HomeMy WebLinkAboutDDW-2025-007679Sanitary Survey - Deficiency Report
PWS Number:UTAH13038 Deficiency Points:30 Survey Date:07/09/2025
Survey Name:KANE COUNTY WCD -
JOHNSON CANYON
Surveyor:Luke Treutel
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP003 | JOHNSON CANYON WELL 2 CHLORINATOR
228. Exhaust fan takes suction near the floor as far as practical from the door and air inlet, and discharges outside away from air inlets.
Rule: R309-520-7(2)(d)(iii)Rule requires a chlorine room exhaust fan to take suction inside the chlorine room near
the floor, as far as practical from the door and air inlet, and discharge air outside of the
building away from air inlets.
Notes:Johnson Canyon Well 2 Chlorinator lacks exhaust fan.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD09 CHLORINE ROOM EXHAUST FAN SUCTION NOT LOCATED NEAR FLOOR
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP003 | JOHNSON CANYON WELL 2 CHLORINATOR
229. Air inlets are located near the ceiling and fitted with louvers.
Rule: R309-520-7(2)(d)(iv)Rule requires chlorine room air inlets to be through wall louvers near the ceiling.
Notes:Johnson Canyon Well 2 Chlorinator lacks air inlet near ceiling.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD10 CHLORINE ROOM AIR INLET NOT LOCATED NEAR CEILING THROUGH WALL
LOUVERS