HomeMy WebLinkAboutDDW-2025-008654System Number 12002
1.1 Indoor Water Use
Number of residential connections - - - - - - - - - - -- - - - - - - - - - - - - - - - - - -647
Number of other connections - - - 19 ERCs of other connections 20.0
Total Equivalent Residential Connections (ERCs)667.0
gpd/ERC Total (gpm)Gallons/ERC Total (gallons)
800 370.6 400 266,800
1.2 Outdoor Water Use
Is the drinking water used for outdoor irrigation?
Residential ERCs using drinking water for irrigation 647
Percentage of Residential ERCs using DW for irrigation 100%Map Zones
Average irrigated acreage per residential connection - - - - - - - - - - - - > > >0.10 1
Total irrigated acreage of other connections (park, school, etc.)10.00 2
Irrigation zone 3 3
4
5
6
gpd/ERC Total (gpm)Gallons/ERC Total (gallons)
488 253.2 253 188,842
1.3 Fire Flow Water Use
Does the water system provide fire protection?
Maximum fire flow demand (in gpm) for water system or pressure zone 1,000
Maximum fire suppression duration (in hours) for water system or pressure zone 1
Required Fire Suppression Storage (in gallons) - - - - - - - - - - - - - - - - -60,000
2. Summary of Water System Capacity Requirements
gpd/ERC Total (gpm)Gallons/ERC Total (gallons)
1,288 623.8 653 515,642
2.1 Does this system have adequate source capacity (per R309-510-7)?
Required Source Capacity 623.8 gpm
Existing Source Capacity 840.0 gpm
Source Capacity Deficit None gpm
Existing % of Total Req'd 134.7%
Division of Drinking Water — Water System Capacity Calculation Sheet (Last Update 3/30/2017)
*Enter the green cells only*
equals to water use of 55 homes.)
MIN. REQUIREMENTS FOR IRRIGATION USE
System Name Mona Town
(*Verify req'd fire flow and duration with local fire code officials.* Enter notes
here, e.g. fire official contact info or comments.)
(Enter notes here regarding whether and what %
of irrigation water is supplied by PWS.)
Source (indoor + outdoor)Storage (indoor + outdoor + fire)
This source capacity assessment is a general overall system calculation. It may not reflect the variations in individual areas or pressure zones.
Yes No
Yes No
Enter number of non-residential connections, e.g., 2 industrial connections.
Convert "Number of other connections" (Cell E9) to ERCs here. [ERCs of other connections = peak day demand of other connections in gal per day / 800 gpd]
Enter estimated irrigated acre per here.
Enter total irrigated acres of other connections here.
Enter fire flow in gpm.
Enter duration in hours.
from the pick list. See "Irrigation Demands & Map" tab on the bottom of the screen or WaterLink.
Less than 100% indicates: (1) additional source capacity is needed, and
Source deficit indicates that: (1) additional source capacity is needed,
Mona Capacity 2025 Page 1 of 2 9/11/2025
2.2 Does this system have adequate storage capacity (per R309-510-8)?
Total Required Storage 515,642 gal
Existing Storage Capacity 1,600,000 gal
Storage Capacity Deficit None gal
Required Fire Storage 60,000 gal
Not
Applicable
Existing % of Total Req'd 310.3%
3. Transient PWS Indoor Water Use — ERC Calcuation (See R309-510, Tables 510-1, 2, & 4 for other facility types.)
GPD/person*GPD/site or pad Gallons/person Gallon/site
or pad ERC/site or pad Total # of ERCs
60 0 30 0 0.00 0.0
20 0 10 0 0.00 0.0
5 0 2.5 0 0.00 0.0
N/A 100 N/A 50 0.13 0.0
Number of people per camp site
Source
(GPD/vehicle)
Storage
(Gal./vehicle)
ERC/1000
vehicles served
Vehicles
served/day ERCs
7 3.5 8.8 0.0
4. Data Input for Calculating ERCs, Source and Storage 4.2 Summary - Existing Sources (enter in green cells below)
Total Existing Source Capacity (in gpm)840
4.1 Projected ERCs Calculation (optional)WS001 Clover Spring 240
Total Projected ERCs 0 WS002 Well #1 600
Existing Residential Connections 0
Obligated Future ERCs (enter below)0
Maximum ERCs (assuming indoor use only)1512
4.3 Summary - Existing Storage Tanks (enter below)
Total Existing Storage Cap. (in gallons)1,600,000
ST001 250K Tank 250,000
ST003 350 K Tank 350,000
ST004 1MG Tank 1,000,000
Notes" tab on the bottom of the screen.)
RV Park
Facility Type
Modern Recreation Camp
Semi-Developed Camp w/ flush toilets
Roadway Rest Stop w/ flushometer valves
Semi-Developed Camp w/o flush toilets
This storage capacity assessment is a general overall system calculation. It may not reflect the variations in individual areas or pressure zones.
Is storage deficiency solely
to fire storage?
Autolink to 4.3 "Total Existing Storage Capcity" cell below.
If applicable, enter number of people per camp site here.
Storage deficit indicates that: (1) additional storage volume is needed, and (2) storage deficiency should be assessed.
Cell I8 ("Number of residential connections") on Page 1 to calculate PROJECTED demand & req'ts (including both existing & future connections).
pressure tanks shall NOT be considered effective storage volume for (1) community systems, or (2) NTNC with significant demand UNLESS an exception has been granted.
Autolink to 2 "Total Storage" cell above.
number in cell I8 or cell I9 on Page 1.
If NO, answer one of question set 2.01 to 2.05 in ESS.If YES, answer one of question set 2.06 to 2.10 in ESS.
Less than 100% indicates: (1) additional storage capacity is needed, and (2) storage deficiency should be assessed.
Mona Capacity 2025 Page 2 of 2 9/11/2025