 2.29 2.20 5 241 267 59 82 98.4 43.71
5 10.00 12.50 0.46 119 2.29 2.20 5 244 266 60 83 97.6 43.74
6 12.50 15.00 0.42 119 2.09 2.00 5 247 271 60 81 98.6 41.80
7 15.00 17.50 0.25 118 1.25 1.20 4 251 266 61 82 99.3 32.22
8 17.50 20.00 0.21 118 1.05 0.99 3 252 259 61 83 99.5 29.53
9 20.00 22.50 0.18 118 0.90 0.85 3 253 258 58 84 100.3 27.34
10 22.50 25.00 0.17 117 0.86 0.80 3 252 259 58 82 101.6 26.55
11 25.00 27.50 0.18 117 0.91 0.85 3 252 262 57 84 101.6 27.32
12 27.50 30.00 0.16 117 0.81 0.76 3 250 262 56 82 100.9 25.75
B1 30.00 32.50 0.13 114 0.66 0.62 2 250 261 55 84 101.5 23.15
2 32.50 35.00 0.13 114 0.66 0.62 2 252 260 52 85 103.2 23.15
3 35.00 37.50 0.13 114 0.66 0.62 2 253 258 52 84 103.2 23.15
4 37.50 40.00 0.14 115 0.71 0.67 2 254 258 51 82 101.8 24.05
5 40.00 42.50 0.14 116 0.71 0.66 2 255 259 51 81 101.9 24.07
6 42.50 45.00 0.16 116 0.81 0.76 2 252 258 50 80 103.7 25.73
7 45.00 47.50 0.18 117 0.91 0.85 2 251 262 50 82 102.1 27.32
8 47.50 50.00 0.32 117 1.61 1.50 3 251 263 49 83 100.3 36.42
9 50.00 52.50 0.23 117 1.16 1.10 3 252 264 49 82 99.3 30.88
10 52.50 55.00 0.22 118 1.11 1.00 3 253 262 48 79 102.0 30.23
11 55.00 57.50 0.21 118 1.06 0.99 3 255 260 48 81 100.4 29.53
12 57.50 60.00 0.20 118 1.01 0.95 3 254 258 47 79 102.6 28.82
Final DGM:
Max
Vac %ISO BWS
60.0 min 38.600 ft3 0.25 in. WC 54.0 °F 116.8 °F 5 1.191 in. WC 99.8 0.106
MOIST. DATA
Vlc (ml)
84.7
FILTER NO.
Y:
ΔH @ (in.WC):
Probe ID:
0.995
1.853
Liner Material:
Gas Temperatures (°F)
4.98
Pitot ID:
Pitot Cp/Type:
0.280
P-420
Pitot
Tube
ΔP
(in WC)
PR705-2
glass
Orifice Press.
ΔH
(in. WC)
DGM Average
Amb.
--
RE
S
U
L
T
S
Run Time
2.7
Vm ΔH Yqa
Pump
Vac
(in. Hg)
Gas Temperatures (°F)
53
53
52
54
TsTm
54
55
16:40
K-FACTOR
16443-c
STACK DATA (EST)
Dry Gas Meter
Reading
(ft3)
EQUIPMENT
Scrubber - AH-513
Vs
(fps)
Compass Minerals - Ogden, UT
2/15/24
STACK DATA (EST)
M5-27
Sample Time
(minutes)
Nozzle Dn (in.):
% ISO
Nozzle ID:
17:55
STACK DATA (FINAL)
Mid-Point Leak Check Vol (cf):
Run 2 Parameter:
Meter Box ID:
Sa
m
p
l
e
Pt
.
ΔP
878.066
876.550
52
52
52
855.490
853.990
56
54
839.466
852.360
848.110
850.270
841.580
845.930
843.740
871.880
875.030
873.450
54
52
54
56
55
54
54
54
55
55
56
55
55
856.890
859.690
861.020
862.230
858.270
865.950
863.460
864.690
867.210
868.580
870.010
Isokinetic Field Data
Location: Start Time:Source:
Date: VALID End Time:Project No.:AST-2024-0064-S PM/CPM
Moisture:11.3 % est.Est. Tm:54 °F Pb:25.76 in. Hg
Barometric:25.70 in. Hg Est. Ts:117 °F Pg:-0.32 in. WC
Static Press:-0.35 in. WC Est. ΔP:0.25 in. WC O2:15.8 %
Stack Press:25.67 in. Hg Est. Dn:0.301 in.CO2:3.2 %
CO2:3.0 %Target Rate:0.75 scfm Check Pt.Initial Final Corr.
