HomeMy WebLinkAboutDDW-2025-007301Sanitary Survey - Deficiency Report
PWS Number:UTAH17024 Deficiency Points:30 Survey Date:08/05/2025
Survey Name:EDGE OF EDEN
SUBDIVISION
Surveyor:David Kruse
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH17024 DISTRIBUTION SYSTEM
39. Does the water system have detailed records of cross connection control activities? (inventories of backflow assemblies, devices, and air gaps
installed within the system)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes written records of cross connection control activities.
Notes:To resolve this deficiency update assembly inventory and ensure reduced pressure
assemblies are installed on main service lines on all lots which have connections to both a
private well and the public system.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M006 CCC-LACKS WRITTEN RECORDS OF CCC ACTIVITIES
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH17024 DISTRIBUTION SYSTEM
40. Does the water system have records of on-going enforcement activities? (test history, enforcement activities, hazard assessments)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes test history and documentation of on-going enforcement activities.
Notes:To resolve this deficiency update assembly inventory and ensure reduced pressure
assemblies are installed on main service lines on all lots which have connections to both a
private well and the public system.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M007 CCC-LACKS ON-GOING ENFORCEMENT IMPLEMENTATION