HomeMy WebLinkAboutDERR-2025-005521 WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
MECHANICAL AND ELECTRONIC LINE LEAK DETECTOR PERFORMANCE TESTS
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This data sheet can be used to test the mechanical line leak detector (MLLD) and electronic line leak detector (ELLD) with submersible turbine
pump (STP) systems. See PEI/RP 1200 Sections 9.1 and 9.2 for test procedures.
Line Number 1 2 3
Product Stored RUL PUL DSL
Leak Detector Manufacturer Incon Incon Incon
Leak Detector Model PLLD PLLD PLLD
Type Of leak Detector
☐MLLD
☒ELLD
☐MLLD
☒ELLD
☐MLLD
☒ELLD
☐MLLD
☐ELLD
MLLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG)
STP full operating pressure
Check valve holding pressure
Line resiliency (ml) (line bleedback volume as measured
from check valve holding pressure to 0 psig)
Step through time in seconds (time the MLLD hesitates at
metering pressure before going to full operating pressure as
measured from 0 sig with no leak induced on the line)
Metering pressure (STP pressure when simulated leak rate 3
gph at 10 psig)
Opening time in seconds (the time the MLLD opens to allow
full pressure after simulated leak is stopped)
Does the STP pressure remain at or below the metering
pressure for at least 60 seconds when the simulated leak is
induced? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Does the leak detector reset (trip) when the line pressure is
bled off to zero psig? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Does STP properly clycle on/off under normal fuel system
operating conditions? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
A “No” answer to any of the above questions indicates that the MLLD fails the test.
ELLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG)
STP full operating pressure 30 28 32
How many test cycles are observed before alarm/shutdown
occurs? 1 1 1
Does the simulated leak cause on alarm? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
A “No” answer to the above question indicates that the ELLD fails the test.
Does the simulated leak cause an STP shutdown? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the in spection
procedure. This procedure is applicable to tank monitor stems that touch the bottom of the tank when in place.
Tank Number 1 2 3
Product Stored RUL PUL DSL
ATG Brand and Model Incon 550 Incon 550 Incon 550
1. Tank Volume, gallons 19,782 7,901 10,420
2. Tank Diameter, inches 118 118 118
3. After removing the ATG from the tank, it has been
inspected and any damaged or missing parts replaced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
4. Float moves freely on the stem without binding? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
5. Fuel float level agree with the value programmed into
the console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
6. Water float level agree with the value programmed into
the console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
7. Inch level from the bottom of the stem when 90% alarm
is triggered? 99 1/8 99 7/8 98 1/2
8. Inch level at which the overfill alarm activates
corresponds with the value programmed in the gauge? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
9. Inch level from the bottom when the water float first
triggers an alarm? 2 2 2
10. Inch level at which the water float alarm activates
corresponds with the value programmed in the gauge? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
If any answers in Lines 3, 4, 5, or 6 are “No” the system has failed the test.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
LIQUID SENSER FUNCTIONALITY TESTING
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This procedure is to determine whether liquid sensors, located in the interstitial spaces of the UST systems, are able to detect the presence of water and fuel. See
PEI/RP1200, Section 8.3 for the test procedure.
Sensor Location UDC 1/2 UDC 3/4 UDC 5/6 UDC 7/8 INT INT STP
Product Stored All All RUL/PUL RUL/PUL RUL PUL/DSL RUL
Type of Sensor
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
Test Liquid ☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
Is the ATG Console clear of any active or
recurring warnings or alarms regarding
the leak sensor? If the sensor is in alarm
and functioning, indicate why.
☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
Is sensor alarm circuit
operational? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
Has sensor been inspected and in good
operating condition? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
When placed in test liquid, does the
sensor trigger an alarm? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
When alarm is trigger, is the sensor
identified on the ATG console? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
Any “No” answers indicate the sensor fails the test.
Test Results: ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail
Comments:
Tester’s Name: Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
LIQUID SENSER FUNCTIONALITY TESTING
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This procedure is to determine whether liquid sensors, located in the interstitial spaces of the UST systems, are able to detect the presence of water and fuel. See
PEI/RP1200, Section 8.3 for the test procedure.
Sensor Location STP STP Fill Fill
Product Stored PUL DSL DSL PUL
Type of Sensor
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
Test Liquid ☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
Is the ATG Console clear of any active or
recurring warnings or alarms regarding
the leak sensor? If the sensor is in alarm
and functioning, indicate why.
☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
Is sensor alarm circuit
operational? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
Has sensor been inspected and in good
operating condition? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
When placed in test liquid, does the
sensor trigger an alarm? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
When alarm is trigger, is the sensor
identified on the ATG console? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
Any “No” answers indicate the sensor fails the test.
