Loading...
HomeMy WebLinkAboutDDW-2025-009485Sanitary Survey - Deficiency Report PWS Number:UTAH05017 Deficiency Points:65 Survey Date:09/16/2025 Survey Name:GREENDALE AND BOOTLEG CAMPGROUNDS Surveyor:Hunter Payne Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | STORAGE FACILITY ST001 76C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Tank lid not completely sealed with gasket. Recommend installing new gasket for a complete seal. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST002 | STORAGE FACILITY ST002 96A. Overflow line discharges at least 12 inches above ground or the flood rim of receiving basin? Rule: R309-545-13 Rule requires all water storage tanks to be provided with an overflow that discharges at an elevation between 12 and 24 inches above the ground surface or the rim of the receiving basin. Notes:The overflow discharge is overgrown and sediment has built up beneath it to the degree that it no longer has an adequate air gap. Recommend digging out the air gap beneath the overflow. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V011 END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12 AND 24 INCHES FROM GROUND SURFACE Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Treatment - Chlorination General | TP001 | GREENDALE WTP 141. Solution tanks and tank refilling line entry points are properly labeled to identify the chemicals Rule: R309-525-11(8)(c)(vii)Rule requires tanks to be properly labeled to designate the chemical contained. Notes:Solution tanks were not labeled. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TG03 SOLUTION TANKS AND CHEMICAL REFILL LINES NOT LABELED