Loading...
HomeMy WebLinkAboutDDW-2025-006450Sanitary Survey - Deficiency Report PWS Number:UTAH09093 Deficiency Points:30 Survey Date:07/09/2025 Survey Name:BEAVER DAM VILLAGE SSD Surveyor:Brent Arns Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST005 | STORAGE FACILITY (25K #1) 186. Are access openings present? ... if yes, answer the following question(s) Rule: R309-545-14 and 14(1)Rule requires drinking water storage tanks to be designed with reasonably convenient access to the interior for cleaning and maintenance. Notes:Tank is installed in underground vault, vault has access hatch but no direct access hatch to tank Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: VL03 STORAGE TANK LACKS AN ACCESS OPENING LOCATED ABOVE THE LEVEL OF THE OVERFLOW FOR TANK O&M Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST006 | STORAGE FACILITY (25K #2) 200. Are access openings present? ... if yes, answer the following question(s) Rule: R309-545-14 and 14(1)Rule requires drinking water storage tanks to be designed with reasonably convenient access to the interior for cleaning and maintenance. Notes:Tank is installed in underground vault, vault has access hatch but no direct access hatch to tank Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: VL03 STORAGE TANK LACKS AN ACCESS OPENING LOCATED ABOVE THE LEVEL OF THE OVERFLOW FOR TANK O&M