HomeMy WebLinkAboutDDW-2025-006674Sanitary Survey - Deficiency Report PWS Number: UTAH23086 Deficiency Points: 240 Survey Date: 03/25/2025 Survey Name: SKULL VALLEY WATER GROUP LLC Surveyor: Chris Martin Storage Tanks | ST001 | 300K RAW WATER - NOT POTABLE
122C. Access opening lid properly gasketed Rule: R309-545-14(2)
Notes: Access opening doesn't appear to have a gasket. Deficiency Points: 25
Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET
BETWEEN THE LID AND FRAME
Storage Tanks | ST001 | 300K RAW WATER - NOT POTABLE 123. Access opening locked Rule: R309-545-14(3) Rule requires the lid to any access opening to have a locking device. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes: The access opening is bolted but was found to be unbolted at time of survey.
Deficiency Points: 25 Days until points become effective on IPS: 120
Date Completed 14/17/2025
Storage Tanks | ST001 | 300K RAW WATER - NOT POTABLE 124. Roof or wall penetrations sealed Rule: R309-545-6(1) and 545-9 Rule requires openings in a storage tank roof or top, designed to accommodate control apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have additional proper shielding to prevent vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW.
Notes: There is significant corrosion near the tank vent that needs to be assessed and repaired. Deficiency Points: 100 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO
UNSEALED OPENINGS ON TANK ROOF OR SIDEWALLS
Date Completed 6/25/2025
Storage Tanks | ST001 | 300K RAW WATER - NOT POTABLE128B. Overflow line covered with #4 mesh non-corrodible screen Rule: R309-545-13(3) Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens installed at a location least susceptible to damage by vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW.
Notes: Overflow needs a new screen. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN
Date Completed 4/3/2025
Sanitary Survey - Deficiency Report PWS Number: UTAH23039 Deficiency Points: 530 Survey Date: 03/25/2025 Survey Name: US MAGNESIUM Surveyor: Chris Martin
Storage Tanks | ST001 | 150K DEMIN TANK 68. Roof or wall penetrations sealed Rule: R309-545-6(1) and 545-9 Rule requires openings in a storage tank roof or top, designed to accommodate control apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have additional proper shielding to prevent vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW.
Notes: There are holes in the roof of the tank. Deficiency Points: 100
Days until points become effective on IPS: 120 SDWIS Deficiency Description: V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO
UNSEALED OPENINGS ON TANK ROOF OR SIDEWALLS
Date Completed 5/14/2025
Storage Tanks | ST002 | I MG TANK (RAW WATER) 79C. Vent covered with #14 or finer non-corrodible mesh screen. Rule: R309-545-15(4) Rule requires a water storage tank vent to be fitted with #14 mesh or finer noncorrodible screen and vents 6-inches or greater in diameter to be fitted with additional heavy gauge screen or substantial covering to protect the #14 mesh screen from vandalism or damage. This significant deficiency must be corrected within 120 days of notification or have a compliance action plan approved by DDW.
Notes: Screen looks damaged from distance. Deficiency Points: 25 Days until points become effective on IPS: 120
Date Completed4/23/2025
Storage Tanks | ST002 | I MG TANK (RAW WATER) 80C. Access opening lid properly gasketed Rule: R309-545-14(2) Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW.
Notes: Bolted lid does not appear to have a gasket. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET
BETWEEN THE LID AND FRAME
Date Completed 4/17/2025
Storage Tanks | ST002 | I MG TANK (RAW WATER) 82. Roof or wall penetrations sealed Rule: R309-545-6(1) and 545-9 Rule requires openings in a storage tank roof or top, designed to accommodate control apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have additional proper shielding to prevent vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes: There is signs of leakage along the bottom of the tank. Deficiency Points: 100 Days until points become effective on IPS: 120
SDWIS Deficiency Description: V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO UNSEALED OPENINGS
ON TANK ROOF OR SIDEWALLS
Storage Tanks | ST002 | I MG TANK (RAW WATER) 83. Area surrounding ground-level or buried storage tank is graded to prevent surface water from standing within 50 feet. Rule: R309-545-7(4) Rule requires the area surrounding a ground-level or buried water storage tank be graded in a manner to prevent surface water from standing within 50 feet of the tank. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes: Surface water is ponded around the tank. Deficiency Points: 25 Days until points become effective on IPS: 120
SDWIS Deficiency Description: V001 STORAGE TANK SURROUNDING AREA NOT GRADED TO PREVENT STANDINGWATER WITHIN 50 FEET OF THE TANK
Date Completed 6/26/2025
Storage Tanks | ST003 | 300K FIRE FLOW TANK (RAW WATER) 94C. Access opening lid properly gasketed Rule: R309-545-14(2) Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW.
Notes: There is no gasket on the lid. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME Storage Tanks | ST003 | 300K FIRE FLOW TANK (RAW WATER) 95. Access opening locked Rule: R309-545-14(3) Rule requires the lid to any access opening to have a locking device. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW.
Notes: This is a bolted tank lid but it is currently unbolted. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V029 STORAGE TANK ACCESS OPENING LACKS A LOCK
Date Completed 4/17/2025
Storage Tanks | ST003 | 300K FIRE FLOW TANK (RAW WATER) 96. Roof or wall penetrations sealed Rule: R309-545-6(1) and 545-9 Rule requires openings in a storage tank roof or top, designed to accommodate control apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have additional proper shielding to prevent vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes: There is corrosion near the tank vent with apparent holes. Deficiency Points: 100 Days until points become effective on IPS: 120
SDWIS Deficiency Description: V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO UNSEALED OPENINGS ON TANK ROOF OR SIDEWALLS
Date Completed 6/25/2025
Storage Tanks | ST003 | 300K FIRE FLOW TANK (RAW WATER) 100B. Overflow line covered with #4 mesh non-corrodible screen Rule: R309-545-13(3) Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens installed at a location least susceptible to damage by vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW.
Notes: There is a hole in the screen.
Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4
SCREEN
Date Completed 4/3/2025