HomeMy WebLinkAboutDDW-2025-009361Sanitary Survey - Deficiency Report
PWS Number:UTAH02070 Deficiency Points:25 Survey Date:09/03/2025
Survey Name:BEAR RIVER WCD-
TREMONTON BOOSTER
STATION
Surveyor:Dixon Ekins
Sanitary Survey Category: PU
SDWIS Severity Code: Significant Deficiency
Pump Stations | PF001 | BOOSTER STATION
57. If the pump station is used to pressurize the distribution system, does it have at least two functioning pumping units? ... if yes, answer the
following question(s)
Rule: R309-540-5(4)(b)Rule states inline booster pumps, withdrawing water directly from distribution lines
without storage and feeding water directly into distribution lines, shall have at least two
pumping units. This significant deficiency must be corrected within 120 days of
notification or have a corrective action plan approved by DDW.
Notes:No
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: PS18 IN-LINE BOOSTER PUMP STATION LACKS REDUNDANCY TO MEET PEAK
DEMAND WITH ONE PUMP OUT OF SERVICE