HomeMy WebLinkAboutDDW-2025-008264Sanitary Survey - Deficiency Report
PWS Number:UTAH26022 Deficiency Points:175 Survey Date:07/30/2025
Survey Name:CAMP CLOUD RIM Surveyor:Rebecca Yoo
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | STORAGE FACILITY ST001
60C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:gasket needs repair
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | STORAGE FACILITY ST001
65A. Mild deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust.
Notes:corrosion
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE
DETERIORATION
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | STORAGE FACILITY ST001
66B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:overflow line was not covered with mesh
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN
Sanitary Survey Category: MR
SDWIS Severity Code: Significant Deficiency
Treatment - General | TP001 | JUDGE LAKE WTP
85. Daily operating records reflect chemical dosages and total quantities used
Rule: R309-105-14(3)(a)Rule requires all water system using chemical addition or specialized equipment for the
treatment of drinking water to regularly complete operational reports. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:daily chem dosages not calculated
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TG20 DAILY RECORDS DO NOT REFLECT DOSAGES ACCURATELY
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Treatment - General | TP001 | JUDGE LAKE WTP
88. Does water system have a DEQ/DWQ (UPDES permit) discharge permit for the proper disposal of treatment plant waste to land or water?
Rule: R309-105-6 R309-105-6
Notes:treatment plant discharge does not have discharge permit
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TGR3 TRIGGER FOR UNDOCUMENTED SYSTEM FACILITY OR PROCESS
Sanitary Survey Category: MR
SDWIS Severity Code: Significant Deficiency
Treatment - Chlorination General | TP001 | JUDGE LAKE WTP
115. Daily operating records reflect chemical dosages and total quantities used
Rule: R309-105-14(3)(a)Rule requires all water system using chemical addition or specialized equipment for the
treatment of drinking water to regularly complete operational reports. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:daily chemical quantitates used not calculated
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TG20 DAILY RECORDS DO NOT REFLECT DOSAGES ACCURATELY
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Liquid Hypochlorination | TP001 | JUDGE LAKE WTP
122. Records are kept to minimize the use of decayed hypochlorite solution
Rule: R309-520-7(3)(b)Rule requires the water system to provide an operational means, such as keeping
records of the delivery date of the hypochlorite solution, to avoid the injection of
significantly decayed hypochlorite solutions.
Notes:Record of hypochlorite age not kept
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD68 NO RECORDS KEPT TO MINIMIZE USE OF DECAYED HYPOCHLORITE SOLUTION
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Filtration - General | TP001 | JUDGE LAKE WTP
135. Is backwash flow rate verified to determine it meets minimum requirements?
Rule: R309-525-15(7)Rule requires that backwash systems be designed and operated to
provide for adequate backwash with minimum media loss.
Notes:backwash flow rate is not verified
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: T076 INADEQUATE WATER SUPPLY OR FLOW RATE TO MEET FILTER BACKWASH
NEEDS
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Dual-Media (also called Rapid Sand) - Filtration | TP001 | JUDGE LAKE WTP
138. Filter media is evaluated to verify it meets the manufacturer's specifications for depth and effective media size?
Rule: R309-525-15(4)R309-525-15(4)
Notes:filter media needs to be evaluated. references to JV were provided in a follow up email
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: T033 MEDIA DEPTHS NOT MEETING REQUIREMENTS