HomeMy WebLinkAboutDDW-2025-007586Sanitary Survey - Deficiency Report
PWS Number:UTAH20017 Deficiency Points:45 Survey Date:07/16/2025
Survey Name:FERRON RESERVOIR
CAMPGROUND
Surveyor:Sitara Federico
Sanitary Survey Category: SM
SDWIS Severity Code: Recommendation
Management and Operations | DS001 | UTAH20017 DISTRIBUTION SYSTEM
31. Does your water system have an Emergency Response Plan?
Rule: R309-105-18 All suppliers are advised to develop contingency plans to cope with possible emergency
situations. In many areas of the state the possibility of earthquake damage shall be
realistically considered.
Notes:
Deficiency Points: 0
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M001 NO CURRENT EMERGENCY RESPONSE PROGRAM
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | SPRING #1
58. Area of equal or higher elevation within 50 feet of spring collection devices is fenced.
Rule: R309-515-7(7)(e)Rule requires a stock-tight fence around the spring collection area.
Notes:No fence or exception for not having a fence
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS02 SPRING COLLECTION AREA NOT FENCED
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | SPRING #1
66. Is a spring collection box present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box
to permit spring inspection and testing.
Notes:Still deficient per last sanitary survey
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | FIBERGLASS TANK
81A. Overflow line discharges at least 12 inches above ground or the flood rim of receiving basin?
Rule: R309-545-13 Rule requires all water storage tanks to be provided with an overflow that discharges at
an elevation between 12 and 24 inches above the ground surface or the rim of the
receiving basin.
Notes:Not 12 inches above ground
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V011 END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12
AND 24 INCHES FROM GROUND SURFACE