Test Results: ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail
Comments: RUL fill sump sensor not programmed.
Tester’s Name: Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
OVERFILL ALARM OPERATION INSPECTION
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the in spection
procedure. This procedure is applicable to tank monitor stems the touch the bottom of the tank when in place.
Tank Number 1 2 3
Product Stored RUL PUL DSL
ATG Brand and Model Incon 550 Incon 550 Incon 550
1. Tank Volume, gallons 19,782 7,901 10,420
2. Tank Diameter, inches 118 118 118
3. Overfill alarm activates in the test mode at the
console? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
4. When activated, overfill alarm can be heard or seen
while delivering to the tank? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
5. After removing the probe from the tank, it has been
inspected and any damaged or missing parts replaced? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
6. Float moves freely on stem without binding? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
7. Moving product level float up the stem trigger
alarm? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
8. Inch level from bottom of stem when 90% alarm is
triggered? 99 1/8 99 7/8 98 1/2
9. Tank volume at inch level in Line 8. 17,803 7,110 9,378
10. Calculate (Line 9 / Line 1) X 100 90% 90% 90%
11. Is line 10 less than 90%? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
12. Fuel float level on the console agrees with the
gauge stick reading? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
13. Overfill alarm activates at any product level above
90% tank capacity? ☐Yes ☒No ☐Yes ☒No ☐Yes ☒No ☐Yes ☐No
If any answers in Lines 3, 4, 5, 6, 7, or 11 are “No,” or Line 13 is “Yes,” the system has failed the test.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
SPILL BUCKET INTEGRITY TESTING HYDROSTATIC TEST METHOD
SINGLE- AND DOUBLE-WALLED VACUUM TEST METHOD
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This procedure is to test the leak integrity of single- and double-walled spill buckets. See PEI/RP1200 Section 6.2 for hydrostatic test
method, Section 6.3 for single-walled vacuum test method and Section 6.4 for double-walled vacuum test method.
Tank Number 1 1 2 2
Product Stored RUL RUL PUL PUL
Spill Bucket Capacity 5-Gallon 5-Gallon 5-Gallon 5-Gallon
Manufacturer OPW OPW OPW OPW
Construction ☒Double-walled
☐Single-walled
☒Double-walled
☐Single-walled
☐Double-walled
☒Single-walled
☐Double-walled
☒Single-walled
Test Type
☐Hydrostatic
☒Vacuum
☒Double-walled
☐Single-walled
☐Hydrostatic
☒Vacuum
☒Double-walled
☐Single-walled
☒Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☒Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
Spill Bucket Type ☒Product
☐Vapor
☐Product
☒Vapor
☒Product
☐Vapor
☐Product
☒Vapor
Liquid and debris remove from spill
bucket?* ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
Visual Inspection (no cracks, loose
parts or separation of the bucket from
the fill pipe.)
☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
Tank Riser cap included in test? ☐Yes ☐No
☒NA
☐Yes ☐No
☒NA
☒Yes ☐No
☐NA
☒Yes ☐No
☐NA
Drain valve included in test? ☐Yes ☐No
☒NA
☐Yes ☐No
☒NA
☒Yes ☐No
☐NA
☐Yes ☐No
☒NA
Starting Level 15” WC 15” WC 10 3/4” 8 1/8”
Test Start Time 0 0 2:10 2:10
Ending Level 14” WC 14” WC 10 3/4” 7 5/8”
Test End Time 5 5 3:10 3:10
Test Period 5-Minute 5-Minute 1-Hour 1-Hour
Level Change -1” WC -1” WC 0” -1/2”
Pass/fail criteria: Must pass visual inspection. Hydrostatic: Water level drop of less than 1/8 inch; Vacuum single-walled only: Maintain at least 26 inches water
column; Vacuum double-walled: maintain at least 12 inches water column.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☒Fail
Comments:
*All liquids and debris must be disposed of properly
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
SPILL BUCKET INTEGRITY TESTING HYDROSTATIC TEST METHOD
SINGLE- AND DOUBLE-WALLED VACUUM TEST METHOD
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This procedure is to test the leak integrity of single- and double-walled spill buckets. See PEI/RP1200 Section 6.2 for hydrostatic test
method, Section 6.3 for single-walled vacuum test method and Section 6.4 for double-walled vacuum test method.
Tank Number 3
Product Stored DSL
Spill Bucket Capacity 5-Gallon
Manufacturer OPW
Construction ☐Double-walled
☒Single-walled
☐Double-walled
☐Single-walled
☐Double-walled
☐Single-walled
☐Double-walled
☐Single-walled
Test Type
☒Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☐Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☐Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☐Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
Spill Bucket Type ☒Product
☐Vapor
☐Product
☐Vapor
☐Product
☐Vapor
☐Product
☐Vapor
Liquid and debris remove from spill
bucket?* ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Visual Inspection (no cracks, loose
parts or separation of the bucket from
the fill pipe.)
☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Tank Riser cap included in test? ☒Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
Drain valve included in test? ☒Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
Starting Level 9 1/8”
Test Start Time 2:10
Ending Level 9 1/8”
Test End Time 3:10
Test Period 1-Hour
Level Change 0”
Pass/fail criteria: Must pass visual inspection. Hydrostatic: Water level drop of less than 1/8 inch; Vacuum single-walled only: Maintain at least 26 inches water
column; Vacuum double-walled: maintain at least 12 inches water column.
Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments:
*All liquids and debris must be disposed of properly
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
CONTAINMENT SUMP INTEGRITY TESTING
HYDROSTATIC TESTING METHOD
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This procedure is to test the leak integrity of containment sumps. See PEI/RP1200 Section 6.5 for the inspection procedure.
Containment Sump ID RUL STP PUL STP DSL STP UDC 1/2
Containment Sump Material FRP FRP FRP Poly
Liquid and debris removed from sump?* ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
Visual Inspection (No cracks, loose parts or separation of
the containment sump.) ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No
Containment Sump Depth 4.87 5.2 5.37 2.4
Height From Bottom to Top of Highest Penetration 1.75 1.64 1.81 0.43
Starting Water Level 2.17 2.31 2.27 0.87
Test Start Time 1:35 12:57 12:39 2:04
Ending Water Level 2.17 2.31 2.27 0.87
Test End Time 2:35 1:57 1:39 3:04
Test Period (Minimum test time: 1 hour) 1-Hour 1-Hour 1-Hour 1-Hour
Water Level change 0” 0” 0” 0”
Pass/fail Criteria: Must pass visual inspection. Water level drop of less than 1/8 inch.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail
Comments:
*All Liquids and debris must be disposed of properly.
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
CONTAINMENT SUMP INTEGRITY TESTING
HYDROSTATIC TESTING METHOD
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This procedure is to test the leak integrity of containment sumps. See PEI/RP1200 Section 6.5 for the inspection procedure.
Containment Sump ID UDC 3/4 UDC 5/6 UDC 7/8
Containment Sump Material Poly Poly Poly
Liquid and debris removed from sump?* ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
Visual Inspection (No cracks, loose parts or separation of
the containment sump.) ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
Containment Sump Depth 2.4 2.43 2.43
Height From Bottom to Top of Highest Penetration 0.55 0.58 0.59
Starting Water Level 0.95 1.01 1.01
Test Start Time 2:03 2:12 2:12
Ending Water Level 0.95 1.01 1.01
Test End Time 3:03 3:12 3:12
Test Period (Minimum test time: 1 hour) 1-Hour 1-Hour 1-Hour
Water Level change 0” 0” 0”
Pass/fail Criteria: Must pass visual inspection. Water level drop of less than 1/8 inch.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
*All Liquids and debris must be disposed of properly.
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PIPING SECONDARY CONTAINMENT INTEGRITY TESTING
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This procedure is to test the integrity of the interstitial space of double-walled piping. See PEI/RP1200 Section 5 for the test procedure.
Tank Number 1 1 2 2
Piping Run East West East West
Piping Material Flex D/W Flex D/W Flex D/W Flex D/W
Product Stored RUL RUL PUL PUL
Test Start Time 1:35 1:35 12:57 12:57
Initial Test Pressure, psi (test procedure specifies 5 psi.) 5 5 5 5
Test End Time 2:35 2:35 1:57 1:57
Final Test Pressure, psi 5 5 5 5
Pressure Change
(No reduction in pressure allowed for pass.) 0 psi 0 psi 0 psi 0 psi
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PIPING SECONDARY CONTAINMENT INTEGRITY TESTING
Facility Name: Smith’s #94 Owner: Smith’s Food and Drug Centers, Inc.
Address: 479 South 600 East Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84102 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002468 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 5/28/25
This procedure is to test the integrity of the interstitial space of double-walled piping. See PEI/RP1200 Section 5 for the test procedure.
Tank Number 3 1
Piping Run East East
Piping Material Flex D/W Flex D/W
Product Stored DSL RUL
Test Start Time 12:39 12:39
Initial Test Pressure, psi (test procedure specifies 5 psi.) 5 5
Test End Time 1:39 1:39
Final Test Pressure, psi 5 5
Pressure Change
(No reduction in pressure allowed for pass.) 0 psi 0 psi
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature