HomeMy WebLinkAboutDDW-2025-008882Sanitary Survey - Deficiency Report
PWS Number:UTAH26002 Deficiency Points:180 Survey Date:09/03/2025
Survey Name:CENTER CREEK WATER
SYSTEM
Surveyor:Melissa Noble
Sanitary Survey Category: SM
SDWIS Severity Code: Significant Deficiency
Management and Operations | DS001 | UTAH26002 DISTRIBUTION SYSTEM
23. There are no undocumented drinking water facilities (i.e. tanks, pump stations, treatment facilities, etc.) or recent modifications that have not
gone through or in process of DDW review [LIST UNDOCUMENTED FACILITIES OR DESCRIBE MODIFICATIONS, IF APPLICABLE]
[undocumented sources are covered in a different question]
Rule: R309-100-5(2), R309-500-6, R309-500-9,
R309-500-9(2) and (3)
Rule requires complete plans & specification for all public drinking water projects to
be approved in writing by the Director. Any facility found that has not started DDW
review shall be considered unapproved. This significant deficiency must be corrected
within 120 days of notification or have a corrective action plan approved by DDW.
Notes:Treatment Plan within Well house
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: G001 UNAPPROVED FACILITY IN SERVICE
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Management and Operations | DS001 | UTAH26002 DISTRIBUTION SYSTEM
27C. The interconnection has been approved by DDW.
Rule: R309-550-9(3)Interconnections between different drinking water systems must be reviewed and
approved by the Director. This significant deficiency must be corrected within 120 days
of notification or have a corrective action plan approved by DDW.
Notes:There is no documentation of the consecutive connection with the Division.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: M025 UNAPPROVED INTERCONNECTION WITH ANOTHER WATER SYSTEM
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH26002 DISTRIBUTION SYSTEM
38. Documentation of personnel trained to manage the program (ALL COMUNITY WATER SYSTEMS REQUIRE A DDW CERTIFIED CCC
PROGRAM ADMINISTRATOR. ALL OTHER WATER SYSTEMS REQUIRE AT A MINIMUM BACKFLOW 101 OR EQUIVALENT/
GREATER CCC TRAINING)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes an operator with adequate training in the area of cross connection control
or backflow prevention.
Notes:operator lack CCC training, he let it lapse possibly on accident.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M005 CCC-LACKS OPERATOR TRAINING
Sanitary Survey Category: DS
SDWIS Severity Code: Recommendation
Distribution | DS001 | UTAH26002 DISTRIBUTION SYSTEM
46. Water system has a program to maintain, operate, or control the use of fire hydrants.
Rule: N/A Fire hydrants provide a direct access to the water in the distribution system. In order
to protect the quality and integrity of the water, fire hydrant access should be
controlled.
Notes:the county tests them
Deficiency Points: 0
Days until points become effective on IPS: 0
SDWIS Deficiency Description: D012 FIRE HYDRANT USE POLICY INADEQUATE
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | SPRING NO 1 (E)
66. Is a spring collection box present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box
to permit spring inspection and testing.
Notes:exception granted
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS002 | SPRING NO 2 (W)
81. Is a spring collection box present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box
to permit spring inspection and testing.
Notes:no spring box
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS002 | SPRING NO 2 (W)
82. Is a spring box vent present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect
to venting. Therefore, a junction or collection box requires a vent to be fitted with #14
mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or
covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the
entrance of contaminants, be located and sized to avoid blockage during winter, and
have the end of the vent discharge a minimum of 24 inches above the earth on buried
structures.
Notes:no vent present
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS003 | SPRING NO. 3
96. Is a spring collection box present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box
to permit spring inspection and testing.
Notes:This facility has not been developed
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS004 | CHURCH FARM WELL
107. Water level is measured and recorded periodically
Rule: R309-515-6(12)(e ), R309-515-6(12)(c)(vi)Rule requires provisions be made to permit periodic measurement of water levels in the
completed well.
Notes:no means to measure water level
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S015 WELL LACKS A MEANS TO MEASURE WATER LEVELS PERIODICALLY
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS004 | CHURCH FARM WELL
118C. Air vacuum relief valve on well discharge piping has at least 6 inches of clearance above floor
Rule: R309-515-6(12)(d)(v)Rule requires the exhaust/relief piping on an air release/vacuum relief valve on the well
discharge piping to be at least 6 inches above the well house floor. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:an inch or two of clearance from the ground
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S030 END OF AIR RELEASE VACUUM RELIEF VALVE PIPING LACKS A CLEARANCE
OF AT LEAST 6 INCHES
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Liquid Hypochlorination | TP004 | CHURCH FARM WELL CHLORINATOR
194. There are adequate spill containment provisions for acid and caustic liquids.
Rule: R309-525-11(6)(a)(iv)(B), R309-525-
11(8)(b)(viii)
Rule requires liquid chemical storage tanks to have an overflow and receiving basin or
drain capable of receiving accidental spills or overflows, and meeting all the
requirements of R309-525-23.
Notes:secondary containment is missing
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR
OVERFLOWS