Loading...
HomeMy WebLinkAboutDDW-2025-008103Sanitary Survey - Deficiency Report PWS Number:UTAH05022 Deficiency Points:10 Survey Date:08/26/2025 Survey Name:LUCERNE VALLEY CAMPGROUND Surveyor:Nathan Hall Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | WELL #1 69. Well discharge line has a check valve. Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. Notes:Could not see a check valve, existing deficiency on IPS report. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S024 NO CHECK VALVE ON WELL DISCHARGE PIPING Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS002 | WELL #2 91. Well discharge line has a check valve. Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. Notes:Could not see a check valve, existing deficiency on IPS report. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S024 NO CHECK VALVE ON WELL DISCHARGE PIPING