HomeMy WebLinkAboutDDW-2025-008934Sanitary Survey - Deficiency Report
PWS Number:UTAH02013 Deficiency Points:30 Survey Date:09/18/2025
Survey Name:PLYMOUTH TOWN WATER
SYSTEM
Surveyor:Cameron Draney
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Wells | WS006 | CITY WELL #2
128. Hose connections are equipped with a backflow prevention device
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes test history and documentation of on-going enforcement activities.
Notes:Hose bib without a vacuum breaker observed.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M007 CCC-LACKS ON-GOING ENFORCEMENT IMPLEMENTATION
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Liquid Hypochlorination | TP003 | CITY WELL 2 CHLORINATOR
239. There are adequate spill containment provisions for acid and caustic liquids.
Rule: R309-525-11(6)(a)(iv)(B), R309-525-
11(8)(b)(viii)
Rule requires liquid chemical storage tanks to have an overflow and receiving basin or
drain capable of receiving accidental spills or overflows, and meeting all the
requirements of R309-525-23.
Notes:Containment basin needed.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR
OVERFLOWS