HomeMy WebLinkAboutDDW-2025-007334Sanitary Survey - Deficiency Report
PWS Number:UTAH14056 Deficiency Points:60 Survey Date:08/04/2025
Survey Name:FOOL CREEK CULINARY
WATER COMPANY
Surveyor:Joshua Owens
Sanitary Survey Category: SM
SDWIS Severity Code: Recommendation
Management and Operations | DS001 | UTAH14056 DISTRIBUTION SYSTEM
31. Does your water system have an Emergency Response Plan?
Rule: R309-105-18 All suppliers are advised to develop contingency plans to cope with possible emergency
situations. In many areas of the state the possibility of earthquake damage shall be
realistically considered.
Notes:No plan provided at inspection.
Deficiency Points: 0
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M001 NO CURRENT EMERGENCY RESPONSE PROGRAM
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS003 | BLACK WILLOW SPRING
91. Spring box has a means to release overflow?
Rule: R309-515-7(7)(d), R309-545-13(1)All junction boxes and collection boxes, must comply with R309-545 with respect to
access openings, venting, and tank overflow. Lids for these spring boxes shall be
gasketed and the box adequately vented.
Notes:Inactive
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS23 SPRING BOX LACKS A MEANS OF PROVIDING OVERFLOW
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS003 | BLACK WILLOW SPRING
98. Is a spring box vent present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect
to venting. Therefore, a junction or collection box requires a vent to be fitted with #14
mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or
covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the
entrance of contaminants, be located and sized to avoid blockage during winter, and
have the end of the vent discharge a minimum of 24 inches above the earth on buried
structures.
Notes:Inactive
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP001 | FOOL CREEK CHLORINATOR
144A. Leak response/repair plan available
Rule: R309-105-7, 8 & 18, R309-100 through
605
Trigger for regulatory followup to address concerns.
Notes:Representative of water system was not the water operator and did not know if they had a
plan available. I havenât been able to get in contact with the operator.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Gaseous Chlorination | TP001 | FOOL CREEK CHLORINATOR
144C. Immediate access to NIOSH respirator available
Rule: R309-520-7(2)(k)(ii)Where 150 pound chlorine cylinders are used, a respirator recommended the National
Institute of Occupational Safety and Health must be available. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:No mask.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TD04 150-POUND CYLINDER FACILITY LACKS IMMEDIATE ACCESS TO NIOSH
RESPIRATOR