HomeMy WebLinkAboutDDW-2025-008138Sanitary Survey - Deficiency Report
PWS Number:UTAH26020 Deficiency Points:45 Survey Date:08/08/2025
Survey Name:MILL HOLLOW
CAMPGROUND
Surveyor:Matt Hinckley
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | MILL HOLLOW SPRING
59. Area of equal or higher elevation within 50 feet of spring collection devices is fenced.
Rule: R309-515-7(7)(e)Rule requires a stock-tight fence around the spring collection area.
Notes:Spring collection area is not fenced.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS02 SPRING COLLECTION AREA NOT FENCED
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | MILL HOLLOW SPRING
61B. Overflow has a minimum of 12 inch clearance above flood rim of receiving basin
Rule: R309-515-7(7)(d), R309-545 Overflow pipes on junction and collection boxes shall comply with R309-545 and
discharge a minimum of 12 inches above the ground surface or rim of the receiving
basin. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:Spring overflow lacks 12 inches of clearance above flood rim of receiving basin.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS14 SPRING BOX OVERFLOW OR DRAIN LACKS FREE FALL OF 12 TO 24 INCHES
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | MILL HOLLOW SPRING
69. Spring has a permanent flow-measuring device.
Rule: R309-515-7(7)(h)Rule requires a spring to have a permanent flow measuring device.
Notes:Spring lacks permanent flow-measuring device.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS01 LACKS A PERMANENT DEVICE FOR MEASURING SPRING FLOW