PRODUCT PIPING INTEGRITY TESTING
Facility Name: Salt Lake City Cemetery Owner: Salt Lake Public Utilities
Address: 200 North N Street Address: 1530 West Temple
City, State, Zip: Salt Lake City, Utah 84103 City, State, Zip: Salt Lake City, Utah 84115
Facility I.D.#: 4000842 Phone #: 801-535-6904
Testing Company: Westech Phone #: 801-266-2545 Date: 9/11/2025
This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester.
Tank Number 1 2
Product Stored RUL DSL
Piping Run Only Only
Piping Type FRP FRP
Test Pressure (PSI) 50 50
Test Duration (minutes) 30 30
Leak Rate (GPH) 0.002 0.002
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Taber DeHart, UT-0394
RUL DSL
RULDSL
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
MECHANICAL AND ELECTRONIC LINE LEAK DETECTOR PERFORMANCE TESTS
Facility Name: Salt Lake City Cemetery Owner: Salt Lake Public Utilities
Address: 200 North N Street Address: 1530 West Temple
City, State, Zip: Salt Lake City, Utah 84103 City, State, Zip: Salt Lake City, Utah 84115
Facility I.D.#: 4000842 Phone #: 801-535-6904
Testing Company: Westech Phone #: 801-266-2545 Date: 9/11/2025
Line Number
Leak Detector Manufacturer
☐MLLD
☒ELLD
☐MLLD
☒ELLD
☐MLLD
☐ELLD
☐MLLD
☐ELLD
MLLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG)
STP full operating pressure
Check valve holding pressure
Line resiliency (ml) (line bleedback volume as measured
from check valve holding pressure to 0 psig)
metering pressure before going to full operating pressure as
pressure for at least 60 seconds when the simulated leak is
☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Does the leak detector reset (trip) when the line pressure is
bled off to zero psig? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Does STP properly clycle on/off under normal fuel system
operating conditions? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
A "No" answer to any of the above questions indicates that the MLLD fails the test.
ELLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG)
STP full operating pressure 31 32
How many test cycles are observed before alarm/shutdown
occurs? 1 1
☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
A "No" answer to the above question indicates that the ELLD fails the test.
Does the simulated leak cause an STP shutdown? ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature Taber DeHart
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name: Salt Lake City Cemetery Owner: Salt Lake Public Utilities
Address: 200 North N Street Address: 1530 West Temple
City, State, Zip: Salt Lake City, Utah 84103 City, State, Zip: Salt Lake City, Utah 84115
Facility I.D.#: 4000842 Phone #: 801-535-6904
Testing Company: Westech Phone #: 801-266-2545 Date: 9/11/2025
This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection
procedure. This procedure is applicable to tank monitor stems that touch the bottom of the tank when in place.
Tank Number 1 2
Product Stored RUL DSL
ATG Brand and Model TLS-350 TLS-350
1. Tank Volume, gallons 6,215 6,215
2. Tank Diameter, inches 90.75 90.75
☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
76.5 76.5
corresponds with the value programmed in the ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
1 1
corresponds with the value programmed in the ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Taber DeHart, UT-0394
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
LIQUID SENSER FUNCTIONALITY TESTING
Facility Name: Salt Lake City Cemetery Owner: Salt Lake Public Utilities
Address: 200 North N Street Address: 1530 West Temple
City, State, Zip: Salt Lake City, Utah 84103 City, State, Zip: Salt Lake City, Utah 84115
Facility I.D.#: 4000842 Phone #: 801-535-6904
Westech 801-266-2545 9/11/2025
Sensor Location L-1 INT L-2 INT L-3 STP L-4 STP L-5 UDC
Product Stored DSL RUL DSL RUL RUL/DSL
Type of Sensor
☐Discriminating
☒ Non-Discrimi-
☐Discriminating
☒ Non-Discrimi-
☐Discriminating
☒ Non-Discrimi-
☐Discriminating
☒ Non-Discrimi-
☐Discriminating
☒ Non-Discrimi-
☐Discriminating ☐ Non-Discrimi-
☐Discriminating ☐ Non-Discrimi-
Test Liquid ☒ Water ☐ Product
☒ Water ☐ Product
☒ Water ☐ Product
☒ Water ☐ Product
☒ Water ☐ Product
☐ Water ☐ Product
☐ Water ☐ Product
Is the ATG Console clear of any active or
recurring warnings or alarms regarding
the leak sensor? If the sensor is in alarm ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
Any “No” answers indicate the sensor fails the test.
Test Results: ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail
Taber DeHart, UT-0394 Taber DeHart
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
SPILL BUCKET INTEGRITY TESTING HYDROSTATIC TEST METHOD
SINGLE- AND DOUBLE-WALLED VACUUM TEST METHOD
Salt Lake City Cemetery Salt Lake Public Utilities
200 North N Street 1530 West Temple
Salt Lake City, Utah 84103 Salt Lake City, Utah 84115
4000842 801-535-6904
Westech 801-266-2545 9/11/2025
5-Gallon 5-Gallon
Construction ☐Double-walled ☒☐Double-walled ☒☐Double-walled ☐☐Double-walled ☐
Test Type
☒☐Vacuum ☐Double-walled ☐
☒☐Vacuum ☐Double-walled ☐
☐☐Vacuum ☐Double-walled ☐
☐☐Vacuum ☐Double-walled ☐
Spill Bucket Type ☒Product ☐☒Product ☐☐Product ☐☐Product ☐
☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
parts or separation of the bucket from ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No
Tank Riser cap included in test? ☒☐☐☒☐☐☐☐☐☐☐☐
Drain valve included in test? ☐Yes ☐No ☒☐Yes ☐No ☒☐Yes ☐No ☐☐Yes ☐No ☐
Starting Level
Test Start Time
Test End Time
Test Period
Level Change
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Taber DeHart, UT-0394
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054