Loading...
HomeMy WebLinkAboutDDW-2025-008996Sanitary Survey - Deficiency Report PWS Number:UTAH21019 Deficiency Points:15 Survey Date:08/27/2025 Survey Name:OAK SPRINGS HIGHWAY REST STOP Surveyor:Brian Pattee Sanitary Survey Category: SM SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH21019 DISTRIBUTION SYSTEM 40. Does the water system have records of on-going enforcement activities? (test history, enforcement activities, hazard assessments) Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program that includes test history and documentation of on-going enforcement activities. Notes:System Needs to have Plumbing Code required Backflow Preventer on landscape irrigation system , Recommend same Installation as Shingle Creek Rest area . Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M007 CCC-LACKS ON-GOING ENFORCEMENT IMPLEMENTATION