HomeMy WebLinkAboutDDW-2025-006450Sanitary Survey - Deficiency Report
PWS Number:UTAH09093 Deficiency Points:30 Survey Date:07/09/2025
Survey Name:BEAVER DAM VILLAGE SSD Surveyor:Brent Arns
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST005 | STORAGE FACILITY (25K #1)
186. Are access openings present? ... if yes, answer the following question(s)
Rule: R309-545-14 and 14(1)Rule requires drinking water storage tanks to be designed with reasonably convenient
access to the interior for cleaning and maintenance.
Notes:Tank is installed in underground vault, vault has access hatch but no direct access hatch to
tank
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: VL03 STORAGE TANK LACKS AN ACCESS OPENING LOCATED ABOVE THE LEVEL OF
THE OVERFLOW FOR TANK O&M
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST006 | STORAGE FACILITY (25K #2)
200. Are access openings present? ... if yes, answer the following question(s)
Rule: R309-545-14 and 14(1)Rule requires drinking water storage tanks to be designed with reasonably convenient
access to the interior for cleaning and maintenance.
Notes:Tank is installed in underground vault, vault has access hatch but no direct access hatch to
tank
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: VL03 STORAGE TANK LACKS AN ACCESS OPENING LOCATED ABOVE THE LEVEL OF
THE OVERFLOW FOR TANK O&M