Loading...
HomeMy WebLinkAboutDDW-2025-007290Sanitary Survey - Deficiency Report PWS Number:UTAH17006 Deficiency Points:5 Survey Date:08/06/2025 Survey Name:VISTA GRANDE Surveyor:David Kruse Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | WELL NO 1 74. Wells that pump directly into a distribution system have means to release trapped air from pump discharge piping (for example, pumps directly to a tank, has an air release valve or pump to waste line) Rule: R309-515-6(12)(d)(v)Rule requires a well that pumps directly into the distribution system be equipped with an air release/vacuum relief valve located upstream of the check valve, unless the wellhead valve and piping provide for pumping to waste all trapped air before water is introduced into the distribution system. Notes:still deficient Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SL01 WELL THAT PUMPS DIRECTLY TO DISTRIBUTION LACKS A MEANS TO RELEASE TRAPPED AIR