Loading...
HomeMy WebLinkAboutDDW-2025-006468Sanitary Survey - Deficiency Report PWS Number:UTAH13022 Deficiency Points:125 Survey Date:07/15/2025 Survey Name:DUCK CREEK CAMPGROUND Surveyor:Tom McOmie Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | TANK 1 84C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Tank lid has a gasket but needs to have a thicker one. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | TANK 1 86. Roof or wall penetrations sealed Rule: R309-545-6(1) and 545-9 Rule requires openings in a storage tank roof or top, designed to accommodate control apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have additional proper shielding to prevent vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Conduit needs to be repaired. The joints are broken and has created openings into the tank. Deficiency Points: 100 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO UNSEALED OPENINGS ON TANK ROOF OR SIDEWALLS