HomeMy WebLinkAboutDAQ-2024-007380Clean Harbors Aragonite, LLC
I 1600 North Aptus Road
Aragonite, UT 84029
435.884.8100
www.cleanharbors.com
FedEx # 7726 9481 5210 DIVISION OF AIR QUAL,II
Jily 10,2023
Mr. Bryce Bird
Division of Air Quality (DAQ)
Department of Environmental Quality
195 North 1950 West
P.O. Box 144880
Salt Lake city, UT 84414-4880
RE: Semi-Annual Startup, Shutdown, and Malfunction Report
Clean Harbors Aragonite, LLC
Title V Operating Permit 4500048004
Dear Mr. Bird,
In accordance with Title V Permit condition II.B.2.k.3(i), Clean Harbors Aragonite, LLC (CHA) is
submitting the Semi-Annual Startup, Shutdown, and Malfunction Report for January through June
of 2023. This report requires CHA to submit all startups, shutdowns, and malfunctions that
occurred in the reporting period and include the number, duration, and a brief description of each
occurrence. This information can be seen in Table 1. All occurrences were handled consistent with
the facilities Startup, Shutdown, and Malfunction Plan.
Table 1: Start-Shutdow nd Malfunctions
t,TAH DEPARTMENT OF
EI.IVIBONMENTAL QUAUT'{
JUL 12 ..,(- .,.t
u Ilr lt a
SSMP Reason SSMP Cause Number Duration
(hr:min:sec)
Kiln Temperature Cutoff
AWFCO - (product fuel didn't
maintain heat ouick enoush)I 0l : 19:59
Smoke Blinds Infrareds 1 00:03:48
No Fuel (pump or lance failures)J 04:30:36
Afterburner Temperature Cutoff No Fuel (pump failures)2 0l :17:00
Activated Carbon Below Permissive
Cutoff Plugged Line 6 08:01:28
I't and 2nd Stage Low pH and 2nd Stage
Rundown PH
Soda Ash Plussed Line 2 0l:24:01
oH Probes Fail 2 00:38:01
Soda Ash Pump Failed 1 00:19:00
l" and 2no Stage Brine Flow Rate Valve or Pine Failure 2 00:00:04
High Combustion Zone Pressure Cutoff
Builduo Fall 8 00:00:23
ID Fan Failure 00:00:53
Power Failure I 00:00:37
Kiln Seal Issue I 00:00:01
"People and Technologt Creating a Better Environment"
REVIEWEDInitials: Date: March 27, 2024Compliance Status: OKFile #: 10725 (B2)
SSMP Reason SSMP Cause Number Duration
(hr:min:sec)
Baghouse Pressure Drop/Opacity Cutoff
Bashouse Bas Failure 7 00:00:20
Dust in Outlet Duct 8 00:00:49
Leakins Bypass Damper 00:00:02
Pressure Tubins Plugeed 00:00: l7
High Instrument Span - Baghouse Inlet
Pressure Baghouse Bag Failure 2 00:00:07
High Instrument Span - Activated
Carbon Feed Rate
Carbon Build Up Around Platform l0 00:06:40
Power Failure Utilitv Power Loss 4 03:29:32
In accordance with Permit Condition I.K and Utah Administrative Code R307-415-5d, I certiff
under penalty of law that this document and all affachments were prepared under my direct
supervision in accordance with a system designed to assure that qualified personnel properly gather
and evaluate the information submitted. Based upon my inquiry of persons or persons who manage
the system, or those persons directly responsible for gathering the information submitted is, to the
best of my knowledge and belief, true, accurate and complete. I am aware that there are significant
penalties for submitting false information, including the possibility of imprisonment for known
violations.'wh
William L. Simmons
Facility GM III
Clean Harbors Aragonite, LLC
I1600 North Atpus Road
PO Box 1339
Grantsville, Utah 84029 -1339
(o) 435.8a4.8351
(c) 870.310.6029
simmons. william@cleanharbors. com
www.cleanharbors.com