HomeMy WebLinkAboutDDW-2025-008370DDW IPS <ddwips@utah.gov>
FW: [EXT] Re: Significant Deficiencies Due Next Month #15004
1 message
Tyler J Wood <tjwood@parker.com>Wed, Sep 3
To: "ddwips@utah.gov" <ddwips@utah.gov>Cc: "paulspens@gmail.com" <paulspens@gmail.com>, Tyler Wood <twood201067@gmail.com>
Hi Jen
We have taken care of all three of these issues.
A cap with small hole was placed over the vent hole in cabinet as suggested. Picture attached.
A #14 or less mesh screen has been placed around the vent. Picture attached.
A UV resistant sealant has been applied to the wellhead fixture. completely sealing it from outside contaminants. This seal will be inspected semiannually for degradation and replaced as nece
attached.
Thank you
On Fri, Aug 1, 2025, 10:02 AM DDW IPS <ddwips@utah.gov> wrote:
On May 1, 2025, a sanitary survey was conducted on Central Enterprise Water Co, revealing three significant deficiencies. Our records indicate that all of these signdeficiencies remain unresolved.
ST001 STORAGE FACILITY ST001 A 0 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending
V005
STORAGE FACILITY
VENT NOT
DOWNTURNED AT
LEAST 2 INCHES
BELOW ANY OPENING
SIG
The vent contained within the cupboard is not
downturned and is used as a opening to place a SCADA
sensor. To resolve this deficiency, this vent needs to
rendered not a vent by closing the opening and
preventing debris from entering the tank. Staff advises
the water system to consider placing a fernco cap on top
of the vent, with a slight puncture to allow the SCADA
sensor to enter.
05/01/2025 25
WS003 SUMMER RIDGE WELL A 5 Hide Details ( 3 )
Code Description Severity Comments Determined
Date Pending
S013
WELL LACKS THE
REQUIRED WELL
SEAL
SIG
Sanitary seal on wellhead has degraded and is no longer
sealing the entire wellhead. To resolve this deficiency the
sanitary seal needs to be replaced.
05/01/2025 50
S006
END OF WELL CASING
VENT LACKS NO. 14
SCREEN
SIG
Current vent is not a #14 mesh or finer non-corrodible
screen. To resolve this deficiency replace the plastic cap
with a #14 mesh or finer non-corrodible screen.
05/01/2025 25
If these issues have already been addressed, kindly provide detailed documentation outlining the corrective actions taken, along with any supporting photographic e
The system was granted 120 days to rectify these deficiencies, with the deadline set for September 4, 2025. If additional time is required to complete the necessaryplease follow this link to request a Corrective Action Plan.
Your prompt attention to this matter is greatly appreciated.
Thanks,
Jen-
--
Jennifer Yee
IPS Rule Manager
Environmental Scientist | Division of DrinkingWater
M: (385) 515-1501
drinkingwater.utah.gov
(801) 536-4200
Emails to and from this email address may be considered public records and thus subject to Utah GRAMA
requirements.
"PLEASE NOTE: The preceding information may be confidential or privileged. It only should be used or disseminated for the purpose of conducting business with Parker. If you are not an inte
please notify the sender by replying to this message and then delete the information from your system. Thank you for your cooperation. Parker Hannifin Corporation and its subsidiaries, affiliaassociated companies ("Parker") process personal data in accordance with Parker’s Personal Data Privacy Policy which may be accessed from www.parker.com"