Loading...
HomeMy WebLinkAboutDDW-2025-008270Sanitary Survey - Deficiency Report PWS Number:UTAH26043 Deficiency Points:150 Survey Date:08/14/2025 Survey Name:OAK HAVEN WATER COMPANY Surveyor:Danielle Zebelean Sanitary Survey Category: SM SDWIS Severity Code: Recommendation Management and Operations | DS001 | UTAH26043 DISTRIBUTION SYSTEM 31. Does your water system have an Emergency Response Plan? Rule: R309-105-18 All suppliers are advised to develop contingency plans to cope with possible emergency situations. In many areas of the state the possibility of earthquake damage shall be realistically considered. Notes: Deficiency Points: 0 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M001 NO CURRENT EMERGENCY RESPONSE PROGRAM Sanitary Survey Category: SM SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH26043 DISTRIBUTION SYSTEM 36. Legally adopted authority statement Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program that includes a legally adopted and functional local authority to enforce the program (i.e., ordinance, bylaw, or policy). Notes:Did not have Cross Connection Program information at the survey Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M003 CCC-LACKS LOCAL AUTHORITY Sanitary Survey Category: SM SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH26043 DISTRIBUTION SYSTEM 39. Does the water system have detailed records of cross connection control activities? (inventories of backflow assemblies, devices, and air gaps installed within the system) Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program that includes written records of cross connection control activities. Notes:Did not have Cross Connection Program information at the survey Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M006 CCC-LACKS WRITTEN RECORDS OF CCC ACTIVITIES Sanitary Survey Category: SM SDWIS Severity Code: Minor Deficiency Cross Connection and Operator Certification | DS001 | UTAH26043 DISTRIBUTION SYSTEM 40. Does the water system have records of on-going enforcement activities? (test history, enforcement activities, hazard assessments) Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program that includes test history and documentation of on-going enforcement activities. Notes:Did not have Cross Connection Program information at the survey Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M007 CCC-LACKS ON-GOING ENFORCEMENT IMPLEMENTATION Sanitary Survey Category: OC SDWIS Severity Code: Significant Deficiency Cross Connection and Operator Certification | DS001 | UTAH26043 DISTRIBUTION SYSTEM 41. Operator meets required level of certification for water system. ( IF NO CERTIFIED OPERATOR IS REQUIRED MARK COMPLIANT ) Rule: R309-105-11, R309-300-5(3)Rule requires every community and NTNC water system and public water systems that utilize treatment/filtration to have at least one operator certified at the classified grade of the water system. Certification must be appropriate for the type of system operated (treatment and/or distribution). This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Need to have a treatment level 1 certificate. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: C001 SYSTEM DIRECT RESPONSIBLE CHARGE OPERATORS NOT CERTIFIED AT THE REQUIRED LEVEL Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | UPPER TANK 85C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Gasket was missing in a few places. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST002 | MIDDLE TANK 99. Are access openings present? ... if yes, answer the following question(s) Rule: R309-545-14 and 14(1)Rule requires drinking water storage tanks to be designed with reasonably convenient access to the interior for cleaning and maintenance. Notes: Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: VL03 STORAGE TANK LACKS AN ACCESS OPENING LOCATED ABOVE THE LEVEL OF THE OVERFLOW FOR TANK O&M Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST003 | LOWER TANK 118A. Mild deterioration or spalling? Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls that shall also exclude birds, animals, insects, and excessive dust. Notes:Cracks still apparent on roof of tank Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE DETERIORATION