Loading...
HomeMy WebLinkAboutDDW-2025-009361Sanitary Survey - Deficiency Report PWS Number:UTAH02070 Deficiency Points:25 Survey Date:09/03/2025 Survey Name:BEAR RIVER WCD- TREMONTON BOOSTER STATION Surveyor:Dixon Ekins Sanitary Survey Category: PU SDWIS Severity Code: Significant Deficiency Pump Stations | PF001 | BOOSTER STATION 57. If the pump station is used to pressurize the distribution system, does it have at least two functioning pumping units? ... if yes, answer the following question(s) Rule: R309-540-5(4)(b)Rule states inline booster pumps, withdrawing water directly from distribution lines without storage and feeding water directly into distribution lines, shall have at least two pumping units. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:No Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: PS18 IN-LINE BOOSTER PUMP STATION LACKS REDUNDANCY TO MEET PEAK DEMAND WITH ONE PUMP OUT OF SERVICE