O2:16.0 %LEAK CHECKS Pre Mid 1 Mid 2 Mid 3 Post Mid 1 (cf)--
N2/CO:81.0 %0.840 S-type Leak Rate (cfm):0.001 ------0.000 Mid 2 (cf)--
Md:29.12 lb/lb-mole A3 SS Vacuum (in Hg):15 ------9 Mid 3 (cf)--
Ms:27.86 lb/lb-mole Pitot Tube:Pass ------Pass --
Stack Probe Filter Imp Exit Aux
Amb.Amb.Amb.Amb.Amb.
Begin End --Ideal Actual --------
A1 0.00 2.50 0.47 115 2.31 2.20 6 250 250 44 65 102.0 44.13
2 2.50 5.00 0.46 113 2.27 2.20 6 247 247 45 69 102.9 43.58
3 5.00 7.50 0.50 114 2.46 2.40 7 249 240 45 68 101.0 45.47
4 7.50 10.00 0.49 114 2.42 2.40 7 249 240 45 68 99.2 45.02
5 10.00 12.50 0.48 113 2.37 2.30 7 251 242 46 67 99.2 44.51
6 12.50 15.00 0.42 114 2.07 2.00 6 249 241 46 70 98.7 41.68
7 15.00 17.50 0.26 115 1.28 1.30 5 252 249 46 71 104.7 32.82
8 17.50 20.00 0.21 115 1.04 1.00 4 249 246 47 71 100.5 29.49
9 20.00 22.50 0.20 115 0.99 0.97 4 251 251 47 72 102.3 28.78
10 22.50 25.00 0.19 114 0.94 0.92 4 249 245 47 75 98.8 28.03
11 25.00 27.50 0.18 115 0.90 0.88 4 250 248 48 78 101.2 27.31
12 27.50 30.00 0.17 114 0.85 0.83 4 249 246 48 82 98.4 26.51
B1 30.00 32.50 0.13 114 0.65 0.64 3 254 245 45 68 99.9 23.19
2 32.50 35.00 0.12 115 0.60 0.59 3 247 248 46 69 98.4 22.30
3 35.00 37.50 0.13 115 0.65 0.64 3 246 244 46 70 99.6 23.21
4 37.50 40.00 0.14 114 0.70 0.69 3 249 244 46 71 97.9 24.06
5 40.00 42.50 0.14 115 0.70 0.69 3 251 242 47 71 99.0 24.08
6 42.50 45.00 0.16 113 0.80 0.79 4 252 245 48 72 102.5 25.70
7 45.00 47.50 0.30 114 1.50 1.50 5 255 243 48 75 97.7 35.22
8 47.50 50.00 0.28 114 1.40 1.40 5 251 240 48 77 102.6 34.03
9 50.00 52.50 0.24 115 1.20 1.20 5 250 244 50 79 100.0 31.53
10 52.50 55.00 0.22 114 1.10 1.10 5 250 243 50 81 100.5 30.16
11 55.00 57.50 0.19 114 0.95 0.93 4 248 244 51 78 102.2 28.03
12 57.50 60.00 0.19 113 0.96 0.93 4 245 244 51 75 98.3 28.01
Final DGM:
Max
Vac %ISO BWS
60.0 min 39.101 ft3 0.26 in. WC 53.1 °F 114.2 °F 7 1.271 in. WC 100.4 0.113
RE
S
U
L
T
S
Run Time
56
56
55
655.515
55
55
57
57
56
56
57
1.4
ΔHVm YqaΔPTmTs
616.414
631.530
629.795
625.490
627.720
623.240
633.030
620.930
651.075
11:19
K-FACTOR
MOIST. DATA
Vlc (ml)
94.0
Scrubber - AH-513
16420-c
STACK DATA (EST)
Parameter:
10:05Compass Minerals - Ogden, UT
2/16/24 Run 3
STACK DATA (EST)
M5-27
Nozzle ID:
Nozzle Dn (in.):
Sa
m
p
l
e
Pt
.
