HomeMy WebLinkAboutDDW-2025-007021Sanitary Survey - Deficiency Report
PWS Number:UTAH23009 Deficiency Points:80 Survey Date:07/22/2025
Survey Name:LINCOLN CULINARY
WATER ASSN
Surveyor:Nagendra Dev
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | MIDDLE CANYON SPRING
60. Area of equal or higher elevation within 50 feet of spring collection devices is fenced.
Rule: R309-515-7(7)(e)Rule requires a stock-tight fence around the spring collection area.
Notes:South end not fenced.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS02 SPRING COLLECTION AREA NOT FENCED
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | MIDDLE CANYON SPRING
62. Spring box has a means to release overflow?
Rule: R309-515-7(7)(d), R309-545-13(1)All junction boxes and collection boxes, must comply with R309-545 with respect to
access openings, venting, and tank overflow. Lids for these spring boxes shall be
gasketed and the box adequately vented.
Notes:Couldn't be verified
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS23 SPRING BOX LACKS A MEANS OF PROVIDING OVERFLOW
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | MIDDLE CANYON SPRING
68B. Spring box lid is gasketed
Rule: R309-515-7(7)(d), R309-545-14 (2)Access openings shall comply with R309-545 and be provided with a cover furnished
with a gasket between the lid and frame. This significant deficiency must be corrected
within 120 days of notification or have a corrective action plan approved by DDW.
Notes:lacks gasket
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS10 SPRING BOX LID LACKS A GASKET
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | MIDDLE CANYON SPRING
69B. Vent has #14 or finer non-corrodible mesh screen and a protective screen/covering if 6-inch diameter or greater.
Rule: R309-515-7(7)(d), R309-545-15(4) and (5)All vents on junction and collection boxes shall comply with R309-545 and be fitted
with No. 14 or finer non-corrodible mesh screen. Vents 6-inch diameter or larger shall
be fitted with additional heavy gage screen or substantial covering to protect the No. 14
mesh screen. This significant deficiency must be corrected within 120 days of
notification or have a corrective action plan approved by DDW.
Notes:Has bigger mesh size (#4)
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS17 SPRING BOX VENT LACKS NO. 14 SCREEN