AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name: IRS Owner: IRS Ogden Service Center
Address: 1160 West 1200 South Address: 1160 West 1200 South, Mail Stop 1473
City, State, Zip: Ogden, Utah 84409 City, State, Zip: Ogden, Utah 84201
Facility I.D.#: 1200064 Phone #: 801-393-4870
Testing Company: Westech Phone #: 801-266-2545 Date: 7/9/25
This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection
procedure. This procedure is applicable to tank monitor stems that touch the bottom of the tank when in place.
Tank Number 4 (South) 5 (North)
Product Stored Red DSL Red DSL
ATG Brand and Model EMKO Incon TS1001
1. Tank Volume, gallons 12,000 10,000
2. Tank Diameter, inches 89 3/4” 89 3/4”
3. After removing the ATG from the tank, it has been
inspected and any damaged or missing parts replaced? ☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
4. Float moves freely on the stem without binding? ☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
5. Fuel float level agree with the value programmed into
the console? ☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
6. Water float level agree with the value programmed into
the console? ☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
7. Inch level from the bottom of the stem when 90% alarm
is triggered? 75 74 3/4”
8. Inch level at which the overfill alarm activates
corresponds with the value programmed in the gauge? ☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
9. Inch level from the bottom when the water float first
triggers an alarm? 1.5 4
10. Inch level at which the water float alarm activates
corresponds with the value programmed in the gauge? ☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
If any answers in Lines 3, 4, 5, or 6 are "No" the system has failed the test.
Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
LIQUID SENSER FUNCTIONALITY TESTING
Facility Name: IRS Owner: IRS Ogden Service Center
Address: 1160 West 1200 South Address: 1160 West 1200 South, Mail Stop 1473
City, State, Zip: Ogden, Utah 84409 City, State, Zip: Ogden, Utah 84201
Facility I.D.#: 1200064 Phone #: 801-393-4870
Testing Company: Westech Phone #: 801-266-2545 Date: 7/9/25
This procedure is to determine whether liquid sensors, located in the interstitial spaces of the UST systems, are able to detect the presence of water and fuel. See
PEI/RP1200, Section 8.3 for the test procedure.
Sensor Location Tank 4 (S) INT Tank 4 (S) STP Tank 4 (S)
East Sump
Tank 4 (S)
West Sump Tank 5 (N)
INT
Tank 5 (N)
STP
Product Stored Red DSL Red DSL Red DSL Red DSL Red DSL Red DSL
Type of Sensor
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
Test Liquid ☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☐ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
Is the ATG Console clear of any active or
recurring warnings or alarms regarding
the leak sensor? If the sensor is in alarm
and functioning, indicate why.
☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
Is sensor alarm circuit
operational? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
Has sensor been inspected and in good
operating condition? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
When placed in test liquid, does the
sensor trigger an alarm? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
When alarm is trigger, is the sensor
identified on the ATG console? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☐ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
Any “No” answers indicate the sensor fails the test.
Test Results: ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☐ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail
Comments:
Tester’s Name: Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
SPILL BUCKET INTEGRITY TESTING HYDROSTATIC TEST METHOD
SINGLE- AND DOUBLE-WALLED VACUUM TEST METHOD
Facility Name: IRS Owner: IRS Ogden Service Center
Address: 1160 West 1200 South Address: 1160 West 1200 South, Mail Stop 1473
City, State, Zip: Ogden, Utah 84409 City, State, Zip: Ogden, Utah 84201
Facility I.D.#: 1200064 Phone #: 801-393-4870
Testing Company: Westech Phone #: 801-266-2545 Date: 7/9/25
This procedure is to test the leak integrity of single- and double-walled spill buckets. See PEI/RP1200 Section 6.2 for hydrostatic test
method, Section 6.3 for single-walled vacuum test method and Section 6.4 for double-walled vacuum test method.
Tank Number 4 (South) 5 (North)
Product Stored Red DSL Red DSL
Spill Bucket Capacity 5-Gallon 5-Gallon
Manufacturer OPW OPW
Construction ☐Double-walled
☒Single-walled
☐Double-walled
☐Single-walled
☒Double-walled
☐Single-walled
☐Double-walled
☐Single-walled
Test Type
☒Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☐Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☒Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
☐Hydrostatic
☐Vacuum
☐Double-walled
☐Single-walled
Spill Bucket Type ☒Product
☐Vapor
☐Product
☐Vapor
☒Product
☐Vapor
☐Product
☐Vapor
Liquid and debris remove from spill
bucket?* ☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
Visual Inspection (no cracks, loose
parts or separation of the bucket from
the fill pipe.)
☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
Tank Riser cap included in test? ☒Yes ☐No
☐NA
☐Yes ☐No
☐NA
☒Yes ☐No
☐NA
☐Yes ☐No
☐NA
Drain valve included in test? ☐Yes ☐No
☒NA
☐Yes ☐No
☐NA
☐Yes ☐No
☒NA
☐Yes ☐No
☐NA
Starting Level 10 3/4” 13 3/4”
Test Start Time 10:20 11:26
Ending Level 10 3/4” 13 3/4”
Test End Time 11:20 12:26
Test Period 1-Hour 1-Hour
Level Change 0” 0”
Pass/fail criteria: Must pass visual inspection. Hydrostatic: Water level drop of less than 1/8 inch; Vacuum single-walled only: Maintain at least 26 inches water
column; Vacuum double-walled: maintain at least 12 inches water column.
Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
*All liquids and debris must be disposed of properly
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
UST OVERFILL EQUIPMENT INSPECTION
AUTOMATIC SHUTOFF DEVICE AND BALL FLOAT VALVE
Facility Name: IRS Owner: IRS Ogden Service Center
Address: 1160 West 1200 South Address: 1160 West 1200 South, Mail Stop 1473
City, State, Zip: Ogden, Utah 84409 City, State, Zip: Ogden, Utah 84201
Facility I.D.#: 1200064 Phone #: 801-393-4870
Testing Company: Westech Phone #: 801-266-2545 Date: 7/9/25
This data sheet is for inspecting automatic shutoff devices and ball float valve. See PEI/RP1200 Section 7 for inspection procedures.
Product Grade Red DSL Red DSL
Tank Number 4 (South) 5 (North)
Tank Volume, gallons 12,000 10,000
Tank Diameter, inches 89 3/4 89 3/4
Overfill Prevention Device Brand OPW OPW
Type ☒ Automatic
Shutoff Device
☐ Ball Float
Valve
☐ Automatic
Shutoff Device
☐ Ball Float
Valve
☒ Automatic
Shutoff Device
☐ Ball Float
Valve
☐ Automatic
Shutoff Device
☐ Ball Float
Valve
AUTOMATIC SHUTOFF DEVICE INSPECTION
1. Drop tube removed from tank? ☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
2. Drop tube and float mechanisms free of debris? ☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
3. Float moves freely without binding and poppet moves
into flow path? ☒Yes ☐No ☐Yes ☐No ☒Yes ☐No ☐Yes ☐No
4. Bypass valve in the drop tube open and free of
blockage (if present)?
☒Yes ☐No
☐Not Present
☐Yes ☐No
☐Not Present
☒Yes ☐No
☐Not Present
☐Yes ☐No
☐Not Present
5. Flapper adjusted to shut off flow at 95% capacity? * ☐Yes ☒No ☐Yes ☐No ☐Yes ☒No ☐Yes ☐No
A "No" to any item in Lines 1-5 indicates a test failure.
BALL FLOAT VALVE INSPECTION**
1. Tank top fitting vapor-tight and leak free? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
2. Ball float cage free of debris? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
3. Ball free of holes and cracks and moves freely in cage? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
4. Vent hole in pipe open and near top of tank? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
5. Ball float pipe proper length to restrict flow to 90%
capacity? *** ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
A "No" to any item in Lines 1-5 indicates a test failure.
Test Results ☐Pass ☒Fail ☐Pass ☐Fail ☐Pass ☒Fail ☐Pass ☐Fail
Comments:
*Use manufacturer’s suggested procedure for determining if automatic shutoff device will shut off flow at 95% capacity.
**If a ball float valve is found to fail the inspection, another method of overfill must be used.
***Use manufacturer’s suggested procedure for determining if flow restriction device will restrict flow at 90% capacity.
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature