HomeMy WebLinkAboutDDW-2025-009491Sanitary Survey - Deficiency Report
PWS Number:UTAH05010 Deficiency Points:50 Survey Date:09/16/2025
Survey Name:ROSS SPRINGS WATER
SYSTEM
Surveyor:Hunter Payne
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH05010 DISTRIBUTION SYSTEM
45A. Open end of vent line covered with #14 mesh screen
Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be
provided with a #14 mesh, non-corrodible screen and a downward elbow, and where
possible, be extended to at least one foot above grade. This significant deficiency must
be corrected within 120 days of notification or have a corrective action plan approved
by DDW.
Notes:Several air release valve vents within the treatment plant were not covered with mesh. The
mesh was replaced during the survey.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D004 AIR RELIEF VALVE PIPE LACKS NO. 14 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | ROSS SPRINGS #1 STORAGE
75C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:The tank lid is not properly gasketed. Recommend installing a new gasket to provide a
complete seal.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME