Loading...
HomeMy WebLinkAboutDDW-2025-009491Sanitary Survey - Deficiency Report PWS Number:UTAH05010 Deficiency Points:50 Survey Date:09/16/2025 Survey Name:ROSS SPRINGS WATER SYSTEM Surveyor:Hunter Payne Sanitary Survey Category: DS SDWIS Severity Code: Significant Deficiency Distribution | DS001 | UTAH05010 DISTRIBUTION SYSTEM 45A. Open end of vent line covered with #14 mesh screen Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be provided with a #14 mesh, non-corrodible screen and a downward elbow, and where possible, be extended to at least one foot above grade. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Several air release valve vents within the treatment plant were not covered with mesh. The mesh was replaced during the survey. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: D004 AIR RELIEF VALVE PIPE LACKS NO. 14 SCREEN Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | ROSS SPRINGS #1 STORAGE 75C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:The tank lid is not properly gasketed. Recommend installing a new gasket to provide a complete seal. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME