Loading...
HomeMy WebLinkAboutDDW-2025-006479Sanitary Survey - Deficiency Report PWS Number:UTAH13061 Deficiency Points:55 Survey Date:07/16/2025 Survey Name:NAVAJO LAKE CAMPGROUNDS Surveyor:Tom McOmie Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS001 | BOY SCOUT SPRING 67. No deep-rooted vegetation is within the 50 ft collection area. Rule: R309-515-7(7)(f)All deep-rooted vegetation within the fenced collection area shall be removed by a means not negatively affecting water quality. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Need to clear out some small Aspin trees. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS07 DEEP ROOTED VEGETATION IN SPRING COLLECTION AREA Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | BOY SCOUT SPRING 69. Is a spring collection box present? ... if yes, answer the following question(s) Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box to permit spring inspection and testing. Notes:Existing deficiency from 7/29/2019 Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | BOY SCOUT SPRING 71. Spring has a permanent flow-measuring device. Rule: R309-515-7(7)(h)Rule requires a spring to have a permanent flow measuring device. Notes:Existing deficiency from 7/29/2019 Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS01 LACKS A PERMANENT DEVICE FOR MEASURING SPRING FLOW Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS002 | OLSEN SPRING 86. Spring has a permanent flow-measuring device. Rule: R309-515-7(7)(h)Rule requires a spring to have a permanent flow measuring device. Notes:Existing deficiency from 7/29/2019 Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS01 LACKS A PERMANENT DEVICE FOR MEASURING SPRING FLOW Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Liquid Hypochlorination | TP001 | BOY SCOUT SPRINGS CHLORINATOR 183. There are adequate spill containment provisions for acid and caustic liquids. Rule: R309-525-11(6)(a)(iv)(B), R309-525- 11(8)(b)(viii) Rule requires liquid chemical storage tanks to have an overflow and receiving basin or drain capable of receiving accidental spills or overflows, and meeting all the requirements of R309-525-23. Notes:Needs spill overflow containment Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR OVERFLOWS