HomeMy WebLinkAboutDDW-2025-006625Sanitary Survey - Deficiency Report
PWS Number:UTAH26057 Deficiency Points:50 Survey Date:07/16/2025
Survey Name:TIMBER LAKES WATER SSD Surveyor:Danielle Zebelean
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Management and Operations | DS001 | UTAH26057 DISTRIBUTION SYSTEM
28B. System lacks more than 20% of required source capacity
Rule: R309-510-7(1)Rule requires a water system's source capacity to legally and physically meet the peak
day demand and the average yearly demand. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:System lacks 60% of required source capacity. Directed Jody to fill out a CAA to gather
system specific sizing information and request a temporary exception to give them time to
gather three years of peak flow data.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S094 SYSTEM LACKS MORE THAN 20% OF REQUIRED SOURCE CAPACITY