Sample Time
(minutes)
Dry Gas Meter
Reading
(ft3)--
0.280
EQUIPMENT
Meter Box ID:
Y:
ΔH @ (in.WC):
Probe ID:
Liner Material:
Pitot ID:
Pitot Cp/Type:
0.995
DGM Average
Amb.
Pitot
Tube
ΔP
(in WC)
Pump
Vac
(in. Hg)
STACK DATA (FINAL)
4.954
FILTER NO.
Mid-Point Leak Check Vol (cf):
55
% ISO
54
Vs
(fps)
Orifice Press.
ΔH
(in. WC)
Gas Temperatures (°F)
49
Gas Temperatures (°F)
PR705-2
1.853
glass
P-420
51
48
51
49
50
50
50
654.100
652.630
53
647.680
649.465
618.670
50
54
51
643.350
644.570
640.965
645.920
634.520
639.845
642.145
638.662
637.330
635.925
Appendix C
Project No. AST-2024-0698
Alliance Technical Group, LLC
Analytical Services
5530 Marshall St.
Arvada, CO 80002
(720) 457-9504
www.alliancetg.com
Analytical Laboratory Report
Compass Minerals - Ogden
765 N 10500 W
Ogden, UT 84404
1 of 22
Quality Assurance Associate
Date
Certification Statement
Alliance Source Testing, LLC (AST) has completed the analysis as described in this report. Results
apply only to the source(s) tested and operating condition(s) for the specific test date(s) and
time(s) identified within this report. All results are intended to be considered in their entirety,
and AST is not responsible for use of less than the complete test report without written consent.
This report shall not be reproduced in full or in part without written approval from the customer.
To the best of my knowledge and abilities, all information, facts and test data are correct.
Data presented in this report has been checked for completeness and is accurate, error-free
and legible. Any deviations or problems are detailed in the relevant sections on the test report.
This document was prepared in portable document format (.pdf) and contains pages as
identified in the bottom footer of this document.
Validation Signature
The analytical data and all QC contained within this report was reviewed and validated by the
following individual.
James Davidson
2 of 22
Digitally signed by James Davidson
DN: C=US, CN=James Davidson, E=james.davidson@stacktest.com
Reason: I am the author of this document
Location: your signing location here
Date: 2024.03.06 16:15:13-06'00'
Foxit PDF Editor Version: 11.2.7
James Davidson
Project Narrative
Analytical Method(s):
Method 5 - Determination of Particulate Matter Emissions From Stationary Sources
Method 202 - Dry Impinger Method for Determining Condensable Particulate Matter
Emissions From Stationary Sources
Filterable The filter(s) were either oven dried and/or desiccated per the method until a final
weight was obtained. The liquid fractions were extracted if required, evaporated and
cooled until a final weight was obtained. These fractions were summed together to
provide the total Particulate Matter collected.
Condensable The filter(s) were extracted per the method. The organic extract was added to the
organic rinse, and the inorganic extract was added to the inorganic rinse. The
inorganic fraction was extracted with solvent per the method. Extracts were combined
with the organic rinse. The organic and inorganic fractions were evaporated and
desiccated until a final weight was obtained.
MDL The Minimum Detection Level (MDL) is 0.5 mg per fraction. If the measured result for a
fraction is less than the MDL, the MDL was used in ensuing calculations.
Blank Correction If blank correction is performed, only blank values returned higher than the MDL are
used. If a blank returns a value less than the MDL, no correction is included. Method
202 Recovery Blank corrections are applied by fraction (inorganic subtracted from
inorganic; organic subtracted from organic).
Custody:The samples were received by Ryan Gillett on 2/22/24 in Arvada, CO. The samples
were received in good condition with proper Chain-of-Custody documentation. No
apparent container problems were noted upon receipt. Prior to analysis, the samples
were kept secure with access limited to authorized personnel of AST.
Number of Samples:23 (2 on Hold)
Labeling: Acceptable
Analyst:Jake Schmitt - Laboratory Analyst I
Eric Grosjean - Technical Director
Equipment:Mettler Toledo Balance ML-104, SN B217893065. This scale was used for analytical
determinations of filters and rinse vessels.
Denver Instruments Balance TB-6201, SN 17904189. This scale was used to measure the
total mass of rinse collected for blank correction.
Analysis was performed on the same balance as the associated tare.
Quincy Lab Inc oven, 30CG, SN G3-012673.
Lab Reagents:Acetone Lot Number: 224521
Hexane Lot Number: 224540
QC Notes:The samples met the minimum criteria established by the relevant method.
A blank correction was applied per the method.
3 of 22
Client
City, State
Project No.
Method
Lab ID
Field ID
Filter ID 15588 - C 16443 - C 16420 - C
Filter Tare Weight, g
Date - Desiccator
Time - Desiccator
Date of Weighing 2/26/24 2/26/24 2/23/24 2/26/24 2/23/24 2/26/24
Time of Weighing 4:56 15:20 14:25 4:56 14:25 4:56
Filter Weight, g 0.5279 0.5276 0.5376 0.5374 0.5422 0.5420
Filter PM Mass, mg*
Lab ID
Field ID
Beaker ID
Beaker tare, g
Beaker with Acetone, g
Acetone Mass, g
Date - Desiccator
Time - Desiccator
Date of Weighing 2/26/24 2/26/24 2/26/24 2/26/24 2/26/24 2/27/24
Time of Weighing 5:01 11:37 5:01 11:37 11:37 5:23
Weight, g 4.1528 4.1531 4.1263 4.1267 4.1569 4.1569
Rinse PM Mass, mg*
Blank Corrected
Total PM Mass, mg
*All fractions were analyzed and returned values greater than the MDL of 0.5 mg.
M5/202 - AH-513 Scrubber - Run 1 Cont. 1 M5/202 - AH-513 Scrubber - Run 2 Cont. 1 M5/202 - AH-513 Scrubber - Run 3 Cont. 1
Compass Minerals - Ogden
Ogden, UT 84404
AST-2024-0698
EPA Method 5
Front Half Filter
D40370 D40375 D40380
13:55 13:55 13:55
2/22/24 2/22/24 2/22/24
62.5 25.6 25.8
Front Half Rinse
M5/202 - AH-513 Scrubber - Run 1 Cont. 2 M5/202 - AH-513 Scrubber - Run 2 Cont. 2 M5/202 - AH-513 Scrubber - Run 3 Cont. 2
32867 32871 32888
D40371 D40376 D40381
4.1477 4.1234 4.1533
97.9 91.6 108.9
12:51
93.8 87.5 104.7
2/23/24 2/23/24 2/23/24
67.8 28.7 29.4
0.4653 0.5119 0.5164
5.3 3.1 3.6
No
12:51 12:51
4 of 22
Client
City, State
Project No.
Method
Lab ID
Field ID
Beaker ID
Beaker tare, g
Beaker with Acetone, g
Acetone Mass, g
Date - Desiccator
Time - Desiccator
Date of Weighing 2/26/24 2/26/24
Time of Weighing 5:01 11:37
Weight, g 4.1526 4.1529
Blank Mass, mg*
Compass Minerals - Ogden
148.25
M5 Acetone Blank
32850
0.0
12:51
144.10
2/23/24
4.1527
D40385
Acetone Blank
EPA Method 5
AST-2024-0698
Ogden, UT 84404
5 of 22
Client
City, State
Project No.
Method
Lab ID
Field ID
Lab ID
Field ID
Beaker ID
Beaker tare, g
Beaker Solvent, g
Solvent Mass, g
Date - Desiccator
Time - Desiccator
Date of Weighing 2/26/24 2/26/24 2/26/24 2/26/24 2/26/24 2/26/24
Time of Weighing 5:08 11:57 5:08 11:57 5:08 11:57
Weight, g 3.9374 3.9377 3.9414 3.9416 3.9422 3.9424
Organic PM Mass, mg*
Lab ID
Field ID
Beaker ID
Beaker tare, g
Beaker Water, g
Water Mass, g
Date - Desiccator
Time - Desiccator
Date of Weighing 2/27/24 2/28/24 2/26/24 2/26/24 2/26/24 2/27/24
Time of Weighing 13:33 5:01 5:16 11:49 11:49 5:30
Weight, g 49.7941 49.7945 81.6311 81.6315 86.3998 86.3999
Inorganic Mass, mg*
Blank Corrected
Total PM Mass, mg
*All fractions were analyzed and returned values greater than the MDL of 0.5 mg.
D40374 D40379 D40384
D40373 D40378 D40383
Inorganic Fraction
3.9359 3.9399 3.9405
M5/202 - AH-513 Scrubber - Run 1 Cont. 5 M5/202 - AH-513 Scrubber - Run 2 Cont. 5 M5/202 - AH-513 Scrubber - Run 3 Cont. 5
32903 32910 32930
437.1 255.6 252.7
M5/202 - AH-513 Scrubber - Run 1 Cont. 4 M5/202 - AH-513 Scrubber - Run 2 Cont. 4 M5/202 - AH-513 Scrubber - Run 3 Cont. 4
31766 31752
49.7912 81.6289 86.3974
337.2486.9 339.1
2.4
Yes
255.9 128.9 223.0
31586
252.0 125.0 219.1
1.7 1.7 1.8
2/23/24
Organic Fraction
Compass Minerals - Ogden
2/26/24 2/23/24 2/23/24
7:25 15:10 15:10
3.1 2.4
M5/202 - AH-513 Scrubber - Run 1 Cont. 3 M5/202 - AH-513 Scrubber - Run 2 Cont. 3 M5/202 - AH-513 Scrubber - Run 3 Cont. 3
Ogden, UT 84404
AST-2024-0698
EPA Method 202
Teflon Filter
D40372 D40377 D40382
2/23/24 2/23/24
15:37 15:37 15:37
2.8 2.1 2.2
6 of 22
Client
City, State
Project No.
Method
Lab ID
Field ID
Lab ID
Field ID
Beaker ID
Beaker tare, g
Beaker Solvent, g
Solvent Mass, g
Date - Desiccator
Time - Desiccator
Date of Weighing 2/26/24 2/26/24 2/26/24 2/26/24
Time of Weighing 5:08 11:57 5:08 11:57
Weight, g 3.9175 3.9173 3.8752 3.8753
Organic Mass, mg*
Lab ID
Field ID
Beaker ID
Beaker tare, g
Beaker Water g
Water Mass, g
Date - Desiccator
Time - Desiccator
Date of Weighing 2/26/24 2/26/24 2/26/24 2/26/24
Time of Weighing 5:16 11:49 5:16 11:49
Weight, g 66.3589 66.3592 75.4776 75.4779
Inorganic Mass, mg*
D40390 D40387
D40389 D40386
32899 32935
M202 - FT Proof Recovery Blank Cont. 5 M202 - FT Proof Blank Cont. 5
133.3 119.6
3.8729
2/23/24 2/23/24
129.4 115.7
3.9162
15:37 15:37
M202 - FT Proof Recovery Blank Cont. 4 M202 - FT Proof Blank Cont. 4
Field Train Blank Proof Blank
1.2 2.0
Inorganic Fraction Blanks
Compass Minerals - Ogden
Ogden, UT 84404
AST-2024-0698
EPA Method 202
Field Train Blank
Teflon Filter Blanks
Organic Fraction Blanks
M202 - FT Proof Recovery Blank Cont. 3 N/A
Field Train Blank Proof Blank
N/A
Proof Blank
D40388
1.1 1.4
31747
66.3579 75.4764
31761
235.0 265.3
15:10 15:10
2/23/24 2/23/24
168.6 189.8
7 of 22
8 of 22
9 of 22
10 of 22
11 of 22
12 of 22
13 of 22
14 of 22
15 of 22
16 of 22
17 of 22
18 of 22
19 of 22
20 of 22
21 of 22
This is the last page of the report.
22 of 22
Appendix D
Method 3/3A Data
Location
Source
Project No.
Date/Time 2/15/24 10:30 Date/Time 2/15/24 10:30
Make/Model/SN Servomex 4900 100269 Servomex 4900 100269
Parameter Cylinder ID Cylinder
Concentration, %
Analyzer
Concentration, %Cylinder ID Cylinder
Concentration, %
Analyzer
Concentration, %
Zero Gas 0.00 0.01 0.00 0.01
High Range Gas CC764364 23.98 24.01 CC764364 23.9 23.87
Mid Range Gas RR02538 11.00 11.00 RR02538 10.9 11.16
Concentration Span, %
Required Accuracy, %
Run No.
Analysis Date/Time 2/15/2024 R1 2/15/2024 R2 2/16/2024 R3
Parameter O2 %CO2 %O2 %CO2 %O2 %CO2 %
Analysis #1 15.02 3.66 15.05 3.60 15.76 3.30
Analysis #2 15.06 3.63 15.09 3.61 15.77 3.20
Analysis #3 15.14 3.58 15.11 3.59 15.72 3.10
Average 15.1 3.6 15.1 3.6 15.8 3.2
Date/Time 2/16/24 8:00 Date/Time 2/16/24 8:00
Make/Model/SN Servomex 4900 100269 Servomex 4900 100269
Parameter Cylinder ID Cylinder
Concentration, %
Analyzer
Concentration, %Cylinder ID Cylinder
Concentration, %
Analyzer
Concentration, %
Zero Gas 0.00 0.00 0.00 0.05
High Range Gas CC764364 23.98 10.99 CC764364 23.90 11.02
Mid Range Gas RR02538 11.00 24.00 RR02538 10.90 23.98
Concentration Span, %
Required Accuracy, %
The remaining consistuent is assumed to be nitrogen.
Run 1 Run 2 Run 3
Compass Minerals - Ogden, UT
Scrubber - AH-513
AST-2024-0064-S
0.48 0.48
24.0
O2 Data CO2 Data
23.9
24.0 23.9
0.48 0.48
Balance
Red Ball Technical Gas Service
555 Craig Kennedy Way
Shreveport, LA 71107
800-551-8150
Accreditation #62754 PGVP Vendor ID # G12023
EPA PROTOCOL GAS CERTIFICATE OF ANALYSIS
Cylinder Number:CC764364 Certification Date:09/21/2023
Product ID Number:127907 Expiration Date:09/19/2031
Cylinder Pressure:1900 PSIG MFG Facility: - Shreveport - LA
COA #CC764364.20230830-0 Lot Number:CC764364.20230830
Customer PO. NO.:Tracking Number:108811898
Customer:Previous Certification Dates:
This calibration standard has been certified per the May 2012 EPA Traceability Protocol, Document EPA-600/R-12/531,
using procedure G2.
Do Not Use This Cylinder Below 100 psig (0.7 Megapascal).
Certified Concentration(s)
Component Concentration Uncertainty Analytical Principle Assayed On
Carbon Dioxide 23.9 %±0.2 %FTIR 09/21/2023
Oxygen 23.98 %±0.04 %MPA 09/14/2023
Nitrogen
Analytical Measurement Data Available Online.
Reference Standard(s)
Serial Number Lot Expiration Type Balance Component Concentration Uncertainty(%)NIST Reference
CC737012 CC737012.20230228 07/09/2031 GMIS N2 O2 20 %0.112 SRM 2659a
EB0022021 EB0022021.20180323 07/15/2026 GMIS N2 CO2 14.9 %0.777 101001
Analytical Instrumentation SMART-CERT
Component Principle Make MPC Date
O2 MPA Thermo 09/13/2023
CO2 FTIR MKS 09/21/2023
Serial
1162980025
017146467
This is to certify the gases referenced have been calibrated/tested, and verified to meet the defined specifications. This
calibration/test was performed using Gases or Scales that are traceable through National Institute of Standards and
Technology (NIST) to the International System of Units (SI). The basis of compliance stated is a comparison of the
measurement parameters to the specified or required calibration/testing process. The expanded uncertainties use a coverage
factor of k=2 to approximate the 95% confidence level of the measurement, unless otherwise noted. This calibration certificate
applies only to the item described and shall not be reproduced other than in full, without written approval from Red Ball
Technical Gas Services. If not included, the uncertainty of calibrations are available upon request and were taken into account
when determining pass or fail.
Timothy Davis
Analytical Chemist
Assay Laboratory: Red Ball TGS
Version 02-J, Revised on 2018-09-17
Model
410i
MKS 2031DJG2EKVS13T
Balance
Red Ball Technical Gas Service
555 Craig Kennedy Way
Shreveport, LA 71107
800-551-8150
Accreditation #62754 PGVP Vendor ID # G12023
EPA PROTOCOL GAS CERTIFICATE OF ANALYSIS
Cylinder Number:RR02538 Certification Date:09/21/2023
Product ID Number:125371 Expiration Date:09/19/2031
Cylinder Pressure:1900 PSIG MFG Facility: - Shreveport - LA
COA #RR02538.20230831-0 Lot Number:RR02538.20230831
Customer PO. NO.:Tracking Number:103925725
Customer:Previous Certification Dates:
This calibration standard has been certified per the May 2012 EPA Traceability Protocol, Document EPA-600/R-12/531,
using procedure G1.
Do Not Use This Cylinder Below 100 psig (0.7 Megapascal).
Certified Concentration(s)
Component Concentration Uncertainty Analytical Principle Assayed On
Carbon Dioxide 10.9 %±0.11 %FTIR 09/21/2023
Oxygen 11.00 %±0.03 %MPA 09/18/2023
Nitrogen
Analytical Measurement Data Available Online.
Reference Standard(s)
Serial Number Lot Expiration Type Balance Component Concentration Uncertainty(%)NIST Reference
CC737012 CC737012.20230228 07/09/2031 GMIS N2 O2 20 %0.112 SRM 2659a
EB0022021 EB0022021.20180323 07/15/2026 GMIS N2 CO2 14.9 %0.777 101001
Analytical Instrumentation SMART-CERT
Component Principle Make MPC Date
O2 MPA Thermo 09/18/2023
CO2 FTIR MKS 09/21/2023
Serial
1162980025
017146467
This is to certify the gases referenced have been calibrated/tested, and verified to meet the defined specifications. This
calibration/test was performed using Gases or Scales that are traceable through National Institute of Standards and
Technology (NIST) to the International System of Units (SI). The basis of compliance stated is a comparison of the
measurement parameters to the specified or required calibration/testing process. The expanded uncertainties use a coverage
factor of k=2 to approximate the 95% confidence level of the measurement, unless otherwise noted. This calibration certificate
applies only to the item described and shall not be reproduced other than in full, without written approval from Red Ball
Technical Gas Services. If not included, the uncertainty of calibrations are available upon request and were taken into account
when determining pass or fail.
Jasmine Godfrey
Analytical Chemist
Assay Laboratory: Red Ball TGS
Version 02-J, Revised on 2018-09-17
Model
410i
MKS 2031DJG2EKVS13T
QA/QC Data
Location
Source
Project No.
Parameter
#1 #2 #3 Dn (Average)Difference
2/15/24 A3 0.280 0.280 0.280 0.280 0.000 SS
2/15/24 P-420 no no no
Date Probe or
Thermocouple ID
Reference
Temp. (°F)
Indicated
Temp. (°F)Difference Criteria Probe Length
2/15/24 PR705-2 250.0 250.0 0.0%6 '
Date 02/15/24
Balance ID:5A2001026
Certified Weight ID:SLC-1KG-3
Certified Weight (g):1000.0
Measured Weight (g):999.8
Weight Difference (g):0.2 ----------
2/15/24 Weather Station No No No
2/15/24 M5-27
ACETONE 230620 Fisher
HEXANES 194731 Fisher
DI 232650 Fisher
Flow Rate (lpm):14 Flow Rate (lpm):14 Flow Rate (lpm):14
Clock Time Temperature Clock Time Temperature Clock Time Temperature
15:15 78.0 18:15 77.0 11:45 75.0 *1.5hr Purge Times*
-78.0 --77.0 --75.0
-78.0 --77.0 --75.0
-78.0 --76.0 --75.0
16:45 78.0 19:45 76.0 13:15 75.0
Compass Minerals - Ogden, UT
Scrubber - AH-513
AST-2024-0064-S
Nozzle Diameter (in.)
Date Nozzle ID Criteria
PM/CPM
Material
Date Meter Box ID Positive Pressure Leak Check
Pass
≤ 0.004 in.
Date Pitot ID Evidence of
damage?
Weather Station Location
OGDEN AIRPORT
Evidence of
mis-alignment?
Calibration or
Repair required?
Field Balance Check
Posttest Purge
Run 1 Run 2 Run 3
± 1.5 % (absolute)
Reagent ByDateField LotField Prep
performedLot#
Date Barometric
Pressure
Evidence of
damage?Reading Verified Calibration or
Repair required?
Document ID 620.004
Revision 23.0
Effective Date 1/25/23
Issuing Department Page 1 of 1
Console ID:
Meter S/N:20035543
Critical Orifice S/N:
(PbI)
(PbF)
(Pb)
(Y)1330-31 1330-31 1330-25 1330-25 1330-19 1330-19
(K')0.8429 0.8429 0.6728 0.673 0.5186 0.519
(VP)13.0 13.0 15.0 15.0 17.0 17.0
Initial DGM Volume, ft3 (VmI)501.924 512.781 528.098 536.765 548.287 555.093
Final DGM Volume, ft3 (VmF)512.781 523.688 536.765 545.420 555.093 561.889
Total DGM Volume, ft3 (Vm)10.857 10.907 8.667 8.655 6.806 6.796
Ambient Temperature, °F (Ta)64 64 63 63 63 63
Initial DGM Temperature, °F (TmI)63 63 64 65 64 64
Final DGM Temperature, °F (TmF)63 64 65 64 64 65
Average DGM Temperature, °F ( Tm)63 64 65 65 64 65
Elapsed Time (Θ)10.00 10.00 10.00 10.00 10.00 10.00
Meter Orifice Pressure, in. WC (ΔH)3.20 3.20 2.10 2.10 1.30 1.30
Standard Meter volume, ft3 (Vmstd)9.2720 9.3058 7.3570 7.3468 5.7693 5.7553
Standard Critical Orifice Volume, ft3 (Vcr)9.2341 9.2341 7.3777 7.3777 5.6868 5.6868
Meter Correction Factor (Y)0.996 0.992 1.003 1.004 0.986 0.988
Tolerance --0.001 0.003 0.008 0.009 0.009 0.007
Orifice Calibration Value (ΔH @)1.803 1.801 1.842 1.842 1.917 1.915
Tolerance --0.051 0.052 0.011 0.011 0.063 0.062
Orifice Cal Check --
Meter Correction Factor (Y)
Orifice Calibration Value (ΔH @)
Accuracy Difference
oF oR oF oR %oF
0 460 2 462 -0.4 2
68 528 69 529 -0.2 1
100 560 102 562 -0.4 2
223 683 225 685 -0.3 2
248 708 250 710 -0.3 2
273 733 274 734 -0.1 1
300 760 301 761 -0.1 1
400 860 401 861 -0.1 1
500 960 501 961 -0.1 1
600 1,060 600 1,060 0.0 0
700 1,160 700 1,160 0.0 0
800 1,260 800 1,260 0.0 0
900 1,360 900 1,360 0.0 0
1,000 1,460 999 1,459 0.1 1
1,100 1,560 1,100 1,560 0.0 0
1,200 1,660 1,199 1,659 0.1 1
Calibration Date:
0.94 1.68 1.66
DGM Calibration-Orifices
Tech Services
25.07
25.07
25.07
K' Factor, ft3·R1/2 / in. WC·min
CL23A
Vacuum Pressure, in. Hg
Initial Barometric Pressure, in. Hg
Final Barometric Pressure, in. Hg
Average Barometric Pressure, in. Hg
Critifcal Orifice ID
Calibration Detail
M5-27
1330
Positive Pressure Leak Check
Equipment Detail - Dry Gas Meter
0.995
1.853
Yes
Personnel
Reference Calibrator Make:
Reference Calibrator Model:
Reference Calibrator S/N:
Calibration Detail
Equipment Detail - Thermocouple Sensor
Reference Temp.Display Temp.
OMEGA
T-197207
Stacey CunninghamReviewed By:
RYAN LYONSCalibration By:
2/2/2024
Appendix E
AH513 Compliance Testing
Run 1 Run 2 Run 3 Average
Start 02/15/2024 13:30 02/15/2024 16:40 02/16/2024 10:05 -
Stop 02/15/2024 15:05 02/15/2024 17:55 02/16/2024 11:19 -
Duration (min)60 60 60 -
Fan Water (gpm).FT513 94.8 93.8 102.4 97.0
Spray Water (gpm).FT513B 35.0 32.6 37.1 34.9
Scrubber Water (gpm).FT513T 129.9 126.3 139.5 131.9
Fan Speed (rpm)AH513_RPM 1344.1 1344.1 1344.1 1344.1
Wet Salt (tph).W501 106.8 106.2 108.8 107.3
Throughput (tph).W503 121.4 120.5 120.4 120.7
Last Page